Plan Review Details - Permit 06101053
Plan Review Stops For Permit 06101053
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-31 Cont ID  
Sent By lursu Date 2008-01-31 Time 15:36 Rev Time 0.00
Received By lursu Date 2008-01-31 Time 15:36 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status   Date 2007-10-01 Cont ID  
Sent By lursu Date 2006-12-21 Time 10:17 Rev Time 0.00
Received By jgomez Date 2006-12-21 Time 10:17 Sent To  
Notes
2006-12-21 10:17:44A NEW PARCEL CONTROL NUMBER WAS ISSUED BY THE PROPERTY
 APPRAISER'S OFFICE .THE PERMIT WAS ATTACHED TO THE
 VALID PCN FROM THE TEMPORARY PCN USED INITIALLY.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2008-04-14 Cont ID  
Sent By jgomez Date 2008-04-14 Time 17:11 Rev Time 0.00
Received By jgomez Date 2008-04-14 Time 17:11 Sent To PC
Notes
2008-04-14 17:48:26DOOR PRODUCT APPROVAL SUBMITTAL CHECKLIST:
  
 1- AS AGREED ON PROVISO DATED 4/12/07SEPARATE PERMIT
 APPLICATION FOR"INSWING" DOOR IS REQUIRED. SEE
 ATTACHED COPY OF PROVISO DATED 4/12/07.
  
 2-DOORIS REQUIRED TO HAVEHURRICANE MISSILE IMPACT
 PROTECTION.PROVIDE PRODUCT APPROVAL FOR INSWING DOOR
 WITH IMPACT GLASS OR PROVIDE COMPLETE INFORMATION FOR
 PROPOSED MISSILE IMPACT PROTECTION TO BE PROVIDED.
 AND,PROVIDE COMPLETE MISSILE IMPACT PROTECTION
 PRE-STORM PREPARATION PLAN TO BE APPROVED BY THE
 BUILDING OFFICIAL. THIS IS REQUIRED BY THECITY IMPACT
 PROTECTION STANDARD ITEMS #13 AND #14. SEE ATTACHED
 COPY.
  
 3- PROVIDE PRODUCTAPPROVAL FOR SELECTED MISSILE
 IMPACT PROTECTION PRODUCT ANDCOMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.ALSO, CLEARLY MARK ON
 PRODUCT APPROVAL DRAWINGS SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACINGTO BE USED TO VERIFY
 COMPLIANCE WITH PRODUCT APPROVAL PROPOSED INSTALLATION
 AND SEC. 1609 FBC 2004.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-03-11 Cont ID  
Sent By jgomez Date 2008-03-11 Time 15:40 Rev Time 0.00
Received By jgomez Date 2008-03-11 Time 15:40 Sent To PC
Notes
2008-03-11 15:43:38BUILDING SUBMITTAL CHECKLIST.
  
 1- NEED TO PROVIDE 3 COPIES OF PRODUCT APPROVAL FOR
 "INSWING" ENTRY DOOR AT THE COUNSELING OFFICE UNDER A
 SEPARATE PERMIT AS REQUESTED AND AGREED ONPROVISO
 DATED 4-12-07. SEE ATTACHED COPY OF PROVISO.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-11-30 Cont ID  
Sent By jgomez Date 2007-11-30 Time 16:02 Rev Time 0.00
Received By jgomez Date 2007-11-30 Time 16:02 Sent To PC
Notes
2007-11-30 16:03:17TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-10-31 Cont ID  
Sent By jgomez Date 2007-10-31 Time 12:45 Rev Time 0.00
Received By jgomez Date 2007-10-31 Time 12:45 Sent To PC
Notes
2007-10-31 12:57:46TRUSS PACKAGE BUILDING REVIEW CHECKLIST.
  
 1- TRUSS LAYOUTSNEED TO SIGNED AND SEALED AND PROVIDE
 ALL ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 1- THIS PROJECT HAS A RESIDENT INSPECTOR ON SITE,
 THEREFORE, NEED TO PROVIDE THREE COMPLETE SETS OF TRUSS
 DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-10-15 Cont ID  
Sent By jgomez Date 2007-10-15 Time 16:28 Rev Time 0.00
Received By jgomez Date 2007-10-15 Time 16:28 Sent To PC
Notes
2007-10-15 16:48:09HANDICAPPED RAMP REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-10-02 Cont ID  
Sent By jgomez Date 2007-10-01 Time 18:57 Rev Time 0.00
Received By jgomez Date 2007-10-01 Time 18:45 Sent To PC
Notes
2007-10-02 09:16:29BUILDING C-3 RAMP REVISION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004.
  
 1- PRODUCT APPROVAL FL5267 SUBMITTEDIS A "HOLLOW
 METAL FRAME" ASSEMBLY ONLY.NEED TO PROVIDE THE
 PRODUCT APPROVAL FOR THE DOOR TO BE USED AS REQUIRED BY
 GENERAL NOTE #2 SHOWN ON SHEET 1 OF 4 OF DRAWING
 FL-640.
  
 2-"HOLLOW METAL FRAME ANCHORING" SYSTEM SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER. SEESHEET 1 OF 4 OFDRAWING FL-640
 SUBMITTED AND THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER.SUBMIT PRODUCT APPROVAL THAT MEETS OR
 EXCEEDS CALCULATED DESIGN PRESSURES.
  
 REMAINDER:
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 3-HANDICAPPED RAMP REQUIRES A MINIMUM LENGTH OF 15'-4
 1/2" TO ACHIEVE THE MAXIMUM RATIO OF 1:12FOR A HEIGHT
 OF 1'-3 3/8".SEC. 11-4.8.2 FBC 2004. REVISE
 DIMENSIONS AS REQUIRED OR PROVIDE COMPLETE CALCULATIONS
 SHOWING HOW THE 15'-4 3/8" WAS ACHIEVED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 4- RE-SUBMITTAL FORM SAYS THAT NUMBER OF REVISED PAGES
 ARE SIX.ACTUAL NUMBER OF REVISED PAGES SUBMITTED ARE
 16. THEREFORE OWES $100 FOR CORRECT NUMBER OF REVISED
 PAGES.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-09-05 Cont ID  
Sent By jgomez Date 2007-09-05 Time 07:49 Rev Time 0.00
Received By jgomez Date 2007-09-05 Time 07:44 Sent To PC
Notes
2007-09-05 09:16:19BUILDING C-3 RAMP REVISION BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004.
  
 1- BUILDING SIZE WAS REDUCED TO ALLOW NEW HANDICAPPED
 RAMP AND STAIRS, BUT DIMENSIONS SHOWN ON REVISED SURVEY
 DON'T MATCH DIMENSIONS SHOWN ON SHEETS A202, A304,
 A810, S1. REVISE AS REQUIRED ALL DIMENSIONS AND SQUARE
 FOOTAGES.
  
 2- SHEET A002: REVISION IS JULY 27 OF 2006 OR 2007?.
 REVISE AS REQUIRED.
  
 3 SHEET A404: REVISE GRADE LINE ELEVATION AND FIRST
 FLOOR ELEVATION TO REPRESENT EXACT HEIGHTREQUIRED FOR
 THE RAMP AND STAIRS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 4- SHEET A521:
 A) PROVIDE COMPLETE SPECS AND DETAILS FOR RATED
 CEILING ASSEMBLY BETWEEN FIRST AND SECOND FLOOR TO
 VERIFY COMPLIANCE WITH CHAPTER 7 OF FBC 2004.
  
 B) CLARIFY WHAT'S THE HVAC DUCTWORK FOR? ACCORDING
 TO PLANS THIS IS THE OUTSIDE AREA OF THE FIRST FLOOR.
  
 5- SHEET A602.2:
 A) RAMP DOESN'T COMPLY WITH SEC. 11-4.8 FBC 2004.
 * DIMENSION SHOWN ON FLOOR PLAN IS NOT ENOUGH TO
 PROVIDE THE 1:12SLOPE RATIO.
 ALSO, CLEARLY PROVIDE FINISH FLOOR ELEVATION AT TOP AND
 BOTTOM OF RAMP TO VERIFY COMPLIANCE WITH PROPOSED
 SLOPE.
 ** SHOW LANDING ON TOP AND BOTTOM AS REQUIRED BY SEC.
 11-4.8.4(2).
 *** PROVIDE COMPLETE SPECIFICATIONS FOR CONTINUOUS
 STEEL ANGLE SHOWN ON GUARD/HANDRAIL DETAIL #06. SEC.
 106.1.2 CITY AMENDMETNS TO FBC 2004.
 **** DRAWING #07 IS A FLOOR PLAN, NOT ELEVATION. REVISE
 AS REQUIRED.
 ***** END OF HANDRAILS NEED TO COMPLY WITH SEC.
 11-4.8.5(6).
  
 B) STAIRS DON'T COMPLY WITH SEC. 11-4.9 FBC 2004.
 * NOSING DOESN'T COMPLY WITH SEC. 11-4.9.3 FBC 2004.
 ** FOUR RISERSAT 51/4"DON'T ADD UP TO 1'-8 3/4".
 REVISE AS REQUIRED. (ALS0, IT SAYS 5' INSTEAD OF 5".
 REVISE AS REQUIRED).
 *** END OF HANDRAILS NEED TO COMPLY WITH SEC.
 11-4.9.4(6) FBC 2004.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR NEW EXTERIOR DOOR TYPE SHOWN ON
 MAINTENANCE/STORAGE AREA.
 ***REMAINDER:DESIGNER OF RECORD TO REVIEW AND APPROVE
 IN WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
  
 REMAINDER:
 * PROVIDE ALLINFORMATION FOR ALL BUILDINGS IN THIS
 PROJECT REQUESTED ON PROVISOAT TIME OF PERMIT
 ISSUANCE TO AVOID DELAYS OR CONFLICTS.
 ** PROVIDE COMPLETE INFORMATION FOR TRUSS PACKAGE FOR
 ALL BUILDINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-10 Cont ID  
Sent By jgomez Date 2007-07-10 Time 10:52 Rev Time 0.00
Received By jgomez Date 2007-07-10 Time 10:52 Sent To PC
Notes
2007-07-10 10:56:36TRUSS PACKAGE CHECKLIST:
 1-A) ONLY TWO SETS WERE SUBMITTED. THIS TYPE OF
 PROJECT REQUIRES THREE COMPLETE SETS.THREE SIGNED AND
 SEALED SETS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND SEC. 61G15-23 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) TRUSS ENGINEER TO PROVIDE ALL THREE SETS WITH
 ORIGINAL SIGNATURE. COPY OF SIGNATURE IS NOT ALLOWED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 C) EVERY INDIVIDUALSHEETNEEDS TO HAVE
 ENGINEER'S ORIGINAL SEAL, SIGNATURE AND DATE.
 OTHERWISE, ENGINEER MAY WANT TO FOLLOW ALL CONDITIONS
 REQUIREDBY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE
 CODE TO COMPLY WITH THE SIGNING AND SEALING OF ALL
 SHEETS.INFORMATION SUBMITTED DOESN'T COMPLYWITH
 THIS SECTION.
  
  
 2- ENGINEER OF RECORD TO CHECK DETAILS GIVEN ON
 STRUCTURAL DRAWINGS FOR SUPPORT OF TRUSSES AT THE ENDS.
 TRUSS PACKAGE SHOWS DIFFERENT END CONNECTIONS.REVISE
 EITHER TRUSS PACKAGE OR ENGINEERED DRAWINGS AS REQUIRED
 TO MATCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-14 Cont ID  
Sent By jgomez Date 2007-06-14 Time 16:23 Rev Time 0.00
Received By jgomez Date 2007-06-14 Time 16:23 Sent To PC
Notes
2007-06-14 16:30:37REVISION CHECKLIST:
  
 1- THIS IS NOT A SUBMITTALBUT A REVISION ON
 PREVIOUSLY APPROVED PRODUCT APPROVALS. THEREFORE OWES
 $80.00 FOR REVISION FEES.
  
 2- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 DESIGNER OF RECORDAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. PRODUCT APPROVALS SUBMITTED
 DON'T SHOWDESIGNER OF RECORD APPROVAL IN WRITING.
  
 3- SINGLE HUNG WINDOWS PRODUCT APPROVAL:
 A) PROVIDE CURRENT PRODUCT APPROVAL FL42-R4. (ONE
 SUBMITTED IS FL 42-R1).
  
 B) PROVIDE ONLY ALL THE TECHNICAL INFORMATION
 (DRAWINGS, SPECS, ETC) THAT WAS SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. GO THE FLORIDA WEBSITE
 WWW.FLORIDABUILDING.ORG AND DOWNLOAD CORRESPONDING
 INFORMATION TO SPECIFIC MODEL TO BE INSTALLED.
  
 C) MAKE SURE ALL DRAWINGS ARE LEGIBLE.
  
 4- SLIDING GLASS DOORS:
 A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY.
  
 5- FIXED WINDOWS.
 A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY.
  
 6- SWING DOORS:
 A) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
  
 7- PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS AND
 CLEARLY IN THE PRODUCT APPROVAL DRAWINGS SPECIFIC
 MULLION SIZE AND ANCHORTYPE AND SPACING TO BE USED.
 SEC. 106.1.2CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE:
 RESUBMITTAL FEES FOR REVISIONS WILL BE CHARGED AGAIN ON
 NEXT SUBMITTAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-13 Cont ID  
Sent By jgomez Date 2007-04-12 Time 15:47 Rev Time 0.00
Received By jgomez Date 2007-04-12 Time 14:19 Sent To PC
Notes
2007-04-12 16:01:29BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL FOR "INSWING"ENTRY DOOR
 AT COUNSELING OFFICE UNDER A SEPARATE PERMIT.
  
 2- PROVIDE CORRECT INFORMATION FOR FLAT ROOF ASSEMBLY
 UNDER A SEPARATE PERMIT. (* ALL ENGINEERING SHEETS NEED
 ORIGINAL SEAL AND SIGNATURE. ** ENGINEERING TO MATCH
 ASSEMBLY SPECIFIED ON PLANS.*** CHECK ROOF SHEATHING
 THICKNESS.**** PROVIDE CORRECT PROJECT ADDRESS ON
 ENGINEERING SHEETS).
  
 2- PROVIDE CORRECT DRAWINGS FOR ENTRY DOOR.NOA
 02-0215.04 SUBMITTED HAS THE "INSWING" DOOR DRAWINGS.
 THIS IS A DADE COUNTY PRODUCT APPROVAL DIVISION MISTAKE
 THAT WAS ALREADYREVISED. NOW WEBSITE HAS CORRECT
 "OUTSWING" DOOR DRAWINGS. PROVIDE 3 COPIES, REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD.
  
 3-RINKER SPECIFICATIONS LETTER FOR 2 HOUR CONCRETE
 BLOCK: PROVIDE LETTER ADDRESSED TO THE CITY OF WEST
 PALM BEACH AND WITH CORRECT PROJECT NAME.THIS IS
 MERRY PLACE PROJECT, NOT BOCA DEVELOPMENT.
  
 4- SUBMIT ALL TRUSS DRAWINGS FOR REVIEW PRIORTO
 CONSTRUCTION/INSTALLATION. TRUSS PACKAGE TO BE REVIEWED
 AND APPROVED BY DESIGNER OF RECORDPRIOR TO
 SUBMITTAL.
  
 5- PROVIDE COPY OFTHE RECORDED MERRY PLACE PLAT FOR
 CITY RECORDS.
  
 8- PROVIDE 3 COPIES OF APPROVED AND RECORDED SURVEY
 SHOWING UNITY OF TITLE REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-28 Cont ID  
Sent By jgomez Date 2006-12-28 Time 16:28 Rev Time 0.00
Received By jgomez Date 2006-12-28 Time 16:28 Sent To  
Notes
2006-12-28 16:54:33BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2-A) NORTH WALL 15%OPENINGS ALLOWED PER TABLE 704.8
 FBC 2004AND SEC. 704.8.1 (AUTOMATIC SPRINKLER
 SYSTEM).NEED TO BE 2 HOURS WALL FIRE RESISTANCE.
 REVISE AS REQUIRED. SEE SURVEY FOR BUILDING SETBACK IN
 RELATIONSHIP TO PROPERTY LINE. TABLES 601, 602 AND
 704.8 APPLY. DOES WHY I ASKED FOR THE SURVEY TO VERIFY
 COMPLIANCE WITH THESE TABLES.
  
 B) DOOR SWINGS OUT TO PUBLIC RIGHT OF WAY ON EAST
 WALL. NEED DOOR THAT SWINGS IN.SEC. 3202.2 FBC 2004.
  
 ***NOTE: PROVIDE PRODUCT APPROVAL FOR INSWING DOOR.
 DESIGNER OF RECORD TO REVIEW IT AND APPROVE IT. SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004
  
 C) NORTH ARROW IN SURVEY IS POINTING TO THE WRONG
 DIRECTION. REVISE AS REQUIRED.
  
 D) ARCHITECT TO CHECK RECORDED SURVEY AND CHANGE ALL
 DIMENSIONS AS REQUIRED. THIS APPLIES TO ALL BUILDINGS.
 RECORDED SURVEY IS THE OFFICIAL LEGAL DOCUMENT FOR
 PROPERTY LINES AND BUILDING SEPARATION.
  
 E) SURVEY SHOWS EAST WALL TO BERIGHT ON THE
 PROPERTY LINE. THIS BUILDING HAS ABOUT 6 " SETBACK IN
 THE FOOTPRINT.NONE OF THE ARCHITECTURAL OR STRUCTURAL
 DRAWINGS SHOW EXACT DIMENSION.PROVIDE EXACT DIMENSION
 AND SURVEY TO SHOW THAT BUILDING FOOTING IS NOT
 ENCROACHING INTO THE PUBLIC RIGHT OF WAY.
  
 3- REVISION CLOUDS ON SHEET A004 DON'T ALLOW TO READ
 THE INFORMATION.
  
 4- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH. SEE PARKING SPACES FOR BUILDING C3.
 THERE IS AN ALLEY WHERE PARKING SPACES ARE SHOWN.
 REVISE AS REQUIRED.
  
 5- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA AS
 REQUIRED BY CHAPTER 13 FBC 2004.
  
 6- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH
 CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT
 NUMBER, ETC.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR. DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON ALL
 PLANS AND DETAILS. (NOT JUST THE ONES LISTED IN THE
 TRUSS ANCHOR SCHEDULE). PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC
 CONNECTORS.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 E) FIXED WINDOWS. NEED PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA
 02-0123.03 SUBMITTED IS FOR SMALL MISSILE IMPACT.
  
 F) ALUMINUM TUBE MULLIONS. NEED PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT
 RATING.
 ***INDICATE MULLION FASTENING. SECTION 1609FBC 2004
 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) FLAT ROOF: PROVIDE NAIL ENHANCING CALCULATIONS
 FOR PERIMETER AND CORNER AREAS USING RAS 117 STANDARD
 AS REQUIRED BY GENERAL LIMITATION #7 ON PAGE 32 OF 32
 OF NOA #03-0501.02 SUBMITTED.CALCULATIONS TO CLEARLY
 IDENTIFY NOA AND SPECIFICSELECTED ASSEMBLY.
  
  
 8) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 9- THE INTENTION OF THE CODE IS TO DETERMINE THE
 MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE
 BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY
 GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A
 SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE
 ALL EGRESS REQUIREMENTS SHALL BE MET. ROOMS COULD BE
 USED FOR ANY PURPOSE AT ANY TIME. PROOF OF THIS IS THAT
 OWNER CHANGED THE USE ALREADY. THAT'S WHY OCCUPANCY
 LOAD CALCULATIONS NEED TO BE ESTABLISHED BY THE LARGEST
 NUMBER COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1
 THROUGH 1004.1.3. ACCORDING TO THIS SECTION TABLE
 1004.1.2 FBC 2004 AND FLOOR PLANS, THE FLOOR AREA PER
 OCCUPANT SHALL BE CALCULATED FOR 5S.F..
 PROVIDE CALCULATIONS FOR NUMBER OF PEOPLE ON EACH ROOM
 OR SPACE TO VERIFY COMPLIANCE WITH TOTAL NUMBER OF
 PEOPLE.
  
  
 10-SHEET S-1 ROOF FRAMING PLAN PLAN CALLS FOR METAL
 TRELLIS. PROVIDE COMPLETE DRAWINGS/DETAILS AND PRODUCT
 APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 SEC. 1609 FBC 2004.
  
 11- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By jgomez Date 2006-12-06 Time 10:59 Rev Time 0.00
Received By jgomez Date 2006-12-06 Time 10:57 Sent To  
Notes
2006-12-06 11:47:44BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED
 DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER.
  
 2- REVISE ENERGY CALCULATIONS:
 A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE
 BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF
 2004 FBC.
 B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR
 TYPES.
 D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL
 SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS.
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED
 ADDRESS AND BUILDER NAME.
 F) OWNER/AGENT TO SIGN AND DATE ALL ENERGY FORMS.
 NOTE: THIS APPLIES TO ALL ENERGY FORMS FOR ALL
 BUILDINGS. CHECK ALL ENERGY FORMS TO BE SUBMITTED.
  
 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT
 LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE
 PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE
 WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE
 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL
 DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE
 SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING
 SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE
 ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE
 BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO
 SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT
 BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE
 FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE
 CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED
 DOESN'T PROVIDE ALL THIS INFORMATION.
  
 4- SHEET A004:
 A) OCCUPANCY LOAD CALCULATIONS NEED TO BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
 ACCORDING TO THIS SECTION,TABLE 1004.1.2 FBC 2004 AND
 FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE
 CALCULATED FOR 5S.F. PER PERSON. REVISE OCCUPANT LOAD
 CALCULATIONS AS REQUIRED.
  
 B) MISSING UNIT MODEL TYPE IN PROJECT TABULATION
 CHART.
 C) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET
 A004 AND SHEETS A202 AND A304.REVISE AS REQUIRED.
 NEED CORRECT AREAS TO ESTIMATE BUILDING VALUATION. SEC.
 108.3 CITY AMENDMENTS TO FBC 2004. PROVIDE PORCHES,
 BALCONIES AND BUILDING AREAS.
  
 5- SHEET A101:
 A) SPECIFY NUMBER OF PARKING SPACES REQUIRED BY
 ZONING FOR BUILDING C3 TO VERIFY COMPLIANCE OF
 HANDICAPPED SPACES PROVIDED AS REQUIRED BY CHAPTER 11
 FBC 2004.
  
 B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND
 ACCESSIBLE ROUTEFROM PARKING SPACE TO PUBLIC ASSEMBLY
 BUILDING C3TO VERIFY COMPLIANCE WITH CHAPTER 11 FBC
 2004.
  
 6- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL
 MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT
 NEEDS TO BE REVIEWED FOR SECTION 504 OF THE
 REHABILITATION ACT COMPLIANCE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED.
 ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER
 PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO
 ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT
 APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY.
  
 B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR.
  
 D) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLYU905.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 F) FIXED WINDOWS: NEED PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA
 02-0123.03 IS FOR SMALL MISSILE IMPACT RESISTANT
 WINDOWS. ALSO, PROVIDE FLORIDA COVER PAGE.
  
 G) ALUMINUM TUBE MULLIONS: NEED PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT
 RATING FOR MISSILE IMPACT. ALSO, PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 ***NOTE: FROM SUBMITTED NOA SPECIFY SPECIFIC FASTENING
 METHOD TO VERIFY COMPLIANCE WITH SEC. 1609 FBC 2004.
  
 H) ALUMINUM STOREFRONT WINDOWS: PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 I) LEASING/RES. SVC ENTRY DOORS: PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 J) FLAT ROOF: PROVIDE FLAT ROOF CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS PER RAS
 117 AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE
 OF NOA.
 PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE.NOTE:
 THIS APPLIES TO ALL PRODUCT APPROVALS.
 PROVIDE ONLY THE PAGES WITH THE APPROVED ASSEMBLY TO BE
 INSTALLED ALONG WITH ALL THE FRONT PAGES SHOWING ALL
 APPROVED COMPONENTS AND LAST PAGE WITH THE GENERAL
 LIMITATIONS.
  
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- SHEET A103:
 A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES
 HEIGHT 48" MAX.
  
 B) PROVIDE DETAILS/SPECS FOR GRAB BARS
 REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET A104:
 A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S
 THE QUESTION MARK FOR?.
 B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON
 CHAPTER 11 FBC 2004.
  
 13- SHEET 110:
 A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE
 BLOCK THICKNESS.
 B) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE.
 REFERENCE UL 2004, NOT UL 1999.
  
 14- SHEET A202:CLARIFY SQUARE FOOTAGES.ALSO,
 COORDINATE ALL THESE AREAS WITH GENERAL AREA TABULATION
 ON SHEET A004.
  
 15- SHEET A304: SEE PLUMBING COMMENTS AND SEC. 1611 FBC
 2004..
  
 16- SHEET A400: DOESN'T APPLY TO THIS BUILDING.
  
 17- SHEET A500: PROVIDE ONLY INFORMATION THAT
 CORRESPONDS TO THIS BUILDING.
  
 18- SHEETA701.1:DETAIL 01: HOW IS THE FASTENER
 EMBEDED 1-1/4" INTO THE BUCK IF THE BUCK IS ONLY 1X
 THICK. REVISE AS REQUIRED.
  
 19- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO
 BE PRESSURE TREATED. REVISE DETAILSAS REQUIRED.
  
 20- SHEET A704: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 21- SHEET A705: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 22- SHEET A706.1: PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS BUILDING.
  
 23- SHEET A706.2: PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS BUILDING.
  
 24- SHEET A707: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 25- SHEET A810:
 A) SEE COMMENTS ONSHEET A004 REGARDING OCCUPANT
 LOAD.
 B) SEE PLUMBING COMMENTS REGARDING PROPER FACILITY
 USE.FINAL FLOOR LAYOUTMAY AFFECT CALCULATIONS ON
 SHEET A004 AS WELL.
 C) MULTIPURPOSE ROOM AND COUNSELING AREA MAY BE
 COMBINED ALSO. TAKE THIS IN CONSIDERATION WHEN DOING
 OCCUPANT LOAD CALCULATIONS.
 D) NUMBER OF PEOPLE MAY AFFECT NUMBER OF EGRESS
 DOORS REQUIRED.
  
 26- SHEET S-2: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6
 FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE
 SIMPSON CATALOGUE.
  
 27- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION
 OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS
 FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 19:10 Sent To  
Notes
2007-08-23 19:11:05REV.OK

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By dpalmer Date 2006-12-18 Time 13:51 Rev Time 0.00
Received By dpalmer Date 2006-12-18 Time 07:33 Sent To  
Notes
2006-12-18 13:52:32REDLINED:
  
 700.12E FOR EM LTS.
 400A'S ON MAINS FOR TWO UNITS AND HOUSE PANEL.
 WATER HEATERNOT PERMITTED IN STAIRWAY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-26 Cont ID  
Sent By dpalmer Date 2006-11-26 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2006-11-26 Time 08:01 Sent To  
Notes
2006-11-26 12:27:58MERRY PLACE
  
 1713 N DIXIE HWY TYPE IV BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
 PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE
 INDICATED.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
 PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE
 WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON
 THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR
 INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 100
 WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS FIVE
 F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE ALONG
 EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR THIS
 CIRCUIT. PLEASE ALSO THE LOADS FOR THE OTHER EXTERIOR
 FIXTURES WHICH WERE ALSO NOT ADDED.
 PLEASE SEE ALL INTERIOR LIGHTS AS THE SAME SCENARIO
 TAKES PLACE. THE AMOUNT OF WATTAGE BASED ON THE
 FIXTURES SHOWN ON THE FIXTURE SCHEDULE AND PLANS DO NOT
 CORRELATE.
 PLEASE SEE THE FOLLOWING COMMENTS ALSO AS THE EM/EXT
 LIGHTS ARE NOT CIRCUITED.
  
 4) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT
 LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3
 ABOVE FOR LOADS.
  
 5) NOTE: PLEASE MISSING RECEPTACLE FOR 2FT OF WALL
 SPACE IN UNIT PER 210.52
  
 6) NOTE: PLEASE SEE 408.7, 240.24 AND 110.26 FOR THE
 LOCATION OF THE HOUSE ELECTRICAL PANEL SHOULD NOT BE
 LOCATED IN ANY STORAGE AREA AND/OR LOCATION WITH EASILY
 IGNITABLE MATERIALS OR FLAMMABLES.
  
 7) NOTE: PLEASE PROVIDE CIRCUITING FOR THE EXTERIOR
 EMERGENCY LIGHTS. PLEASE KNOW THESE SHALL NOT BE ON THE
 LOAD SIDE OF THE TIME CLOCK AS BEING INDICATED FOR
 STAIR LIGHTS. WHEN USING A ASTRONOMICAL TIME CLOCK,
 THESE SHALL WIRED ON THE LINE SIDE OF SAID TIME CLOCK.
  
 PLEASE SEE AS A SAFETY DESIGN ISSUE, IF THE STAIRS ARE
 ENCLOSED IN ANY FASHION AND CAN EVEN GET DARK ENOUGH IN
 THE MIDDLE OF THE DAY DUE TO OVER CAST OF DENSE CLOUDS,
 A PHOTO-CELL FOR CONTROL IN PLACE OF OR WIRED INLINE ON
 THE LOAD SIDE OF THE TIME CLOCK WOULD ENSURE THE
 MINIMUM FOOT CANDLES FOR STAIR WAYS AT ALL TIMES.
 PLEASE SEE LS 101 7.8.1.3,7.9.2.2
  
 8) NOTE: PLEASE SEE THE ELECTRICAL J-BOX FOR THE
 CONNECTION OF THE GAS HOT WATER HEATER IS BEING SHOWN
 LOCATED IN THE STAIRWAY LOCATION? PLEASE CLARIFY THIS.
 WHERE IS THE GAS WATER HEATER GOING TO BE INSTALLED?
 MAY NOT INTERFERE WITH MEANS OF EGRESS IN ANY WAY.
  
 9) NOTE: PLEASE SEE METER CENTER FOR THIS BUILDING TYPE
 SEEMS TO INDICATE BEING 400A RATED AND THE SERVICE
 ENTRANCE CONDUCTORS ARE ONLY RATED FOR 350A'S PER
 310.15B6. PLEASE EITHER INSTALL A MAIN BREAKER IN THE
 MC WHICH WILL LIMIT THE LOAD ON THE CONDUCTORS TO
 350A'S OR ADJUST THE CONDUCTORS FOR THE 400A SERVICE
 PROVIDED.
 PLEASE KNOW IF ADJUSTING THE SEC'S AND INCREASING THE
 SIZE TO 400 MCM, THEN PLEASE SEE 250.66 FOR THE SIZING
 OF THE GROUNDING ELECTRODE CONDUCTOR WHICH WILL BE
 REQUIRED TO BE INCREASED TO A 1/0. 310.15B6, 250.66,
 240.4, 240.6
  
 10) NOTE: PLEASE SEE E311 AS THE RATINGS FOR EQUIPMENT
 IS BEING NOTED AND BASED ON A MAIN RATING WITH SERIES
 RATED EQUIPMENT.
 PLEASE SEE SOME BUILDING TYPES WHICH ARE SHOWN AS BEING
 MLO?? HOW WILL THE RATINGS BE AFFECTED THEN?
 PLEASE SEE 110.9, AND 240.12 FOR COORDINATION REQUIRED
  
  
 11) NOTE: PLEASE SEE THE TOTAL SQ FT ON THE PERMIT
 APPLICATION SHOWS 1282 SQ FT, HOWEVER BASED ON PLANS
 THIS DOES NOT CORRELATE WITH THIS TYPE IV BUILDING.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By lmartine Date 2006-12-05 Time 13:51 Rev Time 0.00
Received By lmartine Date 2006-12-05 Time 13:51 Sent To  
Notes
2006-12-05 13:51:44SEE 06101116

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By rchokshi Date 2006-11-22 Time 16:42 Rev Time 0.00
Received By rchokshi Date 2006-11-22 Time 16:42 Sent To  
Notes
2006-11-22 16:42:48WE DO NOT HAVE THE CIVIL DWGS FOR THIS PERMIT PROJECT
 BUT WE REVIEWED,MADE FOLLOWING COMMENTS TO EXPEDITE
 THE PERMITTING PROCESS: PLEASE PROVIDE FOLLOWING INFO
 IN YOUR CIVIL DRAWINGS FOR THIS PERMIT SITE:
 1.DID YOU MAKE ANY CHANGES IN STORM WATER/DRAINAGE
 SYSTEM FROM PREVIOUS MASTER PERMIT? PLEASE TELL US WHAT
 CHANGES YOU MADE IN WRITING AND MUST BE APPROVED FROM
 SFWMD ALSO. AND A COPY OF SFWMD.
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON CIVIL
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION FOR THIS PERMIT PROJECT MUST MEET FL
 BLDG CODE, PLEASE SHOW ON THE DRAWINGS.,
 5. HOW YOU CONNECT TO THE ROOF DRAINS ? WHERE THE ROOF
 DRAINS GO?
 6. PLEASE SHOW ON DRAWINGS,POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE
 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 8.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 THIS BUILDING SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-10 Cont ID  
Sent By mawillia Date 2007-04-10 Time 17:52 Rev Time 0.00
Received By mawillia Date 2007-04-10 Time 17:48 Sent To  
Notes
2007-04-10 17:52:17*****APPROVED*****
  
  
 ADDITIONAL SETS OF PLANS WERE SUBMITTED FOR THIS MERRY
 PLACE PROJECT.SHEETS A404, E202, E304, AND FP304 WERE
 STAMPED, INITIALED, AND DATED 01/23/2007.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-23 Cont ID  
Sent By mawillia Date 2007-01-23 Time 16:56 Rev Time 0.00
Received By mawillia Date 2007-01-23 Time 16:56 Sent To  
Notes
2007-01-23 16:58:09*****APPROVED*****
  
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 12/01/2006
 HAVE BEEN ADDRESSED.SHEETS A404, E202, E304, AND
 FP304 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By mawillia Date 2006-12-01 Time 11:49 Rev Time 0.00
Received By mawillia Date 2006-12-01 Time 11:49 Sent To  
Notes
2006-12-01 12:27:40*****DENIED*****
  
  
  
 1.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING NORTH
 DIXIE HIGHWAY.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH. INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN
 3" IN HEIGHT.
  
 2.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 SPRINKLER SYSTEM.
  
 4. FIRE SPRINKLER SYSTEM SHALL BE MONITORED.
  
 5. SHOW DETAIL OF THE FIRE DEPARTMENT CONNECTION (FDC).
 THE FDC SHALL BE NO GREATER THAN 150 FEET TO THE
 NEAREST FIRE HYDRANT.
  
 6.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 7.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTING, AND FIRE EXTINGUISHERS (2A-10 BC RATED) FOR
 THE GROUND FLOOR PLAN.
  
 8.WILL THIS BUILDING HAVE A FIRE ALARM SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By kstevens Date 2006-12-28 Time 09:43 Rev Time 0.00
Received By kstevens Date 2006-12-28 Time 09:43 Sent To  
Notes
2006-12-28 09:44:30SEPARATE GAS PERMIT REQUIRED. - PLANS/REQUIREMENTS TO
 BE SUBMITTED WITH GAS APPLICATION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By kstevens Date 2006-11-17 Time 09:41 Rev Time 0.00
Received By kstevens Date 2006-11-17 Time 09:41 Sent To  
Notes
2006-12-28 09:43:19DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 15:34 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 15:34 Sent To M
Notes
2008-05-07 15:35:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 09:40 Sent To B
Notes
2008-04-10 09:41:22TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 15:28 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 15:28 Sent To B
Notes
2008-03-05 15:29:18TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 14:47 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 14:47 Sent To B
Notes
2007-11-26 14:47:42TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 08:15 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 08:15 Sent To  
Notes
2007-09-24 08:16:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 14:17 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 14:17 Sent To  
Notes
2007-09-21 13:54:199/21/07-TO "Z" BOX
2007-09-18 14:20:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 08:50 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 08:50 Sent To B
Notes
2007-08-23 13:52:16TO "COMM" BD#55
2007-08-03 08:51:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-06-28 Cont ID  
Sent By shill Date 2007-06-28 Time 15:17 Rev Time 0.00
Received By shill Date 2007-06-28 Time 15:17 Sent To B
Notes
2007-06-28 15:17:15TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:55 Sent To B
Notes
2007-06-04 11:55:43TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 09:04 Sent To P
Notes
2007-04-13 09:04:403RD SET OF PLANS ROUTED TO "KSTEVENS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:35 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:35 Sent To P
Notes
2007-03-30 17:35:51TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:54 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:54 Sent To  
Notes
2007-03-26 18:54:55WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 15:30 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 15:30 Sent To  
Notes
2006-12-18 15:31:02TO "COMM" BD#28/PLANS ON RACK/12 ROLL AND 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-06 Cont ID  
Sent By jgomez Date 2006-12-06 Time 17:48 Rev Time 0.00
Received By jgomez Date 2006-10-31 Time 09:59 Sent To  
Notes
2006-11-03 11:42:2811/3/06--SUBMITTAL ROUTED TO "COMM" BD#57 W/ ORIGINAL
 APPL. PACKAGE
2006-10-31 10:00:43(PLANS ROUTED TO INCOMING TODAY) TO "COMM" BD#57/PLANS
 ON RACK 14 ROLLS/1 BOX--EXPEDITED PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-08 Cont ID  
Sent By tgordon Date 2008-05-08 Time 10:26 Rev Time 0.45
Received By tgordon Date 2008-05-08 Time 10:26 Sent To  
Notes
2008-05-08 10:26:53MECH. REVISION TO PAGE M202.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By tgordon Date 2007-09-21 Time 13:30 Rev Time 0.40
Received By tgordon Date 2007-09-21 Time 13:30 Sent To I
Notes
2007-09-21 13:38:23REVISION TO MECH. PLAN PAGE M304.
 *** PROVISO ***
 1) IF EXTERIOR WALL IS RATED THEN COMPLY WITH 2004
 FBC/M 401.6.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By tgordon Date 2006-12-20 Time 11:05 Rev Time 0.20
Received By tgordon Date 2006-12-20 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By tgordon Date 2006-11-20 Time 09:30 Rev Time 1.00
Received By tgordon Date 2006-11-20 Time 09:30 Sent To  
Notes
2006-11-20 09:57:54*** DENIED ***
 1) AHU 5 AND CU 5 ARE NOT SHOWING IN THE A/C SCHEDULE
 ON PAGE M401, PLEASE CORRECT.
  
 2) NEED TO SHOW HOW MANY CFM'S OF OUTDOOR AIR IS GOING
 TO AHU 5 ON FIRST FLOOR, PLEASE SEE 2004 FBC/M 401.2.
  
 3) THE RETURN AIR GRILL IN THE MULTI PURPOSE ROOM IS
 LOCATED IN A CLOSET AND IF THE DOOR IS CLOSED IT WILL
 STOP THE RETURN AIR, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-11 Cont ID  
Sent By kstevens Date 2007-04-11 Time 12:50 Rev Time 0.00
Received By kstevens Date 2007-04-11 Time 12:50 Sent To  
Notes
2007-04-11 12:57:34PASSED/PROVISO
  
 REVISION REQUIRED FOR SHEET P402. REVISION SHALL BE
 SUBMITTED WITHIN 60 OF THE DATE THEPERMIT IS USSUED.
 THE RISER DIAGRAM INDICATES THE LAVS AS "S" TRAPS. 3"
 IS REQUIRED TO THE W/M'S. THE TRAP FOR THE W/M IS NOT
 VENTED AS DRAWN.BOTH W/M'S SHALL BE SHOWN AS BEING
 LOCATED ACROSS THE ROOM FROM THE BATHROOM FIXTURES.
  
 KENNETH H. STEVENS
 PLUMBING PLAN REVIEW
 WEST PALM BEACH
 PH. (561) 805-6721
 FAX (561) 805-6731
 E-MAIL - [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-28 Cont ID  
Sent By kstevens Date 2006-12-28 Time 15:06 Rev Time 0.00
Received By kstevens Date 2006-12-28 Time 15:06 Sent To  
Notes
2006-12-28 15:22:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. OK
 4. OK
 5. DELETED
 6. OK
 7.OK NOT REQUIRED FOR THIS BUILDING.
 8.OK NOT REQUIRED FOR THIS BUILDING.
 9.OK NOT REQUIRED FOR THIS BUILDING.
 10. OK NOT REQUIRED THIS BUILDING.
 11. OK
 12. OK
 13. OK (UNIT LOCATION ONLY)
 14. OK
 15. OK
 16. OK. NOT REQUIRED FOR THIS BUILDING.
 17. OK
 18. OK
 19. OK. NOT REQUIRED FOR THIS BUILDING.
  
 20. SHTS A802 DETAILS 04 & 09 INDICATE
 THE CENTERLINE OF THE W/C 18" OFF THE
 WALL, AND THE CENTERLINE OF THE LAV TO
 BE MIN. 15" OFF THE WALL (TO BE CENTERED
 ON THE 30" WIDTH OF THE CLEAR FLOOR
 SPACE). SECTIONS 11-4.16.2, 11-4.19.3
 AND FIG. 28.
 ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR
 CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING.
 PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE
 DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR
 SPACE REQUIRED IN SECTION 11-4.16..2.
 ****RESPONSE NOTED, BUT SHT A802 HAS NOT BEEN
 SUBMITTED.
  
 21. OK
 22. OK. NOT REQUIRED FOR THIS BUILDING.
 23 OK
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC
 RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT
 RISER DIAGRAMS FOUND.
 ****RESPONSE NOTED, BUT THE THE WASH MACHINES SHALL NOT
 DRAIN THRU THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. THE WASH MACHINE SHALL DRAIN DOWNSTREAM OF
 THE THE BATHROOM FIXTURES. SECTION 909.1.-THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT THE LAV'S
 AND WASH MACHINES. IN THE RISER THE LAV ARMS AND THE
 WASH MACHINE BRANCH LINES ARE INDICATED AS ABOVE THE
 SLAB, WHERE AS THE PIPING FOR THE LAVS AND WASH
 MACHINES ARE INDICATED AS BELOW THE SLAB. PLEASE
 CORRELATE. SECTION 106.1.1.-THE WASH MACHINE SHALL
 DRAIN INTO A BRANCH LINE A MINIMUM OF 3". SECTION
 406.3.
  
 28. SUBMIT A WATER RISER DIAGRAM FOR
 EACH BUILDING. SHOW ALL PIPE SIZES,
 VALVES. RISER CONNECTIONS, AND INDICATE
 BLDG. SHUTOFF VALVE AS WELL AS INDICATE
 THE RPZV BACKFLOW REQUIRED FOR EACH
 BUILDING. SECTIONS 106.1.5.1.3 AND
 SECTION 608.13.2.
 ****RESPONSE NOTED. NO RISER FROM METER TO UNITS
 SUBMITTED. ONLY UNIT RISER SHOWN.
 ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED
 ON ALL WATER DOWN-FEED LINES TO THE DRINKING FOUNTAIN,
 W/C & LAV, AND THE SINK. SECTION 606.1(4).
  
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK - SEPARATE GAS PERMIT REQUIRED.-GAS
 PLANS/REQUIREMENTS SHALL BE SUBMITTED WITH GAS
 APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-18 Cont ID  
Sent By kstevens Date 2006-11-18 Time 07:35 Rev Time 0.00
Received By kstevens Date 2006-11-17 Time 17:13 Sent To  
Notes
2006-11-18 10:48:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY
 WITH SECTION 11-4.24.7 FAUCETS. PLEASE
 INDICATE COMPLIANCE ON DETAIL.
 ****RESPONSE NOTED. NOTE REFERENCED INDICATES
 COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE
 FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE
 SINKS. (LEVER- OPERATED, PUSH-TYPE ETC).
  
 4. SHT A104 GENERAL NOTES II(5)(C) GRAB
 BAR HEIGHTS SHALL BE 33" MIN. TO 36"
 MAX. PAGE 6.5 FHA DESIGN MANUAL.
 ****RESPONSE NOTED. NOTE NOT CORRECTED.
  
 5. DELETED
  
 6. SHT A104 GENERAL NOTES: II(4)(G) SINK
 SHALL HAVE FORWARD APPROACH PER SECTION
 11-4.24.5. SHOW ON DETAIL.
 ****RESPONSE NOTED. COMMENT NOT ADDRESSED
  
 7.OK NOT REQUIRED FOR THIS BUILDING.
 8.OK NOT REQUIRED FOR THIS BUILDING.
 9.OK NOT REQUIRED FOR THIS BUILDING.
 10. OK NOT REQUIRED THIS BUILDING.
  
 11. SHT A205 ADCP ACCESSIBLE UNIT PLAN NOTES LEGEND
 SHALL CHANGE REFERENCE STANDARD TO FHA-98 AMENDMENTS.
 ****RESPONSE NOTED. THIS COMMENT WAS BECAUSE OF THE
 FHA-1996 NOTE AT THE BOTTOM OF THE LEGEND. RESPONSE IS
 CORRECT IN THE FACT THAT 7%, (10 REQUIRED, 9 SHOWN), OF
 THE UNITS ARE TO BE FULLY ACCESSIBLE. ACCESSIBLE DOES
 NOT MEAN ANY PORTION SHALL BE ADAPTABLE AS INDICATED IN
 SOME NOTES. ALL FIXTURES REQUIRED TO BE ACCESSIBLE
 SHALL BE ACCESSIBLE WHEN THE UNIT IS BUILT.
  
 12. SHT A205 HDCP ACCESS. UNIT PLAN
 NOTES LEGEND:NOTE #2 SINK SHALL BE
 ACCESSIBLE, NOT ADAPTABLE AS STATED.
 IF UNIT IS ACCESSIBLE, THEN IT SHALL BE
 BUILT ACCESSIBLE. SHOW CLEAR FLOOR
 SPACE.
 ****RESPONSE NOTED. BUT WE ARE TALKING ABOUT THE
 ACCESSIBLE UNITS, NOT THE ADAPTABLE UNITS IN THIS
 COMMENT. (SEE COMMENT 11 ABOVE).
  
 13. OK (UNIT LOCATION ONLY)
  
 14. SHT A304 SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS.
 SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 & 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE FOR EACH AREA BEING
 DRAINED, ALONG WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO EACH AREA, AND ALL AREAS OF
 ROOFS THAT DRAIN ONTO THE AREAS FROM
 ABOVE.
 ****RESPONSE NOTED. PER SECTION 1503.4.3, OVERFLOW
 SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS. AS SHOWN THE
 OVERFLOW SCUPPER IS APPROXIMATELY 34FT FROM THE
 DOWNSPOUT. IF THE PRIMARY ROOF DRAIN FAILS THERE WOULD
 BE A MINIMUM OF 8 TO 8-1/2" OF WATER AT THE LOW POINT
 OF THE ROOF BEFORE THE WATER WILL REACH THE FLOW LINE
 OF THE SCUPPER. THIS WILL RESULT IN OVER 27,000 GALLONS
 OF WATER ON THE ROOF OR ABOUT 23,000 LBS, (20LB/FT)
 LOAD ON THE ROOF. THE SIZING OF THE SCUPPER CAN NOT BE
 DETERMINED WITH OUT REFERENCE TO THE DEFLECTION OF THE
 ROOF. SECTIONS 1101.7, 1107.3 AND TABLE1106.7.
  
 15. SHT A304 LOWER FLOOR INDICATES AREA
 DESIGNATED AS "B" OCCUPANCY, AND AREA
 DESIGNATED AS "A-3"OCCUPANCY. SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 AND
 403.1. A DRINKING FOUNTAIN IS REQUIRED
 IN EACH OCCUPANCY, AND A SERVICE SINK IS
 REQUIRED IN THE "A-3" OCCUPANCY. THERE
 ARE NO W/C'S, OR LAVS SHOWN IN ONE SPACE
 FOR LOWER FLOOR PLAN. PLEASE CLARIFY.
 ****RESPONSE NOTED. FACILITIES HAVE NOT BEEN PROVIDED
 AS INDICATED. RESPONSE INDICATES THAT A DOOR WILL BE
 PROVIDED BETWEEN THE STORAGE AREA AND THE COUNSELING
 AREA. I DO NOT BELIEVE THAT A STORAGE AREA CAN BE USED
 AS AN ACCESS BETWEEN OCCUPANCIES. PLEASE INDICATE ON
 THE FLOOR PLAN THE USE FOR EACH AREA OF THE FIRST
 FLOOR. SECTION 106.1.1.
  
 16. OK. NOT REQUIRED FOR THIS BUILDING.
  
 17. SHT A700.1 FINISH SCHEDULE FOR
 LEASING OFFICE AND COMMUNITY RESOURCE.
 PLEASE INDICATE HOW PTD. GYP. BD. MEETS
 THE REQUIREMENT OF SECTION 1210.2.
 ****RESPONSE NOTED. FINISH SCHEDULE NOT CHANGED.
  
 18. SHT A801 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTION, AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF THE DINKING FOUNTAIN IS NOT
 A "HI/LOW" TYPE.
 ****RESPONSE NOTED. NO ACTION TAKEN.
  
 19. OK. NOT REQUIRED FOR THIS BUILDING.
  
 20. SHTS A802 DETAILS 04 & 09 INDICATE
 THE CENTERLINE OF THE W/C 18" OFF THE
 WALL, AND THE CENTERLINE OF THE LAV TO
 BE MIN. 15" OFF THE WALL (TO BE CENTERED
 ON THE 30" WIDTH OF THE CLEAR FLOOR
 SPACE). SECTIONS 11-4.16.2, 11-4.19.3
 AND FIG. 28.
 ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR
 CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING.
 PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE
 DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR
 SPACE REQUIRED IN SECTION 11-4.16..2.
  
 21. SHT A810 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A). A SERVICE SINK
 IS REQUIRED FOR THE STORAGE OCCUPANCY.
 TABLE 403.1.
 ****RESPONSE NOTED. NOT ACTION TAKEN.
  
 22. OK. NOT REQUIRED FOR THIS BUILDING.
  
 23 SHTS P301 THRU P310 PLAN KEY NOTES #7
 PRESSURE RELIEF VALVE IS INDICATED AS
 RUNNING UNDER THE SLAB. THE RELIEF VALVE
 DISCHARGE LINE SHALL NOT HAVE ANY
 TRAPPED SECTIONS PER SECTION 504.6.1.
 ****RESPONSE NOTED. SHT P301 NOT SUBMITTED THIS
 BUILDING. NO CLARIFICATION SHOWN.
  
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC
 RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT
 RISER DIAGRAMS FOUND.
  
 28. SUBMIT A WATER RISER DIAGRAM FOR
 EACH BUILDING. SHOW ALL PIPE SIZES,
 VALVES. RISER CONNECTIONS, AND INDICATE
 BLDG. SHUTOFF VALVE AS WELL AS INDICATE
 THE RPZV BACKFLOW REQUIRED FOR EACH
 BUILDING. SECTIONS 106.1.5.1.3 AND
 SECTION 608.13.2.
 ****RESPONSE NOTED. NO RISER FROM METER TO UNITS
 SUBMITTED. ONLY UNIT RISER SHOWN.
  
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS
 SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1
 UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF
 UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES
 BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN
 BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E"
 INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN
 BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F"
 INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1
 PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE
 INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION
 106.1.1.
  
 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES
 LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS
 ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT
 THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE.
 IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE
 UNIT CAN BE ADAPTABLE.
 NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996.
 PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES
 "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY
 ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT".
 THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE
 OR FULLY ACCESSIBLE.
  
 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7%
 TO BE FULLY "ADAPTABLE" PLEASE CLARIFY.
  
 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-07 Cont ID  
Sent By choops Date 2007-08-07 Time 09:20 Rev Time 0.00
Received By choops Date 2007-08-07 Time 09:20 Sent To  
Notes
2007-08-07 09:21:02APPROVED PER AJV

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-16 Cont ID  
Sent By ajones Date 2006-11-16 Time 10:13 Rev Time 0.00
Received By ajones Date 2006-11-16 Time 10:13 Sent To  
Notes
2006-11-16 10:15:451. LANDSCAPING PLANS SHALL BE APPROVED BEFORE A CO IS
 ISSUED.
 2.THE PARKING ON LILAC COURT SHALL BE REDESIGN THE
 MATCH THE APPROVED MINOR AMENDMENT BEFORE A CO IS
 ISSUED.
 3.SHEET A400 IS NOT THE DESIGN FOR THIS BUILDING.
 4.ALL DOORS SHALL BE COVERED WITH A CANOPY OR OTHER
 MEANS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved