Plan Review Details - Permit 06101014
Plan Review Stops For Permit 06101014
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-12-19 Cont ID  
Sent By mjacobs Date 2007-12-19 Time 07:24 Rev Time 0.00
Received By mjacobs Date 2007-12-19 Time 06:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-11 Cont ID  
Sent By mjacobs Date 2007-09-11 Time 10:50 Rev Time 0.00
Received By MJACOBS Date 2007-09-14 Time 13:37 Sent To  
Notes
2007-09-11 10:50:53REVISIONS DOORS AND WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-20 Cont ID  
Sent By mjacobs Date 2007-08-20 Time 11:49 Rev Time 0.00
Received By mjacobs Date 2007-08-18 Time 13:57 Sent To  
Notes
2007-08-20 11:49:22BUILDING PLAN REVIEW
 PERMIT: 06101014
 ADD: 505 16TH STREET
 CONT: J.JAY ROTHE
 TEL: (561) 389-4137
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION:P
  
 NOTE:
 IF ANY STRUCTURAL WORK WAS DONE AT THIS PROJECT
 INDICATE THE AREAS WITH CLOUDS AND GIVE THE DETAIL
 DRAWINGS WITH DIMENSIONS ACCORDINGLY. THE NEW SPRINKLER
 SYSTEM WILL INCREASE THE VALUE OF THE PROJECT;
 THEREFORE ADDITIONAL FEES WILL BE ADDED ACCORDINGLY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 13:47 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 13:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-14 Cont ID  
Sent By mjacobs Date 2007-03-14 Time 11:53 Rev Time 0.00
Received By mjacobs Date 2007-03-14 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-15 Cont ID  
Sent By mjacobs Date 2007-02-15 Time 12:17 Rev Time 0.00
Received By mjacobs Date 2007-02-15 Time 07:53 Sent To  
Notes
2007-02-15 14:20:23BUILDING PLAN REVIEW
 PERMIT:06101014
 ADD: 50516TH STREET
 CONT:J JAY ROTHE INC.
 TEL: (561)389-4137
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE THE INFORMATION FROM FYRE-TEC. FOR THE FIRE
 RATED WINDOWS INSTALLATION.
  
 3)THE NEW STRUCTURE FOR E.W.H.NEEDS PRODUCT
 APPROVALS FOR THE ROOFING SHINGLES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By mjacobs Date 2006-11-27 Time 10:49 Rev Time 0.00
Received By mjacobs Date 2006-11-27 Time 06:17 Sent To  
Notes
2006-11-27 10:49:22 
 BUILDING PLAN REVIEW
 PERMIT:06101014
 ADD:505 :16THST.
 CONT: CARLO MERCURIO INC.
 TEL: (561)630-7591
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PROCUCT APPROVALS
 FOR THE FIRE RATED WINDOWS PER NOTE #23 ON SHEET A-1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 15:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-12 Cont ID  
Sent By dpalmer Date 2007-08-12 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2007-08-12 Time 10:43 Sent To  
Notes
2007-08-12 10:56:34 
  
 ** REVISION DENIED **
  
  
 1) NOTE: PLEASE SEE HOLD WHICH WAS PLACED ON PROJECT BY
 THE INSPECTION SERVICES MANAGER FOR LEVEL OF ALTERATION
 AND PERMITS WHICH HAVE NOT BEEN APPLIED FOR.
  
 2) NOTE: PLEASE SEE THERE WERE ITEMS REDLINED ON
 PREVIOUS PLANS WHICH HAVE NOT BEEN ADDED TO PLANS.
 A) PLEASE SEE MISSING CODE REFERENCES:
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 FBC 2004.
  
 B) PLEASE SEE MISSING CIRCUITS TO BE INDICATED ON PANEL
 SCHEDULE FOR ARC FAULT PROTECTION.210.12,408.4
  
 C) PLEASE SEE MISSING RECEPTACLES IN KITCHEN WITH
 GREATER THAN 2FT OF WALL SPACE. THIS WAS ADDED TO TWO
 UNITS AS THIS WAS A NOTE IN THE REVIEW DATED
 02/15/07.
 210.52
  
 3) NOTE: PLEASE CLEARLY INDICATE THE REVISIONS ON PLANS
 WITH CLOUDS/TRIANGLES ETC.
 PLEASE REVISE PLANS AND TITLE BLOCKS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE AREA ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-07 Cont ID  
Sent By dpalmer Date 2007-03-07 Time 07:26 Rev Time 0.00
Received By dpalmer Date 2007-03-07 Time 07:03 Sent To  
Notes
2007-03-07 07:28:14REDLINED
  
 CODES
 2002 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 THE CIRCUITS TO BE LISTED ON PANEL SCHEDULE WAS NOT
 DONE, REDLINED 2002 210.12 ON PANEL SCHEDULES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-15 Cont ID  
Sent By dpalmer Date 2007-02-15 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 16:12 Sent To  
Notes
2007-02-15 07:24:49 
  
  
 **** UNSAT ****
  
 1) NOTE:PLEASE SEE THE CIRCUITING FOR THE SMOKE
 ALARMS IS SHOWING ALL THE DEVICES ON SEPARATE CIRCUITS.
 PLEASE SEE SOME APT UNITS ARE SHOWING AS MANY AS FOUR
 CIRCUITS FOR THE SMOKE ALARMS. PLEASE KNOW THAT THESE
 DEVICES ARE REQUIRED TO BE WIRED *INLINE* THEREFORE
 PLACING 220V ON THESE DEVICES AS THEY ARE ON SEVERAL
 CIRCUITS FOR ONE UNIT.
 PLEASE ADJUST ALL CIRCUITING FOR THESE AS THEY SHOULD
 BE ON ONE CIRCUIT.
 NFPA-72 11.5.1.1, 11.8.3
  
 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN FOR
 THE UNIT PANELS ARE NOT RESIDENTIAL LOAD CALCULATIONS.
 PLEASE SEE THE SECTIONS ALSO REFLECTED ON THE PANELS
 ARE FOR OTHER THAN DWELLING UNITS.
 PLEASE SEE NEC 220 PART II OR PART III.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES MENTIONED THE
 MISSING WASHER/LAUNDRY CIRCUIT. PLEASE SEE THIS IS NOW
 SHOWN ON PANEL SCHEDULE; HOWEVER THE MINIMUM LOAD ON
 THIS CIRCUIT IS REQUIRED TO BE 1500VA PER 220.16B.
 PLEASE ALSO SEE THAT THE LOAD CALCULATIONS DO NOT
 INDICATE OR SHOW THE WASHER/LAUNDRY LOAD BEING
 FIGURED.
 210.11C2
  
 4) NOTE: PLEASE SEE A COUPLE OF MISSING RECEPTACLES PER
 210.52 FOR WALL SPACE TWO FEET OR MORE. PLEASE SEE
 KITCHEN WALLS IN UNITS *C* AND *D*. THERE ARE REDLINED
 ON ONE SET OF THE PLANS SUBMITTED.
 PLEASE ALSO SEE UNIT *B* WHICH DOE SHOW A RECEPTACLE ON
 THIS TWO FT OF WALL; HOWEVER IT IS BEING SHOWN AS A
 DEDICATED CIRCUIT FOR THE WALL AC UNIT. PLEASE KNOW AN
 ADDITIONAL RECEPT WILL BE REQUIRED.
 PLEASE ALSO SEE THAT THESE RECEPTACLES WHICH ARE
 MISSING ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. (210.52B1)
  
 5) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM REQUIRED
 CLEARANCES FOR THE CU DISCONNECTS.
 PLEASE SEE THAT THESE ARE BEING SHOWN WITH LESS THAN
 THE 30 INCHES MINIMUM SIDE TO SIDE REQUIRED. PLEASE SEE
 SOME WITH LESS THAN 1FT BASED ON THE 3/8 INCHES SCALE
 AS NOTED ON PLANS.
 PLEASE ADJUST LAYOUT OF ALL EQUIPMENT AS SHOWN DOWN THE
 SIDE FOR THESE UNITS.
  
 6) NOTE: PLEASE LIST AND INDICATE THE ARC FAULT
 PROTECTED BREAKERS ON PANEL SCHEDULE. A NOTE WAS
 LOCATED ON THE APARTMENT LAYOUT PLANS; HOWEVER PLEASE
 LIST THE BREAKERS ON PANEL SCHEDULE.
 210.12
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE THE RISER DIAGRAM INDICATES
 GROUNDING ELECTRODE PER NEC WHOEVER PLEASE INDICATE THE
 MINIMUM REQUIRED.PLEASE SHOW A MINIMUM OF TOW GROUND
 RODS AND COLD WATER PIPE (IF METAL).
 250.50, 250.56
 CODE MAY NOT BE QUOTED IN LIEU OF SPECIFIC OR TECHNICAL
 DETAIL.
  
 8) NOTE: PLEASE SHOW THE LOCATION AND THE SERVICE ON
 PLANS. (METERS AND RISER)VERIFICATION FOR 110.26 ETC
 NEEDS TO BE VERIFIED. ALSO OVER HEAD CLEARANCES FROM
 2ND FLOOR WINDOWS SHOULD BE TAKEN INTO CONSIDERATION
 BASED ON SERVICE RISER LOCATION. (3FT MINIMUM
 REQUIRED).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By dpalmer Date 2006-11-01 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 07:21 Sent To  
Notes
2006-11-01 09:40:43*******UNSAT *********
  
  
 ** PLEASE SEE THIS IS A NEW REVIEW UNDER A NEW PERMIT,
 HOWEVER THIS WAS REVIEWEDUNDER 05111120. PLEASE SEE
 SOME COMMENTS FROM THE FIRST TWO REVIEWS STILL ARE
 NOTED.
  
 1) NOTE:PLEASE BE SURE THE RELEVANT CODES ARE
 REQUIRED TO BE STATED ON PLANS AS FOLLOWS:
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
 PLEASE ALSO SEE COMMENT WITH RESPECT THE FHA.
  
 2) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE "SD", HOWEVER SEE OTHER NOTE FOR THESE.
 PLEASE ALSO SEE NOTE ABOUT WASHER ETC.
 FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE SEE NFPA DEFINITIONS FOR SMOKE
 DETECTORS AND SMOKE ALARMS. PLEASE KNOW IF THESE ARE
 INDEED DEVICES WHICH DETECT AND CONTAIN THE AUDIBLE
 ALARM, THESE SHOULD BE NOTED AS SA. PLEASE KNOW A SD
 DEVICE IS A DETECTION DEVICE ONLY AND WOULD SIGNAL AND
 ALARM PANEL OR HORNS OF SOME TYPE.
 PLEASE KNOW THIS WAS RECENTLY GONE OVER WITH NFPA AND
 THE CODE COUNSEL.
  
 4) NOTE: PLEASE INDICATE ALL CONDUCTORS FROM METER BANK
 TO THE MAIN DISCONNECTS.
 310.16, 240.4
  
 5) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR"
 IS BEING SHOWN IN THE RISER BEFORE THE FIRST MEANS OF
 DISCONNECT?
 PLEASE SEE 250.6, AND 250.24B.
  
 6) NOTE: PLEASE SEE RISER SEEMS TO INDICATE BUILDING
 STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM,
 HOWEVER PLEASE VERIFY THIS AS THIS IS AN EXISTING
 BUILDING AND IF SHOWN, THEN THIS WOULD BE REQUIRED.
 250.50.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 210.52 FOR SOME MISSING RECEPTS
 FOR 2FT OR MORE OF WALL , WITHIN 6FT OF DOOR, AND 12 FT
 OR MORE OF WALL SPACE.
  
 8) NOTE: PLEASE SEE FHAR 24 CFR 100.205 FOR FIRST FLOOR
 DEVICES TO BE SHOWN AND NOTED.
  
 9) NOTE: PLEASE SEE UNIT "A" WHICH SHOWS A KITCHEN GFI
 RECEPT ON THE KITCHEN LIGHTING CIRCUIT WHICH IS NOT
 PERMITTED. PLEASE SEE 210.52B1.
  
 10) NOTE: PLEASE SEE NO CIRCUIT OR RECEPT DEVICE SHOWN
 FOR UNIT "A" WASHER.
 210.11C2,
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE 210.52B1, WHICH REQUIRES RECEPTS
 LOCATED ON DINING/KITCHEN/ BREAKFAST AREAS AND THE LIKE
 SHALL BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE SOME AREAS WHICH FIT INTO THIS
 DESCRIPTION OR DESIGNATION HOWEVER THEY ARE ON GENERAL
 LIGHTING CIRCUITS WHICH IS NOT PERMITTED.
  
 12) NOTE: PLEASE PROVIDE THE MIN LIGHTING LEVELS FOR
 STAIRS UNDER NORMAL POWER FOR MIN EGRESS REQUIREMENTS
 PER NFPA-101 7.8.1.3, AND MIN LEVELS UNDER
 EMERGENCY.7.9.2.2
 A BATTERY BACK UP FIXTURE OF SOME SORT WILL BE REQUIRED
 FOR EMERGENCY EGRESS TO THE PUBLIC RIGHT OF WAY.
 PLEASE ALSO CLARIFY HOW THIS LIGHTING FROM THE HOUSE
 PANEL IS BEING CONTROLLED??
  
 13) NOTE: PLEASE SUBMIT SPEC FOR OUTSIDE WATER HEATER
 UNITS FROM THE MANUFACTURE INDICATING LISTINGS FROM
 NRTL.
 110.3, 90.7
 FBC 106.1.2
  
 14) NOTE: PLEASE CORRELATE MECHANICAL PLANS WITH
 ELECTRICAL FOR SIZING OF THE HEAT IN THE AHU'S. PLEASE
 SEE THESE ARE BEING SHOWN AS 10KW, HOWEVER PLEASE SEE
 MECH PLANS INDICATE 5KW?
 FBC 106.1.2, NEC 424.3B, 310.16
 ** PLEASE SEE A NAX OCP DEVICE IS ALSO USUALLY SET BY
 THE MANUFACTURE HOWEVER TYPICALLY 150%.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-31 17:56:43REMOVED FROM INCOMING, IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 14:23 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 14:04 Sent To  
Notes
2007-08-20 14:23:24*****APPROVED*****
 REVISED PLAN SHEETS A-2 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 17:03 Rev Time 0.00
Received By mawillia Date 2007-03-15 Time 16:57 Sent To  
Notes
2007-03-15 17:03:17*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 SATISFIED.PLAN SHEETS A-2 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 11:53 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 11:53 Sent To  
Notes
2007-02-23 12:10:38*****UNSAT*****
  
  
 THE FOLLOWING COMMENTS WHICH WERE TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW OF 11/21/2006 STILL NEED TO
 BE RECTIFIED.
  
  
 1.THE SITE PLAN ON SHEET A-2 DEPICTS QUINCE STREET AS
 THE NORTH-SOUTH ROADWAY.THIS ROADWAY IS SPRUCE
 AVENUE.
  
 2.ON SHEET A-1, GENERAL NOTE #27, REFERENCE SHOULD BE
 MADE TO NFPA 241 NOTNFPA 421.
  
 3.ON SHEET A-1, GENERAL NOTE #32, DELETE THE WORD
 "WILL" AND INSERT THE WORDS "SHALL NOT" BETWEEN
 PROCEDURES --- HINDER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By mawillia Date 2006-11-21 Time 11:16 Rev Time 0.00
Received By mawillia Date 2006-11-21 Time 11:15 Sent To  
Notes
2006-11-21 12:08:36*****DENIED*****
  
  
  
 01.PLEASE PROVIDE A LAYOUT OF THE STRUCTURE ON A SITE
 PLAN AS TO HOW IT RELATES TO THE NEAREST STREETS,
 HYDRANTS, RAILROAD, ETC.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE
 SAID PROPERTY OR VICINITY THEREOF.
  
 04.FIRE EXTINGUISHERS TO BE RATED 2A-10 BC.
  
 05.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE
 TIED INTO A FIRE ALARM SYSTEM.THE DEVICES USED AT THE
 SITE ARE SMOKE ALARMS (SA) AND SHOULD BE REFLECTED AS
 SUCH IN THE SUBMITTED PLANS.
  
 06.FOR SPECIFIC LOCATION REQUIREMENTS OF SMOKE
 ALARMS/SMOKE DETECTORS, NFPA 72 - 2002 EDITION -
 11.8.3.5 SHALL BE REFERENCED.
  
 07.SMOKE ALARMS INSTALLED WITHIN 20-FT HORIZONTAL
 PATH OF A COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM SILENCING MEANS OR BE OF THE PHOTOELECTRIC TYPE.
  
 08.SMOKE ALARMS SHALL RECEIVE ITS OPERATING POWER
 FROM THE BUILDING'S ELECTRICAL SERVICE.
  
 09.INSTALL A SMOKE ALARM IN THE LIVING AREA OF THE
 UNITS.
  
 10. INTERIOR FINISH FOR WALLS AND CEILING SHALL BE
 CLASS "A" OR CLASS "C".PLEASE SPECIFY.
  
 11. VERITY THAT THE NUMERICAL ADDRESS (ON THE BUILDING)
 IS NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH PLAINLY
 VISIBLE FROM 16TH STREET.EACH UNIT SHALL HAVE A
 NUMBER OR ALPHABET NO LESS THAN 3" IN HEIGHT ABOVE OR
 IN THE VICINITY OF THE FRONT DOOR (NOT ON THE DOOR).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 14:37 Sent To  
Notes
2007-12-12 14:40:32TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 16:03 Sent To  
Notes
2007-09-08 15:13:44TO BOB SPACE #2
2007-08-27 16:03:30WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:43 Sent To  
Notes
2007-08-10 08:43:47TO BOB BOARD #11

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 10:41 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 10:41 Sent To  
Notes
2007-08-02 10:42:23WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 10:25 Sent To M
Notes
2007-07-11 10:27:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 15:30 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 15:30 Sent To  
Notes
2007-03-06 15:30:45TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 10:10 Sent To  
Notes
2007-02-14 10:10:36TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-11-27 Time   Rev Time 0.00
Received By adarroug Date 2006-10-28 Time 16:11 Sent To  
Notes
2006-11-02 09:42:38TO "BOB"#18
2006-10-28 16:13:55WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-13 Cont ID  
Sent By tgordon Date 2007-08-13 Time 11:11 Rev Time 0.25
Received By tgordon Date 2007-08-13 Time 11:11 Sent To  
Notes
2007-08-13 11:12:58REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-12 Cont ID  
Sent By tgordon Date 2007-07-12 Time 09:49 Rev Time 0.25
Received By tgordon Date 2007-07-12 Time 09:49 Sent To  
Notes
2007-07-12 09:53:58MECHANICAL REVISION
 *** DENIED ***
 1) RETURN AIR DUCT (FLEX) TO AHU-D NEEDS TO BE SIZED.
  
 2) A/C EQUIPMENT SCHEDULE IS MISSING FROM REVISED PLAN,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-02 Cont ID  
Sent By tgordon Date 2006-11-02 Time 12:03 Rev Time 0.30
Received By tgordon Date 2006-11-02 Time 12:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-21 Cont ID  
Sent By mperson Date 2007-08-21 Time 15:15 Rev Time 0.00
Received By mperson Date 2007-08-21 Time 15:15 Sent To  
Notes
2007-08-21 15:23:55REVISION:
 NOTE: THERE ARE NO CHANGES ONPLUMBING SHEET P-1 FROM
 THE ORIGINAL, JUST AN UPDATED SIGNATURE, SEAL AND DATE
 BY ENGINEER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 11:35 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-22 Cont ID  
Sent By jleech Date 2007-02-22 Time 10:00 Rev Time 0.00
Received By jleech Date 2007-02-22 Time 10:00 Sent To  
Notes
2007-02-22 10:06:17DENIED;
 STUDIO SHOWER MUST BE A MINIMUM OF 900 SQ. INCH.
 MINIMUM OF 30" IN DIMENTION MESSURED FROM INSIDE FINISH
 INTERIOR DIMENTION. FBC-2004 SECTION 417.4.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By jleech Date 2006-11-17 Time 12:23 Rev Time 0.00
Received By jleech Date 2006-11-17 Time 12:23 Sent To  
Notes
2006-11-17 12:37:53DENIED;
 1. PLEASE ADD NOTE TO PLUMBING PAGE. "A REDUCED
 PRESSURE PRINCIPAL BACKFLOW PREVENTOR TO BE INSTALLED
 ON THE BUILDING SIDE OF THE
 WATER METER"
 2. PLEASE SHOW BATHROOM MEASUREMENTS IN BATHROOMS WHERE
 THE LAVATORYS WERE MOVED. A DISTANCE OF 30" IS REQUIRED
 FROM THE CENTERLINE
 OF TOILET TO THE CENTERLINE OF THE LAVATORY, AND
 15" TO THE EDGE OF THE TUB TO THE CENTERLINE OF THE
 TOILET. FBC-2004 PLUMBING SECTION
 405.3.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-14 Cont ID  
Sent By kdfreema Date 2007-09-14 Time 13:36 Rev Time 0.00
Received By kdfreema Date 2007-09-14 Time 13:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-17 Cont ID  
Sent By kdfreema Date 2007-08-17 Time 11:03 Rev Time 0.00
Received By kdfreema Date 2007-08-17 Time 11:03 Sent To  
Notes
2007-08-17 11:05:03PLEASE PROVIDE A SURVEY WITH SETBACK INFORMATION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.