| 2006-11-14 17:30:10 | BUILDING REVIEW CHECKLIST: | | | | | | 1-ACCORDING TO INSTALLATION SCHEDULE SUBMITTED THE | | | EDGE DISTANCE IS 3".NEED TO REDUCE ANCHOR SPACING | | | ACCORDING TO TABLE ON SHEET 11 OF 14 OF ENGINEERED | | | ACCORDION SHUTTER DRAWINGS.REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|