Plan Review Details - Permit 06101081
Plan Review Stops For Permit 06101081
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-31 Cont ID  
Sent By jwitmer Date 2007-10-31 Time 14:28 Rev Time 0.55
Received By jwitmer Date 2007-10-31 Time 14:28 Sent To  
Notes
2007-10-31 14:29:34BUILDING PLAN REVIEW
 PERMIT: 06101081
 ADD: 2905 45TH ST
 CONT: FIRST FLORIDA CONSTRUCTION
 TEL: (813)881-0607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1) PLANS HAVE WHITE OUT USED ONSHEETS2 & 4.
 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
  
 2) SHEET# 4 INDICATES EGRESS LIGHTS ON A 1000W
 DIMMER.1006.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL
 BE CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE. ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 PLACES AND FOR SUCH PERIODS OF TIME AS REQUIRED TO
 MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED. EXCEPTIONS: AUTOMATIC MOTION
 SENSOR-TYPE LIGHTING SWITCHES SHALL BE PERMITTED WITHIN
 THE MEANS OF EGRESS, PROVIDED THAT SWITCH CONTROLLERS
 ARE EQUIPPED FOR FAIL-SAFE OPERATION, ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION AND THE
 MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN
 THE AREA SERVED BY THE LIGHTING UNITS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-26 Cont ID  
Sent By jwitmer Date 2007-08-26 Time 13:46 Rev Time 0.55
Received By jwitmer Date 2007-08-26 Time 13:46 Sent To FIRE
Notes
2007-08-26 13:58:57BUILDING PLAN REVIEW
 PERMIT: 06101081
 ADD: 2905 45TH ST
 CONT: FIRST FLORIDA CONSTRUCTION
 TEL: (813)881-0607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PLANS HAVE WHITE OUT USED ONSHEETS2 & 4.
 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
  
 2) SHEET# 4 INDICATES EGRESS LIGHTS ON A 1000W
 DIMMER.1006.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL
 BE CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE. ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 PLACES AND FOR SUCH PERIODS OF TIME AS REQUIRED TO
 MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED. EXCEPTIONS: AUTOMATIC MOTION
 SENSOR-TYPE LIGHTING SWITCHES SHALL BE PERMITTED WITHIN
 THE MEANS OF EGRESS, PROVIDED THAT SWITCH CONTROLLERS
 ARE EQUIPPED FOR FAIL-SAFE OPERATION, ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION AND THE
 MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN
 THE AREA SERVED BY THE LIGHTING UNITS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-09 Cont ID  
Sent By jwitmer Date 2007-02-09 Time 06:47 Rev Time 1.11
Received By jwitmer Date 2007-02-09 Time 06:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By jwitmer Date 2006-11-22 Time 15:43 Rev Time 1.55
Received By jwitmer Date 2006-11-22 Time 15:38 Sent To  
Notes
2006-11-22 16:53:30BUILDING PLAN REVIEW
 PERMIT: 06101081
 ADD: 2905 45TH ST
 CONT: FIRST FLORIDA CONSTRUCTION
 TEL: (813)881-0607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) 2004 FL EXISTING BLDG CODE WHAT LEVEL
 OF CONSTRUCTION IS BEING COMPLETED?
  
 5) PROVIDE THE OCCUPANT LOAD FOR THE
 MEZZANINE AREA? ALSO PROVIDE A LIFE SAFETY
 PLAN INDICATING THE NUMBER OF OCCUPANTS
 AND WHICH STAIRS THEY WILL BE USING.
 DEPENDING ON THE RESULTS OF THE QUESTIONS ABOVE THE
 MONUMENTAL STAIRS MAY HAVE ADDITIONAL COMMENTS.
  
 6) THE SECOND LEVEL OF THE MEZZANINE INDICATES VARIOUS
  
 CUBICLE ENCLOSURES, THE ENCLOSURES THAT ARE LOCATED
 NEXT
 TO THE TOP OF THE SHEET CUT OFF THE DIRECT ACCESS TO AN
 EXIT
 FROM THE MEZZANINE LEVEL.505.4(EXCEPTION# 2). A
 MEZZANINE
 HAVING TWO OR MORE MEANS OF EGRESS IS NOT REQUIRED TO
 BE OPEN
 TO THE ROOM IN WHICH THE MEZZANINE IS LOCATED, IF AT
 LEAST ONE OF
 THE MEANS OF EGRESS PROVIDES DIRECT ACCESS TO AN EXIT
 FROM THE
 MEZZANINE LEVEL.
  
 7) RAISED SEATING AREA BY THE NEW GLASS WALL, A NEW
 STAIR TO THIS AREA
 IS BEING ALTERED, 11-4.1.6(1)(B) ACCESSIBLE BUILDINGS,
 ALTERAATIONS:
 IF EXESTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH
 SUCH ALTERED ELEMENT, SPACE, FEATURE,OR AREA SHALL
 COMPLY WITH THE APPLICABLE
 PROVISIONS OF 11-4.1.1 TO 11-4.1.3. MINIMUM
 REQUIREMENTS FOR NEW CONSTRUCTION.
 PROVIDE VERTICAL ACCESSIBILITY TO THE RAISED SEATING
 AREA.
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 13:52 Sent To FIRE
Notes
2008-01-28 13:54:25REDLINED PLANS,NO LIGHTING LEVELS AS STATED ON PLANS
 SHALL BE PERMITTED TO DIM BELOW THE MINIMUM LEVELS PER
 LS 101 7.8 AND 7.9
 THIS IS STATED ON PLANS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 16:43 Sent To  
Notes
2007-12-03 16:43:58 
 ** DENIED REVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES.
  
  
  
 1) NOTE: PLEASE SEE THE PLANS ARE STILL QUOTING
 LIGHTING CONTROLS ARE TO MEET CHAPTER 13 IN LIEU OF
 ACTUAL DETAILS REQUIRED.
 13-415.1.ABC.1.2.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT SHOW
 THE NEW LIGHTING, CIRCUITING, OR CONTROLS FOR STAIR
 LIGHTS AND EMERGENCY LIGHTING WHICH ARE ON PHOTO-METRIC
 SHEET PROVIDED.
 PLEASE CORRELATE ELECTRICAL FOR ALL LIGHTING.
 PLEASE SHOW CONTROLS AND CIRCUITING. PLEASE BE SURE TO
 SEE NEC 700.12E FOR CIRCUITING OF EMERGENCY LIGHTING
 FIXTURES.
 FBC 106.3.5.1.2, 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 11:47 Sent To  
Notes
2007-10-27 11:47:45** DENIED REVISION 3RD TIME **
  
 1) NOTE: PLEASE SEE THERE ARE STILL COMMENTS FROM THE
 *TWO* PREVIOUS REVIEWS WHICH ARE THE SAME.
 PLEASE KNOW THAT QUOTING THE CODE ON PLANS IN LIEU OF
 SHOWING CODE COMPLIANCE DETAILS IS NOT PERMITTED.
 ** THE PLANS WERE LOOKED OVER BEFORE SUBMITTING WITH
 THE GC AND WERE TOLD THE PLANS HAD NOT BEEN CORRECTED.
 THE PLANS WERE SUBMITTED FOR REVIEW ANYWAY FOR CODE
 COMPLIANCE REVIEW.
  
 2) NOTE: PLEASE SEE PLANS ARE STILL DO NOT INDICATE THE
 LIGHTING CONTROLS AS REQUIRED PER 13-415.1.ABC .1.1,
 AND 13-415.1.ABC .1.2. 13-103
 PLEASE KNOW THAT QUOTING THE CONTROLS ARE TO MEET CODE
 IS NOT PROVIDING THE INFORMATION AS NEEDED.
  
 3) NOTE: PLEASE SEE THE PLANS STILL INDICATE DIMMERS ON
 THE EGRESS LIGHTING PATHS. PLEASE SEE THAT NO
 INFORMATION WAS SUBMITTED ON HOW THE MINIMUM LIGHTING
 LEVELS WILL BE MAINTAINED. PLEASE SEE THE PLANS DO NOT
 INDICATE ANY LIGHTING LEVELS AS PREVIOUSLY REQUESTED.
 THESE ARE ALL *MINIMUM* LIGHTING LEVELS REQUIRED FOR
 LIFE SAFETY UNDER NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE THE 2003 LIFE SAFETY CODE NFPA-101 7.8 AND
 7.9.
 PLEASE SHOW THE PHOTO-METRIC LEVELS BASED ON FIXTURES
 TO BE INSTALLED.
 PLEASE PROVIDE DETAILED INFORMATION WHICH WILL
 SPECIFICALLY SHOW HOW THE MINIMUM LIGHTING LEVELS ARE
 MET.
  
 4) NOTE: PLEASE SEE THAT AS THESE COMMENTS WHICH WERE
 ON BOTH PREVIOUS REVIEWS. IF THESE COMMENTS ARE NOT
 ADDRESSED ON THE FOLLOWING REVIEW, THIS OFFICE IS BEING
 LEFT WITH NO CHOICE BUT TO FORWARD DOCUMENTS/PLANS TO
 THE FLORIDA BOARD OF ARCHITECTS AND STATE BOARD OF
 ARCHITECTS LEGAL COUNSEL FOR REVIEW.
 AS STATED ON ALL PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS TO PLEASE CONTACT THIS OFFICE TO GO OVER THE
 COMMENTS IF THEY ARE NOT UNDERSTOOD.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 15:14 Sent To  
Notes
2007-08-23 15:48:48 
 *** DENIED ***
  
  
 1) NOTE: PLEASE SEE THE PLANS STILL INDICATE A NOTE
 WHICH STATES LIGHTING CONTROL DEVICES TO COMPLY WITH
 CHAPTER 13, HOWEVER MAY NOT QUOTE THE CODE IN LIEU OF
 SHOWING THE REQUIRED DETAIL FOR MINIMUM DESIGN.
 13-415.1.ABC.1.1, .1.2
  
 2) NOTE: PLEASE SEE PLANS NOW CONTAIN WHITE-OUT AND
 HAND WRITTEN CHANGES WHICH IS PROHIBITED UNDERFS
 481.221
  
 3 NOTE:SAME NOTE S PREVIOUS REVIEW. PLEASE SUBMIT
 PHOTO-METRICS FOR THEEGRESS STAIRS UNDER NORMAL AND
 UNDER EMERGENCY CONDITIONS. PLEASE SEE THAT EGRESS
 PATHS SUCH AS HALLWAYS AND STAIRWAY SHALL NOT CONTAIN
 DIMMERS WHICH CAN PLACE THE MINIMUM LIGHTING LEVELS
 BELOW THAT OF THE LIFE SAFETY CODE.
 PLANS STILL INDICATE DIMMERS ON PLANS WHICH ARE
 STRICTLY PROHIBITED. PLEASE KNOW ONCE THE MINIMUM
 LEVELS OF FOOT CANDLES ARE INDICATED, DEPENDING ON THE
 TYPE OF DIMMER, DIMMING MAY BE POSSIBLE IF THE MINIMUM
 LEVELS ARE STILL MAINTAINED AT THE LOWEST POINT OF
 DIMMING. THIS IS A LIFE SAFETY ISSUE.
 PLEASE INDICATE THE LOCATIONS OF THE EXISTING EMERGENCY
 LIGHTS ON PLANS. PLANS STATE A NOTE WHICH DIRECTS
 CONTRACTOR TO ADD IF NOT EXISTING.
 ONE AGAIN PLANS ARE REQUIRED TO SHOW IN DETAIL THE
 *MINIMUM* REQUIRED FOR LIFE SAFETY.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
 ** PLEASE SEEPOSSIBLE COMMENTS FROM THE FIRE MARSHAL
  
 3) NOTE: PLEASE PROVIDE REVISED PANEL SCHEDULES ALONG
 WITH CIRCUITING ON PLANS TO CORRELATE WITH SAID PANEL
 SCHEDULES.
 408.4, 310.16, 240.4.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, 13-101 AS
 NEW LIGHTING CONTROL DEVICES NOW BEING CHANGED OUT ARE
 REQUIRED TO MEET CHAPTER 13.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 16:18 Sent To  
Notes
2007-06-21 16:45:38** UNSAT **
  
 ** REVISIONS
  
 1) NOTE: PLEASE SEE THE SEAL IN USE BY THE ARCHITECT IS
 NOT VALID UNDER RULING UNDER THE FAC 61G1-16.002.
 PLEASE SEE THIS WAS MISSED ON PREVIOUS REVIEWS OF PLANS
 AND NEW SEAL AS REQUIRED UNDER FAC AND FS 481.221 MUST
 BE OBTAINED.
 PLEASE SEE SHEET ATTACHED FROM STATE WEB SITE.
  
 2) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR EGRESS STAIRS
 UNDER NORMAL AND UNDER EMERGENCY CONDITIONS. PLEASE SEE
 THAT EGRESS PATHS SUCH AS HALLWAYS AND STAIRWAY SHALL
 NOT CONTAIN DIMMERS WHICH CAN PLACE THE MINIMUM
 LIGHTING LEVELS BELOW THAT OF THE LIFE SAFETY CODE.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
 ** PLEASE SEE COMMENTS FROM THE FIRE MARSHAL
  
 3) NOTE: PLEASE PROVIDE REVISED PANEL SCHEDULES ALONG
 WITH CIRCUITING ON PLANS TO CORRELATE WITH SAID PANEL
 SCHEDULES.
 408.4, 310.16, 240.4.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, 13-101 AS
 NEW LIGHTING CONTROL DEVICES NOW BEING CHANGED OUT ARE
 REQUIRED TO MEET CHAPTER 13.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 14:35 Sent To  
Notes
2007-02-03 14:48:01DOES NOT INCLUDE ANY LV SCOPE OF WORK, ANY LOW VOLTAGE
 WILL BE UNDER A SEPARATE PERMIT , PLANS AND FEES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 19:45 Sent To  
Notes
2006-11-03 19:58:51*** UNSAT ****
  
 1) NOTE: PLEASE SEE PLANS CONTAIN A RAISED SEAL OVER
 "PHOTO-COPIED" SIGNATURES FOR THE ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221 WHICH REQUIRES AN ORIGINAL
 SIGNATURE.
 PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS SAME
 DESIGN PROFESSIONAL ON PREVIOUS PROJECTS AND ONE SET OF
 PLANS WILL BE RETAINED AND PLACED IN PREVIOUS FILE FOR
 SAID ARCHITECT. PLANS MAY BE FORWARDED TO THE STATE.
  
 2) NOTE: PLEASE SEE PLANS MENTIONS THE "DJ" BOOTH BEING
 RELOCATED, PLEASE CALRIFY ANY RELOCATION OF ELECTRICAL
 SYSTEMS , LIGHTING CONTROLS , LV WIRING ETC.
 PLEASE KNOW ALL LV WIRING WILL BE REQUIRED TO BE
 PERMITTED.
  
  
 ** PLEASE SUBMIT TEH ABOVE INFORMATION FOR REVIEW AND
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-02-04 Cont ID  
Sent By mawillia Date 2008-02-04 Time 14:19 Rev Time 0.00
Received By mawillia Date 2008-02-04 Time 14:06 Sent To  
Notes
2008-02-04 14:07:47*****APPROVED*****
  
 PLAN SHEETS 5 AND 6 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2007-11-06 Cont ID  
Sent By mawillia Date 2007-11-06 Time 11:13 Rev Time 0.00
Received By mawillia Date 2007-11-06 Time 10:48 Sent To  
Notes
2007-11-06 10:52:52*****DENIED*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE REVIEWS
 STILL NEED TO BE REVIEWED
  
  
 1.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION. THE PLANS ARE TO BE SUBMITTED WITH NO INK,
 PENCIL,OR BLACK/WHITE-OUTED MARKINS
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.JOB SITE SHALL BE CLEANED
 OF CONSTRUCTION DEBRIS DAILY.PLEASE ACKNOWLEDGE ON AN
 APPROPIATE PLAN SHEET
  
 4.PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING
 REQUIRED LIGHTING IN AREAS OF MEANS OF EGRESS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-08-28 Cont ID  
Sent By mawillia Date 2007-08-28 Time 11:07 Rev Time 0.00
Received By mawillia Date 2007-08-28 Time 10:50 Sent To  
Notes
2007-08-28 10:54:57*****DENIED*****
 THE FOLLOWING COMMENTS ARE A COMPILATION OF THE
 PREVIOUS FIRE REVIEWS:
  
  
 1.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.JOB SITE SHALL BE CLEANED
 OF CONSTRUCTION DEBRIS DAILY.
  
 3.WILL THE SCOPE OF WORK IMPACT EXISTING FIRE
 SPRINKLER OR FIRE ALARM SYSTEMS.IF SO. SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR THE REMODEL.
  
 4.PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING
 REQUIRED LIGHTING IN AREAS OF MEANS OF EGRESS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-06-27 Cont ID  
Sent By mwennerg Date 2007-06-27 Time 12:51 Rev Time 0.00
Received By mwennerg Date 2007-06-27 Time 12:51 Sent To  
Notes
2007-06-27 12:55:24***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING SEAL
 REQUIREMENTS AND REQUIRED LIGHTING IN AREAS OF MEANS OF
 EGRESS.
  
 2) THE LAST FIRE REVIEW WAS PASSED PROVISO, HOWEVER TWO
 (2) COMMENTS WERE INCLUDED WITH NO RESPONSE NOTED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-14 Cont ID  
Sent By mawillia Date 2007-02-14 Time 13:02 Rev Time 0.00
Received By mawillia Date 2007-02-14 Time 13:02 Sent To  
Notes
2007-02-14 13:04:10*****PROVISO*****
  
  
  
  
 1.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.JOB SITE SHALL BE CLEANED
 OF CONSTRUCTION DEBRIS DAILY.
  
 3.THE WORK WILL NOT IMPACT EXISTING FIRE SPRINKLER OR
 FIRE ALARM SYSTEMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mwennerg Date 2006-12-21 Time 14:45 Rev Time 0.00
Received By mwennerg Date 2006-12-21 Time 14:45 Sent To  
Notes
2006-12-21 15:14:27***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #1 AND MAKE
 APPROPRIATE CORRECTIONS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. JOB SITE SHALL BE CLEANED OF
 CONSTRUCTION DEBRIS DAILY.
  
 4) PLEASE SHOW LOCATIONS (NEW OR EXISTING) OF REQUIRED
 2A-10B,C RATED FIRE EXTINGUISHERS. SPACING TO BE AT
 DISTANCES NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 5) WILL WORK IMPACT EXISTING FIRE SPRINKLER OR FIRE
 ALARM SYSTEMS?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 10:23 Rev Time 0.00
Received By shill Date 2008-01-25 Time 10:23 Sent To E
Notes
2008-01-25 10:24:09TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 16:52 Sent To  
Notes
2007-12-03 09:38:48TO "BOB"#4
2007-11-27 16:52:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 12:23 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 12:23 Sent To  
Notes
2007-10-27 11:21:38TO BOB BOARD SPACE #6
2007-10-19 12:23:23WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 20:56 Sent To  
Notes
2007-08-23 13:29:47TO "BOB"#6
2007-08-07 20:56:32WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 09:55 Sent To E
Notes
2007-06-19 09:55:44TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 09:03 Sent To  
Notes
2007-02-02 09:04:56TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By mwennerg Date 2006-12-21 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2006-11-01 Time 16:38 Sent To  
Notes
2006-11-01 16:58:13TO "COMM" BD#55
2006-11-01 16:39:06WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-08-24 Cont ID  
Sent By tgordon Date 2007-08-24 Time 09:32 Rev Time 0.20
Received By tgordon Date 2007-08-24 Time 09:32 Sent To  
Notes
2007-08-24 09:35:13PLAN STATES EXHAUST CHANGE OUT OF SECOND FLOOR A/C
 SYSTEM. WILL NEED TO APPLY FOR A MECHANICAL PERMIT
 BEFORE REPLACING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 08:46 Rev Time 0.25
Received By tgordon Date 2007-06-25 Time 08:46 Sent To  
Notes
2007-06-25 08:55:17*** DENIED ***
 1) SEE SECOND PAGE OF PLANS UPPER LEVEL STATES 'NO
 MECHANICAL CHANGES' BUT THE PLAN ALSO SHOWS 'NEW A/C 5
 TON'. IF ONLY AN EXACT CHANGE-OUT A MECHANICAL PERMIT
 MAY BE APPLIED FOR AT A LATER DATE, PLEASE STATE SO ON
 PLANS OR CORRECT PLANS.
  
 2) SEE ELECTRICAL REVIEW NOTE #1 REGARDING SEAL, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.