| 2006-11-18 10:48:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: FIRST PLAN REVIEW FOR APPLICATION |
| | |
| | **********FROM PREVIOUS REVIEW********** |
| | |
| | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF |
| | APPLICATION SUBMITTAL PER RESPONSE. |
| | |
| | 2. OK |
| | |
| | 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY |
| | WITH SECTION 11-4.24.7 FAUCETS. PLEASE |
| | INDICATE COMPLIANCE ON DETAIL. |
| | ****RESPONSE NOTED. NOTE REFERENCED INDICATES |
| | COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE |
| | FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE |
| | SINKS. (LEVER- OPERATED, PUSH-TYPE ETC). |
| | |
| | 4. SHT A104 GENERAL NOTES II(5)(C) GRAB |
| | BAR HEIGHTS SHALL BE 33" MIN. TO 36" |
| | MAX. PAGE 6.5 FHA DESIGN MANUAL. |
| | ****RESPONSE NOTED. NOTE NOT CORRECTED. |
| | |
| | 5. DELETED |
| | |
| | 6. SHT A104 GENERAL NOTES: II(4)(G) SINK |
| | SHALL HAVE FORWARD APPROACH PER SECTION |
| | 11-4.24.5. SHOW ON DETAIL. |
| | ****RESPONSE NOTED. COMMENT NOT ADDRESSED |
| | |
| | 7.OK NOT REQUIRED FOR THIS BUILDING. |
| | 8.OK NOT REQUIRED FOR THIS BUILDING. |
| | 9.OK NOT REQUIRED FOR THIS BUILDING. |
| | 10. OK NOT REQUIRED THIS BUILDING. |
| | |
| | 11. SHT A205 ADCP ACCESSIBLE UNIT PLAN NOTES LEGEND |
| | SHALL CHANGE REFERENCE STANDARD TO FHA-98 AMENDMENTS. |
| | ****RESPONSE NOTED. THIS COMMENT WAS BECAUSE OF THE |
| | FHA-1996 NOTE AT THE BOTTOM OF THE LEGEND. RESPONSE IS |
| | CORRECT IN THE FACT THAT 7%, (10 REQUIRED, 9 SHOWN), OF |
| | THE UNITS ARE TO BE FULLY ACCESSIBLE. ACCESSIBLE DOES |
| | NOT MEAN ANY PORTION SHALL BE ADAPTABLE AS INDICATED IN |
| | SOME NOTES. ALL FIXTURES REQUIRED TO BE ACCESSIBLE |
| | SHALL BE ACCESSIBLE WHEN THE UNIT IS BUILT. |
| | |
| | 12. SHT A205 HDCP ACCESS. UNIT PLAN |
| | NOTES LEGEND:NOTE #2 SINK SHALL BE |
| | ACCESSIBLE, NOT ADAPTABLE AS STATED. |
| | IF UNIT IS ACCESSIBLE, THEN IT SHALL BE |
| | BUILT ACCESSIBLE. SHOW CLEAR FLOOR |
| | SPACE. |
| | ****RESPONSE NOTED. BUT WE ARE TALKING ABOUT THE |
| | ACCESSIBLE UNITS, NOT THE ADAPTABLE UNITS IN THIS |
| | COMMENT. (SEE COMMENT 11 ABOVE). |
| | |
| | 13. OK (UNIT LOCATION ONLY) |
| | |
| | 14. SHT A304 SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS. |
| | SUBMIT CALCULATION FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | & 1107 AND ALL SUBSECTIONS. SHOW THE |
| | SQUARE FOOTAGE FOR EACH AREA BEING |
| | DRAINED, ALONG WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS |
| | ADDED TO EACH AREA, AND ALL AREAS OF |
| | ROOFS THAT DRAIN ONTO THE AREAS FROM |
| | ABOVE. |
| | ****RESPONSE NOTED. PER SECTION 1503.4.3, OVERFLOW |
| | SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO |
| | REQUIRED VERTICAL LEADERS OR DOWNSPOUTS. AS SHOWN THE |
| | OVERFLOW SCUPPER IS APPROXIMATELY 34FT FROM THE |
| | DOWNSPOUT. IF THE PRIMARY ROOF DRAIN FAILS THERE WOULD |
| | BE A MINIMUM OF 8 TO 8-1/2" OF WATER AT THE LOW POINT |
| | OF THE ROOF BEFORE THE WATER WILL REACH THE FLOW LINE |
| | OF THE SCUPPER. THIS WILL RESULT IN OVER 27,000 GALLONS |
| | OF WATER ON THE ROOF OR ABOUT 23,000 LBS, (20LB/FT) |
| | LOAD ON THE ROOF. THE SIZING OF THE SCUPPER CAN NOT BE |
| | DETERMINED WITH OUT REFERENCE TO THE DEFLECTION OF THE |
| | ROOF. SECTIONS 1101.7, 1107.3 AND TABLE1106.7. |
| | |
| | 15. SHT A304 LOWER FLOOR INDICATES AREA |
| | DESIGNATED AS "B" OCCUPANCY, AND AREA |
| | DESIGNATED AS "A-3"OCCUPANCY. SUBMIT CALCULATIONS FOR |
| | MINIMUM FACILITIES FOR |
| | EACH OCCUPANCY PER TABLES 1004.1.2 AND |
| | 403.1. A DRINKING FOUNTAIN IS REQUIRED |
| | IN EACH OCCUPANCY, AND A SERVICE SINK IS |
| | REQUIRED IN THE "A-3" OCCUPANCY. THERE |
| | ARE NO W/C'S, OR LAVS SHOWN IN ONE SPACE |
| | FOR LOWER FLOOR PLAN. PLEASE CLARIFY. |
| | ****RESPONSE NOTED. FACILITIES HAVE NOT BEEN PROVIDED |
| | AS INDICATED. RESPONSE INDICATES THAT A DOOR WILL BE |
| | PROVIDED BETWEEN THE STORAGE AREA AND THE COUNSELING |
| | AREA. I DO NOT BELIEVE THAT A STORAGE AREA CAN BE USED |
| | AS AN ACCESS BETWEEN OCCUPANCIES. PLEASE INDICATE ON |
| | THE FLOOR PLAN THE USE FOR EACH AREA OF THE FIRST |
| | FLOOR. SECTION 106.1.1. |
| | |
| | 16. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 17. SHT A700.1 FINISH SCHEDULE FOR |
| | LEASING OFFICE AND COMMUNITY RESOURCE. |
| | PLEASE INDICATE HOW PTD. GYP. BD. MEETS |
| | THE REQUIREMENT OF SECTION 1210.2. |
| | ****RESPONSE NOTED. FINISH SCHEDULE NOT CHANGED. |
| | |
| | 18. SHT A801 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTION, AS WELL AS |
| | SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING IF THE DINKING FOUNTAIN IS NOT |
| | A "HI/LOW" TYPE. |
| | ****RESPONSE NOTED. NO ACTION TAKEN. |
| | |
| | 19. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 20. SHTS A802 DETAILS 04 & 09 INDICATE |
| | THE CENTERLINE OF THE W/C 18" OFF THE |
| | WALL, AND THE CENTERLINE OF THE LAV TO |
| | BE MIN. 15" OFF THE WALL (TO BE CENTERED |
| | ON THE 30" WIDTH OF THE CLEAR FLOOR |
| | SPACE). SECTIONS 11-4.16.2, 11-4.19.3 |
| | AND FIG. 28. |
| | ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR |
| | CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING. |
| | PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE |
| | DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR |
| | SPACE REQUIRED IN SECTION 11-4.16..2. |
| | |
| | 21. SHT A810 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTIONS AS WELL AS |
| | SECTION 11-4.1.3(10)(A). A SERVICE SINK |
| | IS REQUIRED FOR THE STORAGE OCCUPANCY. |
| | TABLE 403.1. |
| | ****RESPONSE NOTED. NOT ACTION TAKEN. |
| | |
| | 22. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 23 SHTS P301 THRU P310 PLAN KEY NOTES #7 |
| | PRESSURE RELIEF VALVE IS INDICATED AS |
| | RUNNING UNDER THE SLAB. THE RELIEF VALVE |
| | DISCHARGE LINE SHALL NOT HAVE ANY |
| | TRAPPED SECTIONS PER SECTION 504.6.1. |
| | ****RESPONSE NOTED. SHT P301 NOT SUBMITTED THIS |
| | BUILDING. NO CLARIFICATION SHOWN. |
| | |
| | 24. OK |
| | 25. OK. NOT REQUIRED FOR THIS BUILDING |
| | 26. OK |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC |
| | RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT |
| | RISER DIAGRAMS FOUND. |
| | |
| | 28. SUBMIT A WATER RISER DIAGRAM FOR |
| | EACH BUILDING. SHOW ALL PIPE SIZES, |
| | VALVES. RISER CONNECTIONS, AND INDICATE |
| | BLDG. SHUTOFF VALVE AS WELL AS INDICATE |
| | THE RPZV BACKFLOW REQUIRED FOR EACH |
| | BUILDING. SECTIONS 106.1.5.1.3 AND |
| | SECTION 608.13.2. |
| | ****RESPONSE NOTED. NO RISER FROM METER TO UNITS |
| | SUBMITTED. ONLY UNIT RISER SHOWN. |
| | |
| | 29. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS |
| | SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1 |
| | UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF |
| | UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES |
| | BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN |
| | BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E" |
| | INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN |
| | BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F" |
| | INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1 |
| | PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE |
| | INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION |
| | 106.1.1. |
| | |
| | 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES |
| | LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS |
| | ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT |
| | THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE. |
| | IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE |
| | UNIT CAN BE ADAPTABLE. |
| | NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996. |
| | PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES |
| | "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY |
| | ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT". |
| | THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE |
| | OR FULLY ACCESSIBLE. |
| | |
| | 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7% |
| | TO BE FULLY "ADAPTABLE" PLEASE CLARIFY. |
| | |
| | 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS |
| | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST |
| | REMOTEAPPLIANCE FOR EACH UNIT. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |