| Plan Review Stops For Permit 06101055 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-12-21 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-12-21 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2006-12-21 10:21:08 | A NEW PARCEL CONTROL NUMBER WAS ISSUED BY THE PROPERTY | | | APPRAISER'S OFFICE .THE PERMIT WAS ATTACHED TO THE | | | VALID PCN FROM THE TEMPORARY PCN USED INITIALLY. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-05-14 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-05-14 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2008-05-14 08:58:49 | CONCRETE BLOCK LETTER AND ENTRY DOOR PRODUCT APPROVAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-03-03 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-03-03 |
Time |
16:13 |
Sent To |
PC |
|
| Notes |
| 2008-03-03 16:13:53 | SUBMITTAL BUILDING REVIEW CHECKLIST: | | | | | | 1- OWES $60.00 REVISION FEES FORSOFFIT REVISION. | | | | | | 2-DOOR PRODUCT APPROVAL NOA 02-0215.04 IS FOR | | | "OUTSWING"DOORS.DRAWINGS SUBMITTED ARE FOR | | | "INSWING" DOORS. DOWNLOAD CORRECT DRAWINGS FROM | | | WEBSITE. | | | REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | ***NOTE: SUBMIT NOA ALONE . FLORIDA PRODUCT APPROVAL | | | FL1190-R1 AND NOA 02--0215.04 DON'T CORRESPOND TO EACH | | | OTHER. | | | | | | 3- PROVIDE RINKER SPECIFICATIONS LETTER FOR 2 HOUR | | | CONCRETE BLOCK AS REQUESTED ON PROVISO. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-11-30 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-11-30 |
Time |
12:57 |
Sent To |
PC |
|
| Notes |
| 2007-11-30 14:00:07 | TRUSS PACKAGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-10-31 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-10-31 |
Time |
09:32 |
Sent To |
PC |
|
| Notes |
| 2007-10-31 09:47:41 | TRUSS PACKAGE BUILDING REVIEW CHECKLIST. | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72FOR STRUCTURAL CONNECTORS HU214-3AND HU210-2 | | | ATTACHED DIRECTLY TO MASONRY WALL TO VERIFY COMPLIANCE | | | WITH THE CALCULATED LOADS FOR GIRDER TRUSS FG02,FG09 | | | (NOTE: FG09 IS A 5 PLY TRUSS), FG10 (NOTE: FG10IS A 4 | | | PLY TRUSS).FG06 (SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004.ENGINEER OF RECORD TO REVIEW AND APPROVE IN | | | WRITING ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO | | | THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTSTO FBC | | | 2004. | | | | | | 2- REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY | | | THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS | | | OFFICE. | | | | | | 3- IF PROVIDING COVER OR INDEX SHEET TO AVOID SIGNING | | | AND SEALING ALL INDIVIDUAL TRUSSES, THEN ALL | | | INFORMATION REQUIRED BY SEC. 61G15-31003 SHALL BE | | | SUBMITTED. THIS PACKAGE IS MISSING STRUCTURAL ENGINEER | | | OF RECORD INFORMATION, PROPER IDENTIFICATION OF PROJECT | | | (AND ADDRESS SHOWN IS NOT CORRECT) AND A CLEARNAMING | | | AND NUMBERING SYSTEM.INDIVIDUAL SHEETS ARE NOT | | | NUMBERED, WHICH ALLOWS TO MATCH INDEX SHEET. | | | | | | 4- TRUSS LAYOUT IS NOT SIGNED AND SEALED AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTE. | | | | | | 5- CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT | | | WITH ANY OTHER LIVE LOADS IF FBC 2004 TABLE 1607.1 | | | REQUIRES ALL MINIMUM LIVE LOADS TO BE INCLUDED IN THE | | | DESIGN.CLARIFY WHICH ARE THE OTHER NONCONCURRENT LIVE | | | LOADS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 6- THIS PROJECT HAS A RESIDENT INSPECTOR, THEREFORE 3 | | | COMPLETE SETS OF TRUSS DRAWINGS ARE REQUIRED. | | | | | | 7- PROVIDE COMPLETE ENGINEERING SPECS FOR BOLTING | | | CRITERIA OF 4 AND 5 PLY GIRDERS AS REQUIRED ON TRUSS | | | LAYOUT NOTES. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-06 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-06 |
Time |
11:54 |
Sent To |
PC |
|
| Notes |
| 2007-08-06 11:55:06 | PRODUCT APPROVAL REVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-10 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-10 |
Time |
12:33 |
Sent To |
PC |
|
| Notes |
| 2007-07-10 12:34:43 | TRUSS PACKAGE CHECKLIST: | | | 1-A) ONLY TWO SETS WERE SUBMITTED. THIS TYPE OF | | | PROJECT REQUIRES THREE COMPLETE SETS.THREE SIGNED AND | | | SEALED SETS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE | | | AND SEC. 61G15-23 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | B) TRUSS ENGINEER TO PROVIDE ALL THREE SETS WITH | | | ORIGINAL SIGNATURE. COPY OF SIGNATURE IS NOT ALLOWED BY | | | CHAPTER 471 FLORIDA STATUTE. | | | | | | C) EVERY INDIVIDUALSHEETNEEDS TO HAVE | | | ENGINEER'S ORIGINAL SEAL, SIGNATURE AND DATE. | | | OTHERWISE, ENGINEER MAY WANT TO FOLLOW ALL CONDITIONS | | | REQUIREDBY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE | | | CODE TO COMPLY WITH THE SIGNING AND SEALING OF ALL | | | SHEETS.INFORMATION SUBMITTED DOESN'T COMPLYWITH | | | THIS SECTION. | | | | | | | | | 2- ENGINEER OF RECORD TO CHECK DETAILS GIVEN ON | | | STRUCTURAL DRAWINGS FOR SUPPORT OF TRUSSES AT THE ENDS. | | | TRUSS PACKAGE SHOWS DIFFERENT END CONNECTIONS.REVISE | | | EITHER TRUSS PACKAGE OR ENGINEERED DRAWINGS AS REQUIRED | | | TO MATCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-14 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-06-14 |
Time |
15:42 |
Sent To |
PC |
|
| Notes |
| 2007-06-14 15:42:32 | REVISION CHECKLIST: | | | | | | 1- THIS IS NOT A SUBMITTALBUT A REVISION ON | | | PREVIOUSLY APPROVED PRODUCT APPROVALS. THEREFORE OWES | | | $70.00 FOR REVISION FEES. | | | | | | 2- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE | | | DESIGNER OF RECORDAS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. PRODUCT APPROVALS SUBMITTED | | | DON'T SHOWDESIGNER OF RECORD APPROVAL IN WRITING. | | | | | | 3- SINGLE HUNG WINDOWS PRODUCT APPROVAL: | | | A) PROVIDE CURRENT PRODUCT APPROVAL FL42-R4. (ONE | | | SUBMITTED IS FL 42-R1). | | | | | | B) PROVIDE ONLY ALL THE TECHNICAL INFORMATION | | | (DRAWINGS, SPECS, ETC) THAT WAS SUBMITTED TO OBTAIN THE | | | FLORIDA PRODUCT APPROVAL. GO THE FLORIDA WEBSITE | | | WWW.FLORIDABUILDING.ORG AND DOWNLOAD CORRESPONDING | | | INFORMATION TO SPECIFIC MODEL TO BE INSTALLED. | | | | | | C) MAKE SURE ALL DRAWINGS ARE LEGIBLE. | | | | | | 4- SLIDING GLASS DOORS: | | | A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY. | | | | | | 5- SUBMIT ONLY THE PRODUCT APPROVALS THAT APPLY TO THIS | | | BUILDING TO EXPEDITE REVIEW PROCESSAND AVOID | | | UNNECESSARY FEES.THERE ARE PRODUCT APPROVALS FOR | | | SWING DOORS THAT DON'T APPLY TO THIS BUILDING. | | | | | | ***NOTE: | | | RESUBMITTAL FEES FOR REVISIONS ARE THE SAME AS FOR THE | | | FIRST TIME REVISIONS ARE SUBMITTED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-03-08 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-03-08 |
Time |
17:26 |
Sent To |
P |
|
| Notes |
| 2007-03-08 17:28:59 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- PROVIDE CORRECT DRAWINGS FOR ENTRY DOOR.NOA | | | 02-0215.04 SUBMITTED HAS THE "INSWING" DOOR DRAWINGS. | | | THIS IS A DADE COUNTY PRODUCT APPROVAL DIVISION MISTAKE | | | THAT WAS ALREADYREVISED. NOW WEBSITE HAS CORRECT | | | "OUTSWING" DOOR DRAWINGS. PROVIDE 3 COPIES, REVIEWED | | | AND APPROVED BY THE DESIGNER OF RECORD. | | | | | | 2-RINKER SPECIFICATIONS LETTER FOR 2 HOUR CONCRETE | | | BLOCK: PROVIDE LETTER ADDRESSED TO THE CITY OF WEST | | | PALM BEACH AND WITH CORRECT PROJECT NAME.THIS IS | | | MERRY PLACE PROJECT, NOT BOCA DEVELOPMENT. | | | | | | 3- DESIGNER OF RECORD TO PROVIDE COMPLETE | | | SPECIFICATIONS/DETAILS FOR INSTALLATION OF HARDISOFFIT | | | & CEMSOFFIT PANELS. SEE SHEET 3 OF 3 OF NOA 02-0729.02 | | | DRAWINGS SUBMITTED. SEC. 106.1.2 CITY AMENDMENTSTO | | | FBC 2004. | | | | | | 4- SUBMIT ALL TRUSS DRAWINGS FOR REVIEW PRIORTO | | | CONSTRUCTION/INSTALLATION. TRUSS PACKAGE TO BE REVIEWED | | | AND APPROVED BY DESIGNER OF RECORDPRIOR TO | | | SUBMITTAL. | | | | | | 5- PROVIDE COPY OFTHE RECORDED MERRY PLACE PLAT FOR | | | CITY RECORDS. | | | | | | 6- PROVIDE 3 COPIES OF APPROVED AND RECORDED SURVEY | | | SHOWING UNITY OF TITLE REVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-01-05 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-01-05 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2007-01-05 19:09:02 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- REVISE ENERGY CALCULATIONS: | | | A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS | | | NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH | | | UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC | | | 2004. | | | | | | | | | B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO | | | PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471 | | | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC. | | | 61G15-23.002. | | | | | | C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE | | | THE FOLLOWING INCORRECT INFORMATION: | | | * NUMBER OF BEDROOMS. | | | ** SLAB ON GRADE TOTAL PERIMETER FEET. | | | *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR | | | WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING | | | OPENINGS SUN EXPOSURE ORIENTATION. | | | | | | 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER | | | INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED. | | | | | | 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND | | | A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY, | | | THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS | | | PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD | | | NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME | | | SURVEY IS SUBMITTED FOR REVIEW. | | | | | | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR | | | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. | | | | | | B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS.ONLY THE ONES SHOWN ON TRUSS ANCHOR | | | SCHEDULE WERE PROVIDED AND THEY ARE MISSING THE PAGE | | | SHOWING THE SPECIFIC CONNECTOR. PROVIDE FLORIDA PRODUCT | | | APPROVAL COVER PAGE AND PAGE SHOWING EACH CONNECTOR. | | | | | | C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL | | | ASSEMBLY U905. | | | | | | D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE | | | DETAIL 11/A705. | | | | | | E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER | | | HEATER. | | | | | | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES | | | MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR | | | SERVICES. | | | | | | 7- PLEASE MAKE SURE ENERGY CALCULATIONS HAVE CORRECT | | | ADDRESS, BUILDING TYPE, PERMIT NUMBER, ETC. | | | | | | 8- NORTH ARROW IN SURVEY IS POINTING TO THE WRONG | | | DIRECTION. REVISE AS REQUIRED. | | | | | | 9- SURVEY TO INDICATE SETBACKS FROM ALL BUILDINGS TO | | | ALL PROPERTY LINES FOR ACCURACY IN DETERMINATING PROPER | | | PERCENTAGE OF OPENINGS.IT WILL ALSO HELP INSPECTOR | | | WHEN CHECKING FORMBOARD SURVEY. | | | THIS APPLIES TO ALL BUILDINGS IN THIS PROJECT. | | | | | | 10- A) OPENINGS IN NORTH WALL EXCEED MAXIMUM PERCENTAGE | | | ALLOWED BY TABLE 704.8 FBC 2004. SEE SURVEY FOR EXACT | | | SETBACK FROM BUILDING TO PROPERTY LINE. REVISE AS | | | REQUIRED. | | | | | | B) OPENINGS IN SECOND FLOOR OF WEST WALL EXCEED THE | | | MAXIMUM PERCENTAGE ALLOWED BY TABLE 704.8 FBC 2004. SEE | | | SURVEY FOR EXACT SETBACK FROM BUILDING TO PROPERTY | | | LINE. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-05 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2006-12-05 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2006-12-05 16:41:15 | BUILDING REVIEW CHECKLIST: | | | 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED | | | DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER. | | | | | | 2- REVISE ENERGY CALCULATIONS: | | | A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE | | | BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF | | | 2004 FBC. | | | B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTES. | | | C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR | | | TYPES. | | | D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL | | | SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS. | | | E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED | | | ADDRESS AND BUILDER NAME. | | | | | | 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT | | | LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE | | | PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE | | | WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE | | | 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL | | | DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE | | | SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING | | | SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE | | | ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE | | | BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO | | | SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT | | | BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE | | | FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE | | | CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED | | | DOESN'T PROVIDE ALL THIS INFORMATION. | | | | | | 4- SHOW ACCESSIBLE ROUTE FROM PARKING SPACE TO ALL | | | APARTMENT ENTRANCES, RECREATIONAL AREAS AND PUBLIC | | | BUILDINGS.WHERE ARE THE DRAWINGS?. | | | | | | 5- INFORMATION REGARDING HANDICAPPED UNITS AND | | | ADAPTABLE UNITS IS CONFUSING.ACCORDING TO FAIR | | | HOUSING ACT,"ALL"GROUND FLOOR UNITS MUST BE | | | "ACCESSIBLE"FROM THE PARKING SPACE TO THE UNIT | | | ENTRANCE. THEN,ALL THE UNITS MUST BE "ADAPTABLE"PER | | | FHA.INFORMATION ON SHEET A100 IS INDICATING THAT | | | THERE ARE 9 ADAPTABLE UNITS ON ACCESSIBLE ROUTE.IF | | | THE INTENTION IS TO GO BEYOND FHA AND TO HAVE FULLY | | | HANDICAPPED UNITS, THEN CLARIFY THAT SUCH UNITS WILL BE | | | FULLY HANDICAPPED UNITS, NOT ADAPTABLE. | | | | | | 6- SHEET A004: | | | A) MISSING UNIT MODEL TYPE IN PROJECT TABULATION | | | CHART. | | | B) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET | | | A004 AND SHEETS A201AND A303.REVISE AS REQUIRED. | | | NEED CORRECT AREAS TO ESTIMATE BUILDING VALUATION. SEC. | | | 108.3 CITY AMENDMENTS TO FBC 2004. PROVIDE PORCHES, | | | BALCONIES AND BUILDING AREAS. | | | | | | 7- SHEET A101: | | | A) HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND | | | CHAPTER 11 FBC 2004 CAN'T OVERLAP TO ACCOMPLISH TOTAL | | | NUMBER OF REQUIRED PARKING SPACES.NEED TO PROVIDE | | | SEPARATE HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND | | | PUBLIC ASSEMBLY AREAS.SEE TABLE ON SECTION 11-4.1.2 | | | FOR REQUIRED NUMBER OF PARKING SPACES. THIS COMMENT | | | APPLIES TO BUILDINGS F AND C FOR MIXED USE BUILDINGS. | | | | | | B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND | | | ACCESSIBLE ROUTES FROM PARKING SPACES TO RESIDENTIAL | | | UNITS AND PUBLIC ASSEMBLY BUILDINGS TO VERIFY | | | COMPLIANCE WITH FAIR HOUSING ACT AND CHAPTER 11 FBC | | | 2004. | | | | | | C) SPECIFY IF PROVIDING VISITORS PARKING SPACES TO | | | VERIFY COMPLIANCE WITH FAIR HOUSING ACT. | | | | | | 8- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL | | | MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT | | | NEEDS TO BE REVIEWED FOR SECTION 504 OF THE | | | REHABILITATION ACT COMPLIANCE. | | | | | | 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED. | | | ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO | | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER | | | PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO | | | ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT | | | APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY. | | | | | | B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR | | | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. | | | | | | C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR. | | | | | | D) SLIDING GLASS DOORS. PROVIDE FLORIDA PRODUCT | | | APPROVAL COVER PAGE. | | | | | | E) ROOF SHINGLES. NEED FLORIDA PRODUCT APPROVAL | | | COVER PAGE. | | | | | | F) RIDGE VENT. NEED FLORIDA PRODUCT APPROVAL COVER | | | PAGE. | | | | | | G) 770-D ROOF LOUVER. NEED FLORIDA PRODUCT APPROVAL | | | COVER PAGE. | | | | | | H) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL | | | ASSEMBLYU905. | | | | | | I) CEMENTITIOUS PANELS FOR ENTRY OVERHANGS. SEE | | | DETAIL 11/A705. | | | | | | J) FALSE SKYLIGHT. SEE ELEVATIONS. | | | | | | K) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER | | | HEATER. | | | | | | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 11- SHEET A103: | | | A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES | | | HEIGHT 48" MAX. | | | | | | B) PROVIDE DETAILS/SPECS FOR GRAB BARS | | | REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2 | | | CITY AMENDMENTS TO FBC 2004. | | | | | | 12- SHEET A104: | | | A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S | | | THE QUESTION MARK FOR?. | | | B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON | | | CHAPTER 11 FBC 2004. | | | | | | 13- SHEET 110: | | | A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE | | | BLOCK THICKNESS. | | | B) DETAIL 18: REQUIRES 2X10 JOISTS AT 16" OC. REVISE | | | UNDER STAIRS DETAILS TO MATCH THIS ASSEMBLY. | | | C) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE. | | | REFERENCE UL 2004, NOT UL 1999. | | | | | | 14- SHEET A201:CLARIFY SQUARE FOOTAGES.ALSO, | | | COORDINATE ALL THESE AREAS WITH GENERAL AREA TABULATION | | | ON SHEET A004. | | | | | | 15- SHEET A303: | | | A) VENTILATION CALCULATIONS: COORDINATE SIZE OF | | | RIDGE VENT. SEE RIDGE VENT PRODUCT APPROVAL FOR | | | REQUIRED OPENING. REVISE CALCULATIONS AS REQUIRED. | | | REVISE DETAIL 16/A705 AS REQUIRED. | | | | | | B) GENERAL ROOF NOTE #2 CALLS FOR DETAIL 14/A705. | | | MISSING THAT DETAIL. | | | | | | 16- SHEET A400: | | | A) ALL DETAILS TO SPECIFY PRESSURE TREATED WOOD (OR | | | ANY OTHER APPROVED METHOD TO ISOLATE WOOD WHEN IN | | | CONTACT WITH CONCRETE OR CONCRTE BLOCK). SEC. 2304.11 | | | FBC 2004. | | | | | | 17- SHEET A500: | | | A) SECTION 17: FLOOR ASSEMBLYL-521 AND INFORMATION | | | ON TYPICAL FLOOR CONSTRUCTION ON SAME DRAWING DON'T | | | MATCH. REVISE AS REQUIRED. ALSO, INFORMATION DOESN'T | | | MATCH SPECIFICATION SHOWN ON SHEET A111. | | | B) REVISEINFORMATION ON UL L-521 ON SHEET A111. | | | SEE 2004 UL BOOK AND REVISE SPECS TO MATCH SUCH | | | LISTING. | | | C) SPECS ON WALL ASSEMBLY U905 DOESN'T MATCH | | | INFORMATION SHOWN ON SAME DRAWING POINTING TO WALL | | | AREAS. REVISE AS REQUIRED. | | | | | | D) PROVIDE INFORMATION THAT ADDRESSES MINIMUM LABELS | | | OF SOUND INSULATION AS REQUIRED BY SEC. 1207.2 AND | | | 1207.3. | | | | | | E) PROVIDE FIREBLOCKING AT ROOF ASSEMBLY | | | INTERSECTION. FLOOR ASSEMBLY NOTE ON DETAIL 17 CLEARLY | | | SPECIFIES TO SEAL JOINTS AT WALL . THIS IS NOT | | | SPECIFIED AT CEILING AREA.SEC. 717 FBC 2004. | | | | | | 18- SHEET A501:MISSING DETAIL 14/ A705 SPECIFIED ON | | | WALL SECTION 16 AND 18. | | | | | | 19- SHEET A701.1:DETAIL 01: HOW IS THE FASTENER | | | EMBEDED 1-1/4" IN TO THE BUCK IF THE BUCK IS ONLY 1X | | | THICK. REVISE AS REQUIRED. | | | | | | 20- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO | | | BE PRESSURE TREATED. REVISE DETAILS 01 AND 06 AS | | | REQUIRED. | | | | | | 21- SHEET A705: | | | A) DETAIL 02: REVISE FLASHING FASTENER SPACING AS | | | REQUIRED BY ROOFING APPLICATION STANDARD RAS 111. | | | | | | B) REVISE DETAIL 16. SEE RIDGE VENT PRODUCT APPROVAL | | | FOR RIDGE CUT OUT DIMENSION. | | | | | | C) PROVIDE COMPLETE STRUCTURAL DETAIL SHOWING | | | INSTALLATION OF FALSE SKYLIGHT TO COMPLY WITH SEC. 1609 | | | FBC 2004. | | | | | | 22- SHEET A706.1: | | | A) DETAIL 00 (?): CHECK VENT HOOD SPECIFICATIONS FOR | | | MIN. CLEARANCE REQUIRED FROM THE RANGE. PROVIDE VENT | | | HOOD SPECS AND REVISE DETAIL AS REQUIRED. | | | | | | 23- SHEET S-1:FOUNDATION PLAN STILL SHOWS A DROP AT | | | THE ENTRANCE TO UNITS. ALL GROUND FLOOR UNITS NEED TO | | | COMPLY WITH FAIR HOUSING ACT. REVISE AS REQUIRED. | | | | | | 24- SHEET S-2: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6 | | | FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE | | | SIMPSON CATALOGUE. | | | | | | 25- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION | | | OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS | | | FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-12-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-17 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-17 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2006-12-17 19:34:46 | ELEC OK, STAMPED PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-26 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-26 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2006-11-26 11:01:17 | MERRY PLACE | | | | | | 417 LILAC COURTTYPE III BLDG. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME | | | NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME | | | ADDITIONAL INFORMATION. | | | | | | ********** UNSAT ************* | | | | | | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR | | | THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE | | | DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER | | | ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON | | | SAID CIRCUIT. | | | MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS | | | AS NOTED IN CODES ABOVE. | | | | | | 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING | | | CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE | | | LOCATED ON PLANS AND IS REQUIRED. | | | | | | 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE | | | ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3, | | | 230.42 ETC | | | | | | 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES | | | PERMITTED IN STORAGE AREAS. | | | (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING | | | IS NOT SHOWN, A MIN | | | 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE | | | DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED. | | | PLEASE ADJUST | | | | | | 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT | | | LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS | | | AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS | | | OF 5KW? | | | PLEASE ADJUST. | | | 220.21 | | | | | | 6) NOTE: PLEASE SEE THE HOUSE PANEL ON E-311 IS BEING | | | SHOWN AS 100MLO AND THE RISER SHOWS THIS AS 60A MLO. | | | IT IS KNOWN THAT A 60A BREAKER IS FEEDING THIS PANEL. | | | | | | 7) NOTE: PLEASE SEERISER SHEET E312, RISER FOR OTHER | | | BUILDING TYPES NO "X" OUT AS DONE ON OTHER PLANS. THE | | | BUIDLIGN TYPE RISER SHOULD CORRELATE TO THIS PEMITTED | | | SET ONLY. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF | | | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE | | | DO NOT HESITATEIN CONTACTING THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-12-05 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-12-05 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2006-12-05 13:00:05 | SEE 06101116 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-11-22 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-11-22 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-11-22 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2006-11-22 15:40:19 | WE DO NOT HAVE THE CIVIL DWGS FOR THIS PERMIT PROJECT | | | BUT WE REVIEWED,MADE FOLLOWING COMMENTS TO EXPEDITE | | | THE PERMITTING PROCESS: PLEASE PROVIDE FOLLOWING INFO | | | IN YOUR CIVIL DRAWINGS FOR THIS PERMIT SITE: | | | 1.DID YOU MAKE ANY CHANGES IN STORM WATER/DRAINAGE | | | SYSTEM FROM PREVIOUS MASTER PERMIT? PLEASE TELL US WHAT | | | CHANGES YOU MADE IN WRITING AND MUST BE APPROVED FROM | | | SFWMD ALSO. AND A COPY OF SFWMD. | | | 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON CIVIL | | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | | MUST MEET PER ADA,,ETC., | | | 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION FOR THIS PERMIT PROJECT MUST MEET FL | | | BLDG CODE, PLEASE SHOW ON THE DRAWINGS., | | | 5. HOW YOU CONNECT TO THE ROOF DRAINS ? WHERE THE ROOF | | | DRAINS GO? | | | 6. PLEASE SHOW ON DRAWINGS,POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE | | | 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 8. | | | ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR | | | THIS BUILDING SITE FOR STORM WATER DRAIN. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-01 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-01 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2007-03-01 14:11:34 | *****APPROVED***** | | | | | | | | | ADDITIONAL SETS OF PLANS WERE SUBMITTED FOR THIS MERRY | | | PLACE PROJECT.SHEETS A403 AND E201 WERE STAMPED, | | | INITIALED, AND DATED 01/23/2007. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-23 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-23 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2007-01-23 10:14:45 | *****APPROVED***** | | | | | | | | | | | | COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 12/01/2006 | | | HAVE BEEN ADDRESSED.SHEETS A403 AND E201 WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-01 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2006-12-01 14:56:55 | *****DENIED***** | | | | | | | | | | | | 1. NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE | | | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. | | | | | | 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF | | | | | | 3.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY | | | THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING LILAC | | | COURT.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. | | | INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN | | | HEIGHT. | | | | | | 4.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 5.FIRE EXTINGUISHERS ARE TO BE 2A-10BC RATED. | | | | | | 6.AS PER NFPA 101 - 10.2.8.1 -2003 EDITION, | | | INTERIOR FINISH FOR WALLS AND CEILINGS IN AN | | | UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR CLASS | | | "B". | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-67221 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-29 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-29 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2006-12-29 13:02:53 | SEPARATE GAS PERMIT REQUIRED. SUBMIT PLANS/REQUIREMENTS | | | WITH THE GAS PERMIT APPLICATION. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-18 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-18 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2006-12-29 13:01:57 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | NOTE: 1ST REVIEW UNDER PERMIT | | | | | | 1B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS | | | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST | | | REMOTEAPPLIANCE FOR EACH UNIT. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-28 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-28 |
Time |
15:55 |
Sent To |
B |
|
| Notes |
| 2008-02-28 15:55:32 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
08:47 |
Sent To |
P |
|
| Notes |
| 2008-02-19 08:47:16 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-26 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-26 |
Time |
15:02 |
Sent To |
B |
|
| Notes |
| 2007-11-26 15:02:51 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-02 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-02 |
Time |
10:01 |
Sent To |
M |
|
| Notes |
| 2007-11-02 10:01:22 | TO "TGORDON" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-03 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-03 |
Time |
08:26 |
Sent To |
B |
|
| Notes |
| 2007-08-03 08:26:38 | TO "JGOMEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-28 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-28 |
Time |
15:19 |
Sent To |
B |
|
| Notes |
| 2007-06-28 15:19:49 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-04 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-04 |
Time |
11:54 |
Sent To |
B |
|
| Notes |
| 2007-06-04 11:55:01 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-27 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-27 |
Time |
19:04 |
Sent To |
FIRE |
|
| Notes |
| 2007-02-27 19:06:03 | TO "F" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-18 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-18 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2006-12-18 15:31:30 | TO "COMM" BD#28/PLANS ON RACK/12 ROLL AND 1 BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-05 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2006-10-31 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2006-11-03 11:43:19 | 11/3/06--SUBMITTAL ROUTED TO "COMM" BD#57 W/ ORIGINAL | | | APPL. PACKAGE | | 2006-10-31 10:04:17 | (PLANS ROUTED TO INCOMING TODAY) TO "COMM" BD#57/PLANS | | | ON RACK 14 ROLLS/1 BOX--EXPEDITED PERMIT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-05 |
Time |
08:25 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-11-05 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2007-11-05 08:26:29 | MECH. REVISION TO PAGES M201 AND M202. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-12-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-20 |
Time |
11:56 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-12-20 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-17 |
Time |
13:34 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2006-11-17 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2006-11-17 13:36:04 | *** PROVISO *** | | | 1) UNITS (A1) UPPER AND LOWER,RETURN AIR TRANSFER | | | GRILLS TO MASTER BEDROOM SUITE NEED TO BE 14"X 8", SEE | | | 2004 FBC/M 601.4. | | | | | | 2) CLOTHES DRYER VENTS MAY NOT EXCEED THE | | | MANUFACTURER'S SPECIFICATION'S. | | | | | | 3) AHU CLOSET DOORS NEED TO BE LOUVERED OR GRILLS NEED | | | TO BE INSTALLED FOR RETURN AIR, SEE 2004 FBC/M 601.4. | | | | | | 4) LAUNDRY ROOM DOORS NEED TO BE LOUVERED OR GRILLS | | | NEED TO BE INSTALLED FOR COMBUSTION AIR, SEE 2004 FBC/M | | | 701.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-02-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-23 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-23 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2008-02-23 18:29:19 | REVISION OK--SHT P303 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-09 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-09 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2007-03-09 16:57:17 | PLUMBING PASSED/'PROVISO: SHEET P402 RISER 4S. 3" STACK | | | REQUIRED FOR THE WASH MACHINES. A REVISION IS REQUIRED. | | | --GAS INFORMATION AND PLANS TO BE SUBMITTED AT THE | | | TIME OF APPLICATION |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-29 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-29 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2006-12-29 15:04:56 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | NOTE: 1ST REVIEW UNDER PERMIT | | | | | | **********FROM PREVIOUS REVIEW********** | | | | | | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF | | | APPLICATION SUBMITTAL PER RESPONSE. | | | | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. DELETED | | | 6. OK | | | 7. OK | | | 8. OK | | | 9.OK NOT REQUIRED FOR THIS BUILDING. | | | 10. OK NOT REQUIRED THIS BUILDING. | | | 11. OK | | | 12. OK | | | 13. OK (UNIT LOCATION ONLY) | | | 14. OK. NOT REQUIRED FOR THIS BUILDING. | | | 15. OK. NOT REQUIRED FOR THIS BUILDING. | | | 16. OK. NOT REQUIRED FOR THIS BUILDING. | | | 17. OK. NOT REQUIRED FOR THIS BUILDING. | | | 18. OK. NOT REQUIRED FOR THIS BUILDING. | | | 19. OK. NOT REQUIRED FOR THIS BUILDING. | | | 20. OK. NOT REQUIRED FOR THIS BUILDING. | | | 21. OK. NOT REQUIRED FOR THIS BUILDING. | | | | | | 22. SHTS P201 & P202 PLAN KEY NOTE #2 INDICATES | | | KITCHEN SINK ARM IS RUN UNDER THE SLAB, | | | BUT THE 3S RISER DIAGRAM ON SHT P402 | | | INDICATES THE SINK ARM IS ABOVE THE SLAB | | | PLEASE CLARIFY AND CORRELATE THE NOTES, | | | FLOOR PLAN, AND RISER DIAGRAM. SECTION | | | 106.1.1. | | | ****RESPONSE NOTED. NO ACTION TAKEN. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | 23. OK | | | 24. OK. (GAS NOTE) | | | 25. OK. NOT REQUIRED FOR THIS BUILDING | | | 26. OK | | | | | | 27. SUBMIT A BUILDING DRAIN SANITARY | | | RISER DIAGRAM ISOMETRIC THAT REFLECTS | | | THE FLOOR PLAN FOR EACH BUILDING. | | | SECTION 106.1.5.1.3. SHOW ALL PIPE | | | SIZES, RISER LOCATIONS, TRAPS, VENTS, | | | AND DFU'S AS THEY ACCUMULATE IN THE | | | SYSTEM. | | | ****RESPONSE NOTED. RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN. CLEANOUT AT THE BACK OF THE BUILDING NOT | | | SHOWN. SHOW CLEANOUTS REQUIRED BY SECTION 708.3.3, | | | CHANGE OF DIRECTIONGREATER THAN 45 DEGREES. | | | ****RESPONSE NOTED, BUT THE CLEANOUT AT THE BACK OF THE | | | BUILDING SHOWN ON THE FLOOR PLAN IS STILL NOT SHOWN ON | | | THE RISER DIAGRAM. | | | | | | 28. OK | | | 29. OK. NOT REQUIRED THIS BUILDING. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | SUBMIT ONE SET OF PLANS FROM FIRST | | | REVIEW FOR COMPARISON TO EXPEDITE 2ND | | | REVIEW. | | | | | | **************NEW COMMENTS************** | | | | | | 1B. OK | | | 2B. OK | | | 3B. OK | | | | | | 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS | | | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST | | | REMOTEAPPLIANCE FOR EACH UNIT. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2 | | | | | | ****RESPONSE NOTED, ALL INFORMATION/PLANS TO BE | | | SUBMITTED WITH GAS PERMIT APPLICATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-18 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-18 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2006-11-18 15:49:44 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | NOTE: 1ST REVIEW UNDER PERMIT | | | | | | **********FROM PREVIOUS REVIEW********** | | | | | | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF | | | APPLICATION SUBMITTAL PER RESPONSE. | | | | | | 2. OK | | | | | | 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY | | | WITH SECTION 11-4.24.7 FAUCETS. PLEASE | | | INDICATE COMPLIANCE ON DETAIL. | | | ****RESPONSE NOTED. NOTE REFERENCED INDICATES | | | COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE | | | FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE | | | SINKS. (LEVER- OPERATED, PUSH-TYPE ETC). | | | | | | 4. SHT A104 GENERAL NOTES II(5)(C) GRAB | | | BAR HEIGHTS SHALL BE 33" MIN. TO 36" | | | MAX. PAGE 6.5 FHA DESIGN MANUAL. | | | ****RESPONSE NOTED. NOTE NOT CORRECTED. | | | | | | 5. DELETED | | | | | | 6. SHT A104 GENERAL NOTES: II(4)(G) SINK | | | SHALL HAVE FORWARD APPROACH PER SECTION | | | 11-4.24.5. SHOW ON DETAIL. | | | ****RESPONSE NOTED. COMMENT NOT ADDRESSED. | | | | | | 7. SHT A201 DETAIL 07 SUPERIMPOSE THE | | | CLEAR FLOOR SPACE FOR THE W/C AS | | | REQUIRED ON PAGE 7.43. | | | ****RESPONSE NOTED.NO ACTION TAKEN. | | | | | | 8 SHTS A201 THRU A205 INDICATE | | | SPECIFICATION "A" OR "B" AS REQUIRED ON | | | PAGES 7.34 & 7.35 FHA DESIGN MANUAL. | | | ****RESPONSE NOTED. NO ACTION TAKEN. | | | | | | 9.OK NOT REQUIRED FOR THIS BUILDING. | | | 10. OK NOT REQUIRED THIS BUILDING. | | | | | | 11. SHT A205 ADCP ACCESSIBLE UNIT PLAN NOTES LEGEND | | | SHALL CHANGE REFERENCE STANDARD TO FHA-98 AMENDMENTS. | | | ****RESPONSE NOTED. THIS COMMENT WAS BECAUSE OF THE | | | FHA-1996 NOTE AT THE BOTTOM OF THE LEGEND. RESPONSE IS | | | CORRECT IN THE FACT THAT 7%, (10 REQUIRED, 9 SHOWN), OF | | | THE UNITS ARE TO BE FULLY ACCESSIBLE. ACCESSIBLE DOES | | | NOT MEAN ANY PORTION SHALL BE ADAPTABLE AS INDICATED IN | | | SOME NOTES. ALL FIXTURES REQUIRED TO BE ACCESSIBLE | | | SHALL BE ACCESSIBLE WHEN THE UNIT IS BUILT. | | | | | | 12. SHT A205 HDCP ACCESS. UNIT PLAN | | | NOTES LEGEND:NOTE #2 SINK SHALL BE | | | ACCESSIBLE, NOT ADAPTABLE AS STATED. | | | IF UNIT IS ACCESSIBLE, THEN IT SHALL BE | | | BUILT ACCESSIBLE. SHOW CLEAR FLOOR | | | SPACE. | | | ****RESPONSE NOTED. BUT WE ARE TALKING ABOUT THE | | | ACCESSIBLE UNITS, NOT THE ADAPTABLE UNITS IN THIS | | | COMMENT. (SEE COMMENT 11 ABOVE). | | | | | | 13. OK (UNIT LOCATION ONLY) | | | 14. OK. NOT REQUIRED FOR THIS BUILDING. | | | 15. OK. NOT REQUIRED FOR THIS BUILDING. | | | 16. OK. NOT REQUIRED FOR THIS BUILDING. | | | 17. OK. NOT REQUIRED FOR THIS BUILDING. | | | 18. OK. NOT REQUIRED FOR THIS BUILDING. | | | 19. OK. NOT REQUIRED FOR THIS BUILDING. | | | 20. OK. NOT REQUIRED FOR THIS BUILDING. | | | 21. OK. NOT REQUIRED FOR THIS BUILDING. | | | | | | 22. SHT P201 PLAN KEY NOTE #2 INDICATES | | | KITCHEN SINK ARM IS RUN UNDER THE SLAB, | | | BUT THE 3S RISER DIAGRAM ON SHT P402 | | | INDICATES THE SINK ARM IS ABOVE THE SLAB | | | PLEASE CLARIFY AND CORRELATE THE NOTES, | | | FLOOR PLAN, AND RISER DIAGRAM. SECTION | | | 106.1.1. | | | ****RESPONSE NOTED. NO ACTION TAKEN. | | | | | | 23. SHTS P301 THRU P310 PLAN KEY NOTES #7 | | | PRESSURE RELIEF VALVE IS INDICATED AS | | | RUNNING UNDER THE SLAB. THE RELIEF VALVE | | | DISCHARGE LINE SHALL NOT HAVE ANY | | | TRAPPED SECTIONS PER SECTION 504.6.1. | | | ****RESPONSE NOTED. SHT P301 NOT SUBMITTED THIS | | | BUILDING. NO CLARIFICATION SHOWN. | | | | | | 24. OK. (GAS NOTE) | | | 25. OK. NOT REQUIRED FOR THIS BUILDING | | | 26. OK | | | | | | 27. SUBMIT A BUILDING DRAIN SANITARY | | | RISER DIAGRAM ISOMETRIC THAT REFLECTS | | | THE FLOOR PLAN FOR EACH BUILDING. | | | SECTION 106.1.5.1.3. SHOW ALL PIPE | | | SIZES, RISER LOCATIONS, TRAPS, VENTS, | | | AND DFU'S AS THEY ACCUMULATE IN THE | | | SYSTEM. | | | ****RESPONSE NOTED. RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN. CLEANOUT AT THE BACK OF THE BUILDING NOT | | | SHOWN. SHOW CLEANOUTS REQUIRED BY SECTION 708.3.3, | | | CHANGE OF DIRECTIONGREATER THAN 45 DEGREES. | | | | | | 28. OK | | | 29. OK. NOT REQUIRED THIS BUILDING. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | SUBMIT ONE SET OF PLANS FROM FIRST | | | REVIEW FOR COMPARISON TO EXPEDITE 2ND | | | REVIEW. | | | | | | **************NEW COMMENTS************** | | | | | | 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS | | | SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1 | | | UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF | | | UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES | | | BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN | | | BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E" | | | INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN | | | BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F" | | | INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1 | | | PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE | | | INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION | | | 106.1.1. | | | | | | 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES | | | LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS | | | ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT | | | THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE. | | | IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE | | | UNIT CAN BE ADAPTABLE. | | | NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996. | | | PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES | | | "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY | | | ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT". | | | THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE | | | OR FULLY ACCESSIBLE. | | | | | | 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7% | | | TO BE FULLY "ADAPTABLE" PLEASE CLARIFY. | | | | | | 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS | | | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST | | | REMOTEAPPLIANCE FOR EACH UNIT. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2006-11-16 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2006-11-16 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2006-11-16 10:28:09 | LANDSCAPING PLANS SHALL BE APPROVED BOFORE A CO IS | | | ISSUED. |
|
|