| 2006-11-03 11:32:03 | UNSAT |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (NOTE: THE SUBMITTED DRAWING IS NOT AN |
| | ISOMETRIC AND DOES NOT INDICATE ALL CUT SECTIONS OF |
| | PIPE OR CORRESPONDING LENGTHS. PLEASE SEE THE ISOMETRIC |
| | EXAMPLE OF THE SUBMITTED GAS SYSTEM WITH THE PROVIDED |
| | INFORMATION. PLEASE PROVIDE ALL ABOVE GROUND PIPE |
| | LENGTHS AND INDICATE THE EXISTING GAS WITH MP |
| | REGULATORS TO SAID RESIDENCE. PLEASE REFERENCE THE |
| | ATTACHED PERMIT INFORMATION INDICATING THAT SAID |
| | ADDRESS HAS GAS.) |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. (NOTE: PLEASE |
| | INDICATE ALL ABOVE GROUND MATERIAL TYPES.) |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (NOTE: SAID ADDRESS HAS EXISTING GAS, PLEASE |
| | PROVIDE EXISTING BTU LOAD.) |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (NOTE: PLEASE PROVIDE THE |
| | EXISTING SYSTEMS LONGEST LENGTH) |
| | |
| | END OF COMMENTS: |
| | |