Plan Review Details - Permit 06101056
Plan Review Stops For Permit 06101056
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-04 Cont ID  
Sent By jwitmer Date 2007-09-04 Time 07:52 Rev Time 0.77
Received By jwitmer Date 2007-09-04 Time 07:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By jwitmer Date 2007-08-27 Time 13:18 Rev Time 1.22
Received By jwitmer Date 2007-08-27 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 14:41 Rev Time 0.77
Received By jwitmer Date 2007-06-28 Time 14:41 Sent To  
Notes
2007-06-28 14:41:55PERMIT: 06101056
 ADD: 501 VILLAGE BLVD
 CONT: MCGOWAN BUILDERS
 TEL: (646)533-0342
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET G1.1 BUILDING CODE SUMMARY PLEASE CORRECT
 BUILDING TYPE: IVTABLE 503, TABLE 601 AND 602.4 IV IS
 CONSIDERED HEAVY TIMBER .
  
 4) 2ND REQUEST WCW ENGINEERS, INC WILL REQUIRE A
 CERTIFICATE OF AUTHORIZATION FOR THEIR FIRM. THE NUMBER
 SUBMITTED F06000007816 MAY BE THE FL CORP NUMBER BUT
 THIS IS NOT THE CERTIFICATE OF AUTHORIZATION THAT IS
 REQUIRED TO BE REGISTERED WITH DEPARTMENT OF BUSSINESS
 AND PROFESSIONAL REGULATION.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY BE ADDED BY
 HAND.
  
 5) COMMENT# 6 FROM THE PREVIOUS REVIEW, DEALS WITH THE
 RAMP FROM THE FREE WEIGHT AREA, RESPONCE INDICATED THE
 RAMP IS LESS THAN 72" LONG WHERE AS WHEN SCALED OUT
 USING THE 1/8" SCALE
 IT INDICATES THE LENGTH TO BE 9'-0". PLEASE CORRECT THE
 DRAWING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-30 Cont ID  
Sent By jwitmer Date 2007-03-30 Time 10:11 Rev Time 1.22
Received By jwitmer Date 2007-03-30 Time 10:11 Sent To  
Notes
2007-03-30 10:23:52BUILDING PLAN REVIEW
 PERMIT: 06101056
 ADD: 501 VILLAGE BLVD
 CONT: MCGOWAN BUILDERS
 TEL: (646)533-0342
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET G1.1 BUILDING CODE SUMMARY PLEASE CORRECT
 BUILDING TYPE: IVTABLE 503, TABLE 601 AND 602.4 IV IS
 CONSIDERED HEAVY TIMBER .
  
 4) 2ND REQUEST WCW ENGINEERS, INC WILL REQUIRE A
 CERTIFICATE OF AUTHORIZATION FOR THEIR FIRM. THE NUMBER
 SUBMITTED F06000007816 MAY BE THE FL CORP NUMBER BUT
 THIS IS NOT THE CERTIFICATE OF AUTHORIZATION THAT IS
 REQUIRED TO BE REGISTERED WITH DEPARTMENT OF BUSSINESS
 AND PROFESSIONAL REGULATION.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY BE ADDED BY
 HAND.
  
 5) COMMENT# 6 FROM THE PREVIOUS REVIEW, DEALS WITH THE
 RAMP FROM THE FREE WEIGHT AREA, RESPONCE INDICATED THE
 RAMP IS LESS THAN 72" LONG WHERE AS WHEN SCALED OUT
 USING THE 1/8" SCALE
 IT INDICATES THE LENGTH TO BE 9'-0". PLEASE CORRECT THE
 DRAWING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By jwitmer Date 2006-11-28 Time 09:39 Rev Time 6.75
Received By jwitmer Date 2006-11-27 Time 16:08 Sent To  
Notes
2006-11-28 11:18:49BUILDING PLAN REVIEW
 PERMIT: 06101056
 ADD: 501 VILLAGE BLVD
 CONT: MCGOWAN BUILDERS
 TEL: (646)533-0342
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3A)CORRECTION SHEET G1.1 BUILDING SUMMARY NOTES: 2004
 FLORIDA BUILDING CODE WITH 2004 WEST PALM BEACH
 ADMINISTRATIVE AMENDMENTS
 2004 EXISTING BUILDING CODE
  
 3B) 2004 EXISTING BUILDING CODE WHAT LEVEL OF
 ALTERATIONS?
  
 4) THE P & E TITLE BLOCKS HAVE WCW ENGINEERS, INC IN
 THE
 TITLEBLOCK BUT THERE IS NO CERTIFICATE OF AUTHORIZATION
 FOR THE FIRM.) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 5) SHEET A1.1 INDICATES THE USE OF A RAMP TO GAIN
 ENTRY
  
 INTO THE CARIDO AREA, BUT NO HANDRAILS ARE INDICATED.
 THERE IS A CUT SECTION
 DETAIL# 7 OF SHEET A6.2 BUT NO INDICATION OF
 HANDRAILS.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6) SHEET A1.1 ALSO INDICATES THE USE OF A RAMP
 IN THE FREE WEIGHTS AREA, PLEASE INDICATE
 THE USE OF HANDRAILS,
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7)A1.1 RECEPTION DESK, PLANS DO NOT PROVIDE DETAILS
 FOR ACCESSIBILITY:
 11-4.32.4 HEIGHT OF TABLES OR COUNTERS .
 THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE
 FROM 28 INCHES
 TO 34 INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR
 OR GROUND.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 12:06 Sent To B
Notes
2007-08-31 14:45:06ELEC OK, STAMPED, SENT TO BUILDING REVIEWER AS THERE
 ARE SHEETS IN SETS WHICH ARE NEW/NOT BEEN STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-23 Cont ID  
Sent By dpalmer Date 2007-07-23 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 13:31 Sent To I
Notes
2007-07-23 14:49:15*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE REVISED ENERGY CALCULATIONS
 SUBMITTED ARE NOT SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE THE PLANS STILL CONTAIN THE OLD ENERGY
 CALCULATIONS ATTACHED DOWN THE LEFT HAND SIDE OF THE
 PLANS.
 PLEASE BE SURE NOT TO ATTACH ANY SUPPORTING DOCUMENTS
 DOWN THE LEFT HAND SIDE OF PLANS.
 PLEASE SEE 13-103.1.1.1
 PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON
 CERTIFICATION SHEET.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-07-23 13:32:09PLANS REMOVED FROM INCOMING, WILL RETURN TO INCOMING
 WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS
 COMPLETED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 12:49 Sent To  
Notes
2007-06-19 15:06:17*** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE NOW
 SUBMITTED WITHOUT THE INPUT DATA REPORTS SHEETS WHICH
 ARE REQUIRED. PLEASE SEE STATEMENT ON COVER SHEET EVEN
 MENTIONS THIS.
 FBC 113-415.1.C.
  
 2) NOTE: PLEASE SEE THE FA NOTE NOW MENTIONS THE CODE
 SECTION HOWEVER IT DOES INDICATE THE MINIMUM LEVELS AS
 NEEDED. MAY NOT QUOTE THE CODE IN LIEU OF THE SPECIFIC
 REQUIREMENT.
 FBC 11-4.28.1,.2, AND .3(4).
  
 3) NOTE: PLEASE SEE PLANS NOW INDICATE A NEW 6-POLE
 CONTACTOR AND LIGHTING CONTROLS HOWEVER NO DETAILS FOR
 THIS IS SHOWN ON PLANS. NO TIME FOR SCHEDULING, NO
 TIMES FOR OVER RIDE DEVICES, NO TIMES ON DEVICES WHERE
 COMPLIANCE WITH FBC CHAPTER 13 IS BEING NOTED.
 PLEASE CLARIFY AND PROVIDE MORE INFORMATION.
  
 4) NOTE: PLEASE SEE THE PREVIOUS TITLE BLOCKS CONTAINED
 PRINTED NAME AND PRINTED LICENSE NUMBER OF THE ENGINEER
 HOWEVER IT WAS IN THE *PRINTED SEAL* WHICH WAS PLACED
 ON PLANS IN LIEU OF THE RAISED SEAL. NOW PLANS ARE
 COMING BACK WITHOUT THE PRINTED SEAL AND ONLY THE
 PRINTED NAME IS SHOWN. PLEASE BE SURE THE PRINTED
 LICENSE NUMBER IS ON PLANS. FAC 61G15-23.002
 PLEASE ALSO CLARIFY WHY THE EXPIRATION DATE FROM FEB 07
 IS BEING SHOWN ON TITLE BLOCKS UNDER ENGINEERS SEAL. AS
 THE EXPIRATION DATE HAS SINCE PAST THIS WOULD NOT BE
 VALID. THIS LICENSE HAS BEEN VERIFIED WITH THE STATE AS
 NOT EXPIRED ON THIS DATE AS NOTED.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By dpalmer Date 2007-03-06 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 18:10 Sent To  
Notes
2007-03-06 07:28:47*** UNSAT 2ND REVIEW ***
  
  
 1) NOTE: PLEASE INCLUDE THE FOLLOWING CODES ALSO
 RELEVANT TO DESIGN.
 NFPA-70 2002, 2002 NFPA-72.
 RESPONSE MENTIONS THAT THE CODES WERE ADDED HOWEVER
 COULD NOT LOCATE THESE ON THE REVISED SHEETS. PLEASE
 SEE THAT THE ELECTRICAL SHEETS ALSO SHOULD STATE THESE
 CODES.
 .
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED ON TITLE BLOCKS FOR THE "P" SHEETS. PLEASE SEE
 THAT A CERTIFICATE OF AUTHORIZATION NUMBER WAS ADDED TO
 THE ELECTRICAL SHEETS HOWEVER THE NUMBER WHICH WAS
 ADDED TO THE PLUMBING SHEETS IS IN FACT THE FLORIDA
 CORPORATION NUMBER WHICH IS NOT THE SAME AS THE CA
 NUMBER. PLEASE CHECK WITH THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION AS THEY WILL BE ABLE TO
 HELP THROUGH THE PROCESS IN OBTAINING A FIRM LICENSE
 NUMBER. IF THE COMPANY HAS A CA NUMBER, PLEASE ADD TO
 TITLE BLOCKS. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE ELECTRICAL SHEETS HAVE NOW COME
 BACK WITHOUT A RAISED SEAL AS REQUIRED IN THE STATE OF
 FLORIDA. FS 471.025, FAC 61G15-23.001
 A PRINT OF THE SEAL IS OK AS LONG AS THE RAISED SEAL IS
 ALSO PRESENT, CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
  
 4) NOTE: PLEASE SEE THE FA DEVICES SEE TO BE CROSSED.
 PLEASE SEE THE *A* WHICH IS BEING ASSUMED FOR THE
 AUDIBLE DEVICE INDICATES THE VISUAL LEVELS AS 95CD AND
 THE *V* FOR VISUAL DEVICE INDICATES 95 DB ? PLEASE
 VERIFY BOTH OF THESE. THE PREVIOUS COMMENT REFERENCED
 THE FBC AS NOTED AND LEVELS FOR VISUAL DEVICES WERE
 75CD MINIMUM. PLEASE CLARIFY
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). PLEASE
 INDICATE THE MINIMUM AREAS WILL FALL INTO THESE
 EXCEPTIONS.
  
  
 AUDIBLE LEVELS AND LIGHTING LEVELS PER FBC.
  
 5) NOTE: PLEASE KNOW THAT ANY *NEW* LIGHTING AREAS AND
 CONTROLS NOT FOR OPERATION 24HRS A DAY WILL REQUIRE
 AUTOMATED SHUT OFF FOR LIGHTING PER 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 THIS IS FOR AREAS OF ALL NEW INSTALLATION ONLY AND NOT
 24/7 OPERATIONS.
 THIS IS BEING NOTED ONLY, HOWEVER PLEASE RESPOND IN
 LETTER IF ANY OF THESE
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-06 07:00:312007-03-06 07:00:31
 IN PROGRESS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-05 Cont ID  
Sent By dpalmer Date 2006-11-05 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 20:56 Sent To  
Notes
2006-11-05 11:22:48**** UNSAT ****
  
 1) NOTE: PLEASE INCLUDE THE FOLLOWING CODES ALSO
 RELEVANT TO DESIGN.
 2003 NFPA-101 AND POSSIBLE NFPA-72 2002, 2002 NFPA-72.
 PLEASE SEE NOTES ON PLANS INDICATE A NFPA-92? BOCA,
 IBCC, ETC.
 PLEASE SEE THE SCOPE OF WORK FOR THIS LOCATION IS UNDER
 THE 2004 FBC.
 PLEASE ALSO SEE COVER SHEET REFERENCESBY THE CITY FOR
 2001, PLEASE KNOW, THIS WOULD BE ACTUALLY THE 2004.
 PLEASE BE SURE TO ADJUST ALL NOTES ON ALL SHEETS.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED ON TITLE BLOCKS FOR BOTH THE "P" AND "E"
 SHEETS. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023..
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE INDICATE THE NEW FA DEVICES OR EXISTING
 IN AREAS BEING REMODELED. PLEASE SEE FBC 11-4.28.1, .2
 AND .3(4). PLEASE INDICATE THE MINIMUM AUDIBLE LEVELS
 AND LIGHTING LEVELS PER FBC.
  
 4) NOTE: PLEASE SEE METHOD "C" AS INDICATED MENTIONS
 TOTAL SQ FT AND WHAT APPEARS TO BE TRADES -OFF-S.
 PLEASE SEE 13-415.2.ABC.1, WHICH MENTIONS TABLES
 415.2.C.1 AS TRADE OFFS FOR SPACES ARE NOT PERMITTED.
 PLEASE CLARIFY THIS.
  
 5) NOTE: PLEASE SEE NO PANEL SCHEDULES WERE SUBMITTED
 FOR ALL CIRCUITING AS SHOWN ON PLANS.NO REVIEW FOR
 CODE COMPLIANCE OF OVER CURRENT PROTECTION DEVICES,
 CONDUCTOR SIZES ETC CAN BE VERIFIED AT THIS TIME.
 240.4, 310.16, 408.4.
 FBC ADMIN SECTION, 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE SOME RECEPTS IN BATH AREAS WHICH
 SHOULD BE GFI PROTECTED WHICH DO NOT INDICATE THIS ON
 PLANS. PLEASE KNOW THERE ARE MANY WHICH SHOW GFI
 RECEPT, HOWEVER AS SOME OF THESE REFLECT BACK TO PANEL
 SCHEDULES IT MAY BE POSSIBLE THAT THE GFI PROTECTION IS
 ACTUALLY IN THE PANEL AT THE BREAKER. HOWEVER PLEASE
 KNOW AS THE PANEL SCHEDULE(S) HAVE NOT BEEN SUBMITTED
 THIS CAN NOT BE VERIFIED AT THIS TIME.
 210.8B1
  
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS AS SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-05 09:51:20REVIEW IN PROGRESS
2006-11-03 20:56:59IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-29 Cont ID  
Sent By mawillia Date 2007-08-29 Time 14:58 Rev Time 0.00
Received By mawillia Date 2007-08-29 Time 14:33 Sent To  
Notes
2007-08-29 14:34:04*****APPROVED*****
  
  
 PLAN SHEETS A6.1, E1.1, AND E2.1 WERE STAMPED,
 INITIALED, AND DATED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By mawillia Date 2007-08-29 Time 14:32 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 16:40 Sent To  
Notes
2007-08-29 14:32:37*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) WILL BE STAMPED WHEN ALL
 OTHER PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 13:27 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 13:18 Sent To  
Notes
2007-03-22 13:22:57*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) WILL BE STAMPED WHEN ALL
 OTHER PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-29 Cont ID  
Sent By mawillia Date 2006-12-29 Time 13:20 Rev Time 0.00
Received By mawillia Date 2006-12-29 Time 13:20 Sent To  
Notes
2006-12-29 14:26:54*****DENIED*****
  
  
  
 1. NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004) EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF
 WORK.IF SO,THIS WILL BE PERMITTED ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ
 ARE IN PLACE.
  
 5.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B IN ALL CORRIDORS AND LOBBIES,
 CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS HAVING AN
 OCCUPANT LOAD OF MORE THAN 300, AND SHALL BE CLASS A,
 CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING AN
 OCCUPANT LOADS OF 300 OR FEWER.
  
 6.SEE BUILDING PLAN REVIEW COMMENT #5 IN REFERENCE
 TO HANDRAILS FOR THE RAMP.PROVIDE THE PRESCIPTIVE
 STRENGHT FOR THE HANDRAILS.
  
 7.ALL FIRE DOORS SHALL COMPLY WITH NFPA 80.
  
 8.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDE WITH PANIC HARDWARE OR FIRE EXIT
 HARWARE, UNLESS OTHERWISE THEY ARE DELAYED-EGRESS LOCKS
 OR ACCESS-CONTROLLED EGRESS LOCKS PERMITTED AND
 APPROVED BY THE AHJ.
  
 9.PLEASE INDICATE LOCATION OF FIRE EXTINGUISHERS,
 EXIT LIGHT, EMERGENCY LIGHTS, FIRE PROTECTION SYSTEM
 DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE
 OF WORK?
  
 10.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE
 PLANS AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RE-SUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 14:31 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 14:31 Sent To E
Notes
2007-08-30 14:31:41TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 09:37 Sent To  
Notes
2007-07-24 10:06:02TO "COMM" BD#54
2007-07-11 09:38:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-05-21 Time 11:40 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 11:40 Sent To  
Notes
2007-06-12 11:41:03TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 15:19 Sent To  
Notes
2007-02-26 13:20:40TO "COMM" BD#39
2007-02-15 15:19:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-03 Cont ID  
Sent By kstevens Date 2007-01-03 Time 06:49 Rev Time 0.00
Received By kstevens Date 2006-10-28 Time 14:39 Sent To  
Notes
2006-11-01 15:18:14TO "COMM" BD#43
2006-10-28 14:38:56WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-11-06 Cont ID  
Sent By tgordon Date 2006-11-06 Time 13:58 Rev Time 30.00
Received By tgordon Date 2006-11-06 Time 13:58 Sent To  
Notes
2006-11-06 13:59:04NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By mperson Date 2007-08-27 Time 16:26 Rev Time 0.00
Received By mperson Date 2007-08-27 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-25 Cont ID  
Sent By kstevens Date 2007-06-20 Time 10:11 Rev Time 0.00
Received By kstevens Date 2007-06-20 Time 10:11 Sent To  
Notes
2007-06-20 10:14:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ******FROM PREVIOUS REVIEWS:
  
 FROM THE PREVIOUS REVIEW:
  
 1. OK
  
 2. SUBMIT A DETAIL FOR ACCESSIBLE SHOWERS. SHOW
 COMPLIANCE WITH SECTION 11-4.21 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT IS STILL
 REQUIRED AND SHALL BE INDICATED. SECTION 11-4.21.6.
 ******NO RESPONSE/NOT ADDRESSED.
  
 3. OK
 4. OK
  
 5. PLUMBING SHEETS REQUIRE THE PRINTED NAME OF THE
 PERSON SIGNING AND SEALING THE PLANS. ALSO THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 COMPANY IS REQUIRED. FAC 61G15-23.002(2) AND FS
 471.025.
 ****RESPONSE NOTED, BUT THE PRINTED NAME OF THE PERSON
 SIGNING & SEALING THE PLANS IS NOT SHOWN, NOR IS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. THE NUMBER
 INDICATED IN THE TITLE BLOCK IS NOT FOR WCW ENGINEERS
 INC. (PLEASE SEE ATTACHED SHEET FROM THE STATE OF
 FLORIDA DBPR WEBSITE).
 ******RESPONSE NOTED BY CERTIFICATE OF AUTHORIZATION
 NUMBER, BUT THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IS NOT INDICATED.
  
 6. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-12 Cont ID  
Sent By kstevens Date 2007-03-12 Time 16:52 Rev Time 0.00
Received By kstevens Date 2007-03-12 Time 16:52 Sent To  
Notes
2007-03-12 16:58:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM THE PREVIOUS REVIEW:
  
 1. OK
  
 2. SUBMIT A DETAIL FOR ACCESSIBLE SHOWERS. SHOW
 COMPLIANCE WITH SECTION 11-4.21 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT IS STILL
 REQUIRED AND SHALL BE INDICATED. SECTION 11-4.21.6.
  
 3. OK
 4. OK
  
 5. PLUMBING SHEETS REQUIRE THE PRINTED NAME OF THE
 PERSON SIGNING AND SEALING THE PLANS. ALSO THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 COMPANY IS REQUIRED. FAC 61G15-23.002(2) AND FS
 471.025.
 ****RESPONSE NOTED, BUT THE PRINTED NAME OF THE PERSON
 SIGNING & SEALING THE PLANS IS NOT SHOWN, NOR IS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. THE NUMBER
 INDICATED IN THE TITLE BLOCK IS NOT FOR WCW ENGINEERS
 INC. (PLEASE SEE ATTACHED SHEET FROM THE STATE OF
 FLORIDA DBPR WEBSITE).
  
 6. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-03 Cont ID  
Sent By kstevens Date 2007-01-03 Time 06:13 Rev Time 0.00
Received By kstevens Date 2007-01-02 Time 18:38 Sent To  
Notes
2007-01-03 06:48:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT D1.1 IN THE REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION 704.5. ALL
 DEMO'D/ CAPPED PIPING SHALL REMAIN UNCOVERED UNTILL
 INSPECTED.
  
 2. SUBMIT A DETAIL FOR ACCESSIBLE SHOWERS. SHOW
 COMPLIANCE WITH SECTION 11-4.21 AND ALL SUBSECTIONS.
  
 3. SHT D1.1 MORE INFORMATION IS REQUIRED. IT IS NOT
 CLEAR WHAT WAS DELETED IN THE MEN'S LOCKER ROOM FROM
 NORTH OF COL. LINE #4 TO SOUTH OF COL. LINE #5, AND
 BETWEEN THE CORRIDOR BETWEEN COL. LINES D & E TO THE
 WALL BETWEEN THE LOCKER ROOM & THE POOL ROOM. IN THE
 WOMEN'S LOCKER ROOM THERE IS AN AREA JUST NORTH OF COL.
 LINE 6 TO THE WALL JUST NORTH OF THE DRINKING FOUNTAIN
 THAT NEEDS CLARIFICATION AS TO WHAT WAS BEING DEMO'D.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 4. SHT D1.1 THE WOMEN'S ROOM SHOWS 6 SHOWERS IN ONE
 AREA & 4 SHOWERS IN WOMEN'S SHOWER (036). DEMO
 INDICATES MAYBE 8 SHOWERS WERE IN AREA 036. WERE
 SHOWERS DELETED?THIS IS NOT INDICATED IN THE DEMO
 NOTES. ARE THE ACCESSIBLE SHOWERS IN THE WOMEN'S AND
 MEN'S ROOMS NEW OR EXISTING? IF NEW SEE COMMENT #2.
  
 5. PLUMBING SHEETS REQUIRE THE PRINTED NAME OF THE
 PERSON SIGNING AND SEALING THE PLANS. ALSO THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 COMPANY IS REQUIRED. FAC 61G15-23.002(2) AND FS
 471.025.
  
 6. PER SECTION 11-4.1.7(2) UP TO 20% OF THE CONTRACT
 SHALL BE USED TO UPGRADE ACCESSIBILITY REQUIREMENTS.
 PLEASE INDICATE HOW THIS REQUIREMENT IS BEING COMPLIED
 WITH. - ACCESSIBLE STALLS DOORS SHALL SWING OUTWARD. IF
 REPLACING PARTITIONS, THIS REQUIREMENT SHOULD BE
 BROUGHT UP TO CODE. SEE FIG. 11-30.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved