Plan Review Details - Permit 06100956
| Plan Review Stops For Permit 06100956 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-02 |
Time |
13:19 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-11-02 |
Time |
13:19 |
Sent To |
PC |
|
| Notes |
| 2007-11-02 13:20:59 | NEW C-3 REVISION TO PATIO AREAS, OK EQUIVALANT | | | FACILITATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
F |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-26 |
Time |
16:25 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-10-26 |
Time |
16:25 |
Sent To |
PC |
|
| Notes |
| 2007-10-26 16:41:08 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BEACH LAKES BLVD | | | CONT: COLUMBIA CONSTRUCTION | | | TEL: (321)246-4825 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION# 18 SHEET C3REVIEW | | | ACTION: DENIED | | | | | | 1)THE ORIGINAL PERMITTED PLANS INDICATED AN ACCESSIBLE | | | ROUTE FROM THE PUBLIC WAY TO THE FRONT OF THE BUILDING. | | | REVISION# 18 NOW INDICATES APPROXIMATELY 2'-0" | | | DIFFERENCE IN GRADE AND EXTERIOR STAIRS. | | | THE REVISION FAILS TO SHOW "EQUIVALENT FACILITATION" | | | 11-2.2 WHICH WILL REQUIRE A DISABLED PERSON TO HAVE TO | | | USE THE DISABLED ACCES POINT BEHIND THE BUILDING. IF | | | THE GRADE DIFFERENCE IN FRONT WAS MADE UP THROUGH AN | | | ACCESSIBLE RAMP WTIH THE CORRECT SLOPE HANDRAILS AND | | | LANDINGS BOTH DISABLED AND THOUGHS NOT DISSABLED WOULD | | | BE ABLE TO USE THE FRONT ACCESSBLE ENTRY ROUTE. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-22 |
Time |
10:10 |
Rev Time |
0.88 |
| Received By |
jwitmer |
Date |
2007-10-22 |
Time |
10:10 |
Sent To |
PC |
|
| Notes |
| 2007-10-22 10:11:13 | REVISION# 12 OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-15 |
Time |
11:11 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-10-15 |
Time |
11:11 |
Sent To |
PC |
|
| Notes |
| 2007-10-15 11:26:22 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BCH LAKES BLVD | | | CONT: COLUMBIA CONSTRUCTION | | | TEL: (321)246-4825 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION NO.12 8/16/07REVIEW | | | ACTION: DENIED | | | | | | SHEETS A.300, A.305 & A.315DENIED. THIS BUILDING IS | | | CLASSIFIED AS A TYPE II-B, UNPROTECTED, UNSPRINKLED. | | | THE SHEETS LISTED ABOVE NOW INDICATE THE USE OF 5/8" | | | CDX PLYWOOD FOR SHEATHING ON BEARING WALLS WHEN | | | REVIEWING SECTION 603.1 AND TABLE 603 FOR A TYPE II-B | | | STRUCTURE THERE CAN BE NO PLYWOOD SHEATHING FOR A II-B | | | BUILDING. | | | HOWEVER THIS IS THE DESIGN THAT YOU ELECTED TO USE, THE | | | MINIMUM BUILDING TYPE BY CODE IS A TYPE V-B FOR A A-2 | | | OCCUPANCY GROUPWITH AN ALLOWABLE 6000 SQ FT/ SINGLE | | | STORY. | | | | | | IF THIS BUILDING WAS TO BE DECLARED A TYPE V-B BUILDING | | | AND TO USE PLYWOOD SUBSHEATHING THEREWOULD STILL BE | | | CONCERNS IN AREAS WHERE THE SHEATHING WOULD BE WITHIN | | | SIX INCHES OF GRADE. PLEASE REVIEW 2304.11.2.5 FOR WOOD | | | SUBSHEATHING REQUIREMENTS. | | | | | | THE ORIGINAL PLANS WERE ALSO PULLED TO SEE IF THERE HAD | | | BEEN REFRENCE MADE TO THE USE OF WOOD SUBSHEATHING OR | | | POSSIBLE DENSE-GLASS SINCE THERE IS TO BE AN EFIS | | | FINISH SYSTEM. I HADN'T FOUND ANY PRODUCT APPROVALS FOR | | | THE EFIS WALL SYSTEMS. | | | A BUILDING PROVISO # 1 WASISSUED WITH THE ISSUANCE | | | OF THE PLANS: | | | 1) PLEASE PROVIDE PRODUCT APPROVAL REPORT FOR STO CORP. | | | THE FLORIDA COVER SHEET INDICATE THE CORRESPONDING | | | REPORT TO BE A ES REPORT NOT THE SUBMITTED MIAMI-DADE | | | NOA. | | | PLEASE INDICATE WHICH SUB-SYSTEM WILL BE USED IN | | | CONJUCTION WITH THIS PROJECT. WILL BE REQUIRED WITHIN | | | 30 DAYS OF ISSUANCE. | | | TO DATE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED AND | | | THIS ISSUE STILL REMAINS AS "OPEN". | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-15 |
Time |
11:09 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-10-15 |
Time |
11:09 |
Sent To |
PC |
|
| Notes |
| 2007-10-15 11:11:19 | REVIEWED SHEETSFOR REVISION# 12 8/16/07 | | | A.000 | | | A.021 | | | A.101 | | | A.110 | | | A.120 | | | A.125 | | | A.130 | | | A.201 | | | A.215 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-25 |
Time |
13:53 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-09-25 |
Time |
13:53 |
Sent To |
PC |
|
| Notes |
| 2007-09-25 13:54:27 | YKK UPDATES TO PRODUCT APPROVALS FOE CURTAINWALL, | | | STOREFRONT AND DOORS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-14 |
Time |
08:49 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-09-14 |
Time |
08:49 |
Sent To |
PC |
|
| Notes |
| 2007-09-14 08:59:55 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BEACH LAKES BLVD | | | CONT: COLOMBIA CONSTRUCTION | | | TEL: (615)497-7032 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND SHOP DRAWING REVIEW: | | | ACTION: DENIED | | | | | | 1)THE SHOP DRAWINGS IDENTIFIED THREE YKK PRODUCTS TO | | | BE USED IN THIS INSTALLATION.T HE CONTRACTOR FAILED TO | | | SUBMIT ONE OF THE PRODUCTS LISTED ON THE SHOP DRAWINGS | | | YHS-50 A STOREFRONT SYSTEM. THE CONTRACTOR FAILED TO | | | PROVIDE THE FLORIDA COVER SHEETS FOR ALL PRODUCTS, 2 OF | | | THE 3 PRODUCTS REQUIRE A PE TO VERIFY THE REPORTS | | | ANCHOR CALCULATIONS AND STRUCTURAL ANALYSIS SINCE THEY | | | WERE DESIGNED AND TESTED BEFORE THE 2004 FBC WHEN | | | DESIGNERS TOOK A 1.33 INCREASE IN STEEL AND STEEL | | | FASTENERS. THE FLORIDA COVER SHEET INDICATES WHICH | | | PRODUCTS HAVE THE CALCULATIONS REVISED. PLEASE HAVE THE | | | PE DO AN ANALYSIS ON THE FASTENERS AND INDICATE SUCH IN | | | WRITING. PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL | | | NUMBER AND BACK UP REPORT, THIS BEING A MIAMI-DADE | | | NOA. | | | | | | 2) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. | | | | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-31 |
Time |
13:32 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-08-31 |
Time |
13:32 |
Sent To |
PC |
|
| Notes |
| 2007-08-31 13:33:03 | REVISION 11 & 12. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-29 |
Time |
11:24 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-08-29 |
Time |
11:24 |
Sent To |
PC |
|
| Notes |
| 2007-08-29 11:31:08 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BEACH LAKES BLVD | | | CONT: COLOMBIA CONSTRUCTION | | | TEL: (615)497-7032 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SHOP DRAWING REVIEW: | | | ACTION: DENIED | | | | | | 1)THE SHOP DRAWINGS FAIL TO INDICATE THE PRODUCT | | | MANUFACTURERAND THE MODEL NUMBER AND OR NAME ON THE | | | SUBMITTAL. | | | PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER AND | | | BACK UP REPORT, THIS BEING A MIAMI-DADE NOA. | | | | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-18 |
Time |
14:00 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-07-18 |
Time |
14:00 |
Sent To |
PC |
|
| Notes |
| 2007-07-18 14:01:45 | REVISION# 9 STOREFRONT CHANGE TO YKK CURTAIN WALL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-05-10 |
Time |
15:31 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2007-05-10 |
Time |
15:31 |
Sent To |
PC |
|
| Notes |
| 2007-05-10 15:38:23 | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT#06100956 | | | ADDRESS: 2380 PALM BEACH LAKES | | | CONT: | | | TELL # (561) | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF PLANS.106.1.1 | | | ADMINISTRATIVE CODE/ 06. | | | | | | BUILDING PROVISOS: | | | | | | 1) PLEASE PROVIDE PRODUCT APPROVAL REPORT FOR STO CORP. | | | THE FLORIDA COVER SHEET INDICATE THE CORRESPONDING | | | REPORT TO BE A ES REPORT NOT THE SUBMITTED MIAMI-DADE | | | NOA. | | | PLEASE INDICATE WHICH SUB-SYSTEM WILL BE USED IN | | | CONJUCTION WITH THIS PROJECT. WILL BE REQUIRED WITHIN | | | 30 DAYS OF ISSUANCE. | | | | | | 2 ) 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERMORMED IN A MANNER | | | SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS | | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | | SAID PROPERTY PURSUANT TO A CONSENT BY | | | THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE | | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | | BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | | SHALL NOT ADVERSELY IMPACT HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE | | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, | | | AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | | ITEMS, ON EXISTING PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | | AS A PERMIT CONDITION, PROVIDE A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | | CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 3) ) 109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-04-25 |
Time |
09:40 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-04-25 |
Time |
09:39 |
Sent To |
PC |
|
| Notes |
| 2007-04-25 09:41:15 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BCH LAKES BLVD | | | CONT:""PLAN REVIEW"" | | | TEL: (407)645-5008 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | | | | 2004 BUILDING PLAN REVIEW | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) 3RD REQUEST COMMENT# 11 FROM THE PREVIOUS REIEW, | | | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS: | | | MISSING REPORTS: | | | A) KAWNEER CURTAIN WALL SYSTEM PLANS INDICATE THE USE | | | OF SEERIES 1600 SYSTEM 2 MISSING REPORT# 04-0908.05 AND | | | THE TECHNICAL SHEETS | | | B) STO- EFIS, SUBSYSEMS ARE NOT MARKED AS TO WHICH | | | SYSTEM TO BE USED, NO REPORTS SUBMITTED, SEE | | | LIMITATIONS. | | | C) ROOFING ASSEMBLIES: JOHN MANVILLE, SINGLE PLY | | | SYSTEM, SUBSYSTEM IS NOT MARKED AS TO WHICH SYSTEM IS | | | TO BE USED. | | | | | | 4) THE PERMIT APPLICATION INDICATES THIS IS DEMOLITION | | | OF AN EXISTING BUILDING AND A NEW SMALLER RESTARAUNT. | | | PLEASE TAKE YOUR PLANS TO THE PALM BEACH COUNTY | | | BUILDING DEPARTMENT FOR IMPACT FEE ASSESSMENT, THERE | | | MAY BE A CREDIT DUE? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-02 |
Time |
09:47 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2007-03-02 |
Time |
09:47 |
Sent To |
PC |
|
| Notes |
| 2007-03-02 10:55:55 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BCH LAKES BLVD | | | CONT:""PLAN REVIEW"" | | | TEL: (407)645-5008 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | | | | 2004 BUILDING PLAN REVIEW | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3)2ND REQUEST, RESPONSE INDICATES SHEET S-1 G-3 STATES | | | ADJACENT | | | ONSITE FACILITIES, STRUCTURES & UTILITY LINES NO | | | MENTION OF | | | ADVERSELY IMPACT OF ADJACENT PROPERTY WHICH INCLUDES | | | BUT NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER | | | DEBRIS | | | AND THE STORAGE OF CONSTRUCTION MATERIAL. 109.3.10* | | | IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERMORMED IN A MANNER | | | SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS | | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | | SAID PROPERTY PURSUANT TO A CONSENT BY | | | THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE | | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | | BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | | SHALL NOT ADVERSELY IMPACT HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE | | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, | | | AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | | ITEMS, ON EXISTING PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | | AS A PERMIT CONDITION, PROVIDE A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | | CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 4) COMPLIED. | | | | | | 5) 2ND REQUEST,5C TYPE OF CONSTRUCTION AS DEFINED IN | | | CHAPTER 6 TABLE 601/ | | | RESPONSE IS TYPE II BUILDING, DOES THIS MEAN | | | THAT YOU WANT TO DESIGNTO THE MORE RESTRICTIVE TYPE | | | II REQUIREMENTS? | | | THIS BUILDING BEING A A-2 OCCUPANCY, MINIMUM BUILDING | | | TYPE OF V-B WITH 6,000 SQ FT / 1 STORY. | | | | | | 6) 2ND REQUEST, PLEASE SUBMIT REPORT PRODUCED BY | | | GEOSYNTEC CONSULANTS 5/01/06 | | | FBC 1802.2.1 QUESTIONABLE SOILS, | | | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN | | | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT | | | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING | | | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION | | | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE | | | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 7) COMPLIED WITH SUBMITTALS PROVIDED, MISSING | | | SUBMITTALS. | | | | | | 8) COMPLIED, NEW CONSTRUCTION. | | | | | | 9) COMPLIED. | | | | | | 10A) SHEET S-1 DESIGN CRITERIA,D-1 STATES ASCE 7-?? | | | DOES NOT PROVIDE THE EDITION? | | | | | | 10B) ROOF ZONE 3 THE TRTIBUTARY AREA OF THE FASTENER IS | | | LESS THAN 10 SQ FT THE NEGATIVE PRESSURES REQUIRED TO | | | HOLD THE SYSTEM DOWN IS -89.0. | | | | | | 11) 2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | MISSING REPORTS: | | | D) EXTERIOR METAL DOOR | | | F ) LOUVERS | | | G) TRUSS ANCHOR FOR THE METALC CHANNELS | | | I) ROOFING ASSEMBLIES FLAT ROOF AS WELL AS THE METAL | | | CANOPY | | | | | | 11B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | NEW COMMENT | | | 12)ENERGY CALCS PLEASE PROVIDE 2 ORIGINAL SIGNED AND | | | SEALED ENERGY REPORTS | | | PLEASE HAVE THE OWNER/ AGENT SIGN THE ENERGY | | | CALCULATIONS. | | | | | | SINCE THIS IS A DEMO AND NEW STURCTURE REVIEW BY P.B. | | | COUNTY IMPACT FEE OFFICE WILL BE REQUIRED. | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-11-22 |
Time |
14:16 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2006-11-22 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2006-11-22 15:16:45 | BUILDING PLAN REVIEW | | | PERMIT: 06100956 | | | ADD: 2380 PALM BCH LAKES BLVD | | | CONT:""PLAN REVIEW"" | | | TEL: (407)645-5008 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | | | | 2004 BUILDING PLAN REVIEW | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERMORMED IN A MANNER | | | SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS | | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | | SAID PROPERTY PURSUANT TO A CONSENT BY | | | THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE | | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | | BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | | SHALL NOT ADVERSELY IMPACT HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE | | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, | | | AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | | ITEMS, ON EXISTING PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | | AS A PERMIT CONDITION, PROVIDE A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | | CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 4) 109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 5 ) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | G) . FT. LIV SPACE/ FL | | | H) SQ. FT. FOOTPRINT | | | I) SQ. FT. UNDER ROOF (TOTAL) | | | J ) OCCUPANT LOAD | | | K ) FLOOD ZONE | | | | | | 6)FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 7)W P B ADMINISTRTIVE CODE 106.3.3* | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 8)SHEET A110 INDICATES THAT THIS IS AN EXISTING | | | RERAUNT | | | AND THERE IS ONLY MODIFICATIONS TO THE EXISTING | | | STRUCTURE, | | | THE PLAN REVIEW APPLICATION INDICATES THIS IS A | | | COMPLETE | | | DEMO AND TO CONSTRUCT A NEW CHIPOTLE RESTRAUNT. PLEASE | | | | | | CORRECT. DISCREPANCY!!! | | | | | | 9)SHEET S-1WIND DESIGN THE BUILDING CATEGORY IS | | | LABELED AS A I NOT A II. | | | BUILDING CATEGORY I IS FARM OUT BUILDINGS OR SMALL SHED | | | CONSTRUCTION. CORRECT. | | | | | | 10) PLEASE PROVIDE THE POSITIVE AND NEGATIVE PRESSURES | | | ON THE ELEVATIONS, INDICATE THE INTERIOR ZONE 4 AND END | | | ZONES, ZONE 5. | | | ALSO PROVIDE A ROOF TOP VIEW WITH ZONES 1,2 & 3 WITH | | | THE ASSOCIATED PRESSURES. | | | | | | 11)1609.1.4 PROTECTION OF OPENINGS. | | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IN THE LOWER 60 FEET (18.3 M) IN | | | BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED | | | OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | | IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN | | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | | THE PROVISIONS OF THE SMALL MISSILE | | | TEST. | | | 11A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS FIXED, STOREFRONT | | | B) OPERATABLE WINDOWS | | | C) GLAZED DOORS | | | D) EXTERIOR METAL CORE DOORS | | | E) MULLIONS | | | F) LOUVERS | | | G) TRUSS ANCHORS FOR METAL C CHANNELS | | | H) EFIS SYSTEMS & SOFFITS | | | I) ROOFING ASSEMBLIES | | | J) PRE-ENGINEERED A/C STANDS | | | | | | 11B)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 11C) ROOFING ASSEMBLIES NEED THE FOLOWING INFORMATION | | | PROVIDED WITH THE REPORT:) THIS ROOF IS MISSING OR | | | NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | | | ___ CONTRACTOR DID NOT PROVIDE THE MEAN | | | | | | ROOF HEIGHT. | | | | | | ___ CONTRACTOR DID NOT INDICATE THE ROOF | | | PITCH. | | | | | | ___ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED. | | | | | | ___ THE SYSTEM PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ___ . | | | | | | ___ THE SYSTEM PROVIDED STATES | | | LIMITATION# 7, SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THE | | | BUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNED | | | AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF | | | CONSULTANT MAY BE SUBMITTED. | | | | | | ___THE SYSTEM PROVIDED INDICATES | | | LIMITATION# 9, NO ENHANCED | | | FASTENING ALLOWED. | | | | | | 12)PROVIDE ENGINEERING FOR THE CANOPY TO BE LOCATED | | | ON | | | THE SOUTH SIDE OF THE BUILDING. PLANS, | | | SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 13)) FBC 13-103.0ENERGY CODE COMPLIANCE | | | SHALL BE DEMONSTRATED BY SUBMITTAL OF | | | APPROPRIATE CODE COMPLIANCE FORMS | | | FBC 13-103.1.1.1THE PROFESSIONALS RESPONSIBLE FOR | | | THE DESIGN OF THE | | | BUILDING SHELL AND THE ELECTRICAL, | | | LIGHTING, MECHANICAL AND PLUMBING | | | SYSTEMS SHALL EACH SIGN THE ENERGY CODE | | | COMPLIANCE FORM, TO CERTIFY COMPLIANCE. | | | | | | 14) PROVIDE DOCUMENTATION OF COMPLIANCE WITH 11-5.2 & | | | 11-5.5.5& 11-5.6. | | | | | | 15) PLANS ARE TO INDICATE COMPLIANCE WITH: 2603.9.2 | | | CLEARANCE BETWEEN EARTH AND FOAM PLASTICS APPLIED TO | | | THE | | | EXTERIOR WALL SHALL BE NOT LESS THAN 6 INCHES (152 | | | MM). | | | | | | | | | 16)SHEET S2 NEEDS TO INDICATE COMPLIANCE WITH: 1816.1 | | | TERMITE PROTECTION. | | | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED | | | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, | | | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR | | | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED | | | FOR USE AS A PREVENTATIVE TREATMENT TO NEW | | | CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE. | | | UPON COMPLETION OF THE APPLICATION OF THE TERMITE | | | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL | | | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED | | | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING | | | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE | | | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. | | | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS | | | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE | | | AND CONSUMER SERVICES.? | | | | | | 1816.1.1 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, THE INITIAL CHEMICAL SOIL TREATMENT INSIDE | | | THE FOUNDATION PERIMETER SHALL BE DONE AFTER ALL | | | EXCAVATION, BACKFILLING AND COMPACTION IS COMPLETE. | | | | | | 1816.1.2 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL | | | SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL | | | TREATMENT, INCLUDING SPACES BOXED OR FORMED. | | | | | | 1816.1.3 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, SPACE IN CONCRETE FLOORS BOXED OUT OR | | | FORMED FOR THE SUBSEQUENT INSTALLATION OF PLUMBING | | | TRAPS, DRAINS OR ANY OTHER PURPOSE SHALL BE CREATED BY | | | USING PLASTIC OR METAL PERMANENTLY PLACED FORMS OF | | | SUFFICIENT DEPTH TO ELIMINATE ANY PLANNED SOIL | | | DISTURBANCE AFTER INITIAL CHEMICAL SOIL TREATMENT. | | | | | | 1816.1.4 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED | | | WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT | | | AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE | | | VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY | | | WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE | | | AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS | | | POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID | | | PENETRATING OR DISTURBING TREATED SOIL. | | | | | | 1816.1.5 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, CONCRETE OVERPOUR OR MORTAR ACCUMULATED | | | ALONG THE EXTERIOR FOUNDATION PERIMETER SHALL BE | | | REMOVED PRIOR TO EXTERIOR CHEMICAL SOIL TREATMENT, TO | | | ENHANCE VERTICAL PENETRATION OF THE CHEMICALS. | | | | | | 1816.1.6 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, CHEMICAL SOIL TREATMENTS SHALL ALSO BE | | | APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1 | | | FOOT (305 MM) OF THE PRIMARY STRUCTURE SIDEWALLS. ALSO, | | | A VERTICAL CHEMICAL BARRIER SHALL BE APPLIED PROMPTLY | | | AFTER CONSTRUCTION IS COMPLETED, INCLUDING INITIAL | | | LANDSCAPING AND IRRIGATION/SPRINKLER INSTALLATION. ANY | | | SOIL DISTURBED AFTER THE CHEMICAL VERTICAL BARRIER IS | | | APPLIED SHALL BE PROMPTLY RETREATED. | | | | | | 17) BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | NOTE WITH THE DEMOLITION OF THE OLD BUILDING BE CERTAIN | | | TO GET THE CREDIT FROM THE DEMO-ED BUILDING!!!! | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-10-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-20 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-20 |
Time |
08:40 |
Sent To |
B |
|
| Notes |
| 2007-10-20 08:56:23 | | | | ** ELECTRICAL PLANS REDINED AS PANEL "C" IS TO MEET | | | 110.11,110.26, 240.24C,D. | | | | | | | | | | | | | | | | | | | | | | | | REVIEWED PER ROBERT BROWN.ABO | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-05 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-05 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2007-10-05 15:32:21 | | | | *** DENIED REVISION *** | | | | | | | | | 1) NOTE: PLANS ARE NOW SHOWING A NEW SUB PANEL BEING | | | LISTED ON PANEL *B* HOWEVER THIS NEW SUB PANEL DOES NOT | | | EXIST ON RISER. | | | PLEASE SHOW WHERE THIS NEW PANEL IS. | | | PLEASE SEE THE PLANS INDICATE A J-BOX FOR CONNECTION OF | | | THESE NEW FEEDERS/BRANCH CIRCUITS YET THE LOCATION OF | | | THIS PANEL CAN NOT BE CONFIRMED. | | | PLEASE SEE THE PANEL SCHEDULE *B* DOES NOT INDICATE ANY | | | NEUTRAL CONDUCTOR WITH THE OTHER CONDUCTORS AS LISTED. | | | CLARIFY WHERE THE PREVIOUS 120V CIRCUITS NOW OBTAIN A | | | NEUTRAL IF NONE IS INSTALLED. | | | DOES THIS PANEL CONTAIN OVER CURRENT PROTECTION | | | DEVICES? | | | DOES THIS PANEL MEET THE MINIMUM CLEARANCE REQUIREMENTS | | | PER 110.26, 240.24? | | | DOES THIS PANEL MEET THE LOCATION FOR ITS ENVIRONMENT? | | | 110.3 | | | PLEASE SUBMIT THE PANEL SCHEDULE FOR THIS NEW CHEF | | | TABLE PANEL. | | | PLEASE SHOW LOCATION AND MEETING 110.26 | | | PLEASE PROVIDE LISTING FOR EQUIPMENT TO REVIEW. THIS | | | WILL NEED TO SHOW ALL ITEMS BEING FED/EQUIPMENT | | | SCHEDULE. 90.7, 110.3 | | | | | | FBC 106.1.2 | | | | | | IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS | | | REVIEW | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-05-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-03 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-03 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2007-05-03 16:54:16 | PLANS REMOVED FROM INCOMING, ELEC OK, AND PLANS ROUTED | | | BACK TO INCOMING WAITING FOR COMM BOARD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-03-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-24 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-24 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2007-03-24 16:30:26 | PLANS WERE REVIEW WHILE IN ZONING, PLANS REMAIN IN | | | ZONING ON 3/24 | | 2007-03-24 16:27:07 | *** UNSAT 3RD REVIEW ** | | | * FIRST REVIEW UNDER PERMIT. | | | | | | | | | 1) NOTE: PLEASE CLARIFY SHEETS 2 AND 3 OF THE FLORIDA | | | ENERGY CALCULATIONS. PLEASE SEE THE FOLLOWING AS THEY | | | DO NOT CORRELATE WITH THE ELECTRICAL PLANS. | | | | | | A) PLEASE SEE THAT THERE IS NOT EXTERIOR LIGHTING | | | ENTERED AND PARKING EXTERNAL LIGHTING ON CALCULATIONS | | | YET THE PLANS CONTAIN BOTH. | | | B) PLEASE SEE THE BATH FIXTURES, WATTAGE AND CONTROLS | | | DO NOT CORRELATE. THE INPUT DATA ONLY CONTAINS ONE | | | FIXTURE OF EACH TYPE WHEN THERE ARE TWO FIXTURES OF | | | EACH TYPE ON PLANS.(ONE OF EACH TYPE OF FIXTURE IN EACH | | | BATH) | | | PLEASE ALSO SEE THE TYPE OF CONTROL ENTERED IS | | | *CENTRAL* WHICH IS NOT POSSIBLE WHEN THE PLANS DO NOT | | | HAVE A *CENTRAL CONTROL*. PLANS DO INDICATE *OCCUPANCY | | | SENSOR TYPE CONTROL*. | | | C) PLEASE SEE DINING TYPE E WHICH STATES *CENTRAL | | | CONTROL*, HOWEVER NO CENTRAL LIGHTING CONTROL SYSTEM IS | | | PROVIDED. THIS TYPE OF FIXTURE IS WIRED AHEAD OF ANY | | | CONTROLS OR SWITCHES PER 700.12E ANYWAY. PLEASE | | | ADJUST. | | | D) PLEASE SEE SIGNAGE IN KITCHEN AREA, SHOWS C-1 AS 17W | | | AND 16W ON CALCULATIONS. | | | E) PLEASE SEE KITCHEN EM TYPE FIXTURES WHICH INDICATE | | | *CENTRAL CONTROL* FOR THESE ALSO. SAME AS NOTED ON *C* | | | ABOVE. | | | | | | PLEASE COORDINATE. IF A LIGHTING SYSTEM IS BEING | | | INSTALLED PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT | | | ALL INFORMATION FOR SAID SYSTEM. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-04 |
Time |
19:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-04 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2007-02-04 19:55:52 | ******* UNSAT 2ND REVIEW ****** | | | | | | *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW | | | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW | | | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION | | | AND/OR CHANGES MADE TO PLANS. | | | | | | **** IMPORTANT**** | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. | | | | | | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY | | | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE | | | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE | | | #1** | | | | | | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A | | | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW | | | NOTE WILL BE REMOVED. | | | | | | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF | | | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. | | | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS | | | REVIEW NOTE #1** | | | | | | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** | | | NEW NOTES ** | | | | | | | | | | | | | | | | | | ** PLEASE KNOW THAT PLANS STILL HAVE NOT BEEN SUBMITTED | | | FOR PERMIT APPLICATION ANS SINCE THE LAST REVIEW THE | | | STATE OF FLORIDA HAS ADOPTED NEW CODES. PLANS HAVE BEEN | | | SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN | | | SUBMITTED FOR PERMIT. | | | ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT, THEY | | | ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS | | | THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH | | | CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT | | | MAY CHANGE. | | | | | | | | | 1) NOTE:NO/OK, PLEASE SEE MOST OF THE PREVIOUS NOTE | | | WAS ADDRESSED HOWEVER PLEASE SEE THE STATE OF FLORIDA | | | HAS ADOPTED NEW CODES AND THE FOLLOWING SHALL BE | | | STATED. | | | 2005 NFPA-70 NEC. | | | PLANS INDICATE A 2004 NEC WHICH IS NOT VALID. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | | PLEASE SEE THAT THE FOLLOWING CODES AT A MINIMUM SHALL | | | BE STATED ON PLANS. | | | 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72 | | | ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA | | | 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE | | | NFPA-70 WILL BE THE 2005.) | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE: OK/NO, PLEASE SEE THE SIGN CIRCUITS WERE ADDED | | | WHICH IS OK, HOWEVER PLEASE SEE THE LOAD ON THESE IS | | | SHOWN AT 1500VA AND 10AMPS? PLEASE SEE 1500VA @120VOLTS | | | IS 12.5. THIS COULD HAVE BEEN REDLINED, HOWEVER THE | | | PLANS ARE NOT IN FOR PERMIT AND ARE COMING BACK FOR | | | OTHER COMMENTS. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | | PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN VA TO BE | | | SHOWN FOR SIGN CIRCUIT. 1200 MIN. | | | | | | 5) NOTE: OK. | | | | | | 6) NOTE: OK, HOWEVER PLEASE SEE THE FOOTER IS BEING | | | SHOWN FOR AN ATTACHMENT, PLEASE VERIFY IF EXISTING OR | | | IS IT THE SPECIFICATION OF THE ENGINEER FOR THE | | | EXISTING FOOTER TO BE *CHIPPED* INTO TO OBTAIN THIS | | | CONNECTION IF NOT EXISTING? | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | | PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM DETAIL. | | | STATING CODE COMPLIANCE IN LIEU OF DETAIL IS NOT | | | PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS KNOWN | | | TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING AND | | | THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A | | | MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS | | | REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS | | | LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50, | | | 250.56 250.104 ETC. | | | | | | 7) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS | | | INFORMATION WAS SUBMITTED IN PACKAGE HOWEVER THIS COULD | | | NOT BE LOCATED. | | | PLEASE SEE TWO SEPARATE ELECTRICAL SITE PLANS WERE | | | SUBMITTED SHOWING TWO SEPARATE PHOTO-METRICS ETC. | | | PLEASE SEE TWO SEPARATE DESIGN PROFESSIONALS ALSO. | | | PLEASE SEE THAT THE PLANS SHALL STATE THE MINIMUM 2004 | | | FBC WIND LOAD OF 140MPH (3 SECOND GUST) EVEN IF THE | | | CALCULATIONS ARE SEPARATE. PLEASE KNOW THAT IF THE | | | POLES ARE NOT ORDERED AND OBTAINED AT THE TIME OF | | | PERMIT APPLICATION THE CALCULATIONS CAN BE A *PROVISO* | | | AS LONG AS THE PLANS INDICATE THE CORRECT INFORMATION. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | | PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW LT POLES. | | | PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT AREA) OF | | | LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS WHICH WILL | | | BE REQUIRED TO BE SIGNED, DATED AND SEALED BY A FLORIDA | | | PE. PLEASE ALSO BE SURE THE TITLE BLOCK FOR THE DESIGN | | | PROFESSIONAL IS ON PLANS. | | | | | | 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL | | | SCHEDULES. 310.16,240.4, | | | FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH. | | | 106.1.2 | | | PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION | | | AT THIS TIME. | | | | | | | | | ** NEW NOTES ** | | | | | | 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE | | | REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGN | | | PROFESSIONAL. PLEASE SEE THE CALCULATIONS SUBMITTED ARE | | | PHOTO-COPIES OF SIGNED AND SEALED ONES. | | | PLEASE SEE FS 471.025, FAC 61G15-23.002 AND FBC | | | 13-103.1.1.1 | | | | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT THE ELECTRICAL PLANS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-04 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-03 |
Time |
20:56 |
Sent To |
|
|
| Notes |
| 2006-11-04 16:59:23 | *** UNSAT *** | | | | | | | | | ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR | | | "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN SUBMITTED FOR | | | PERMIT. | | | ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT , THEY | | | ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS | | | THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH | | | CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT | | | MAY CHANGE. | | | PLEASE KNOW, THE NFPA-70 WILL BE CHANGING AND THE 2005 | | | MAY BE ADOPTED BY THE STATE IN THE NEXT COUPLE OF | | | MONTHS. | | | | | | | | | | | | 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A | | | MINIMUM SHALL BE STATED ON PLANS. | | | 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72 | | | ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA | | | 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE | | | NFPA-70 WILL BE THE 2005.) | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF | | | RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002. | | | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER | | | OF ENGINEER AND MISSING THE CERTIFICATE OF | | | AUTHORIZATION NUMBER FOR FIRM. | | | PLEASE SEE FLORIDA STATUTES 471.023. | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). | | | PLEASE ALSO SEE FRONT COVER SHEET. | | | | | | 3) NOTE: PLEASE SEE 210.62 FOR SPACING OF WINDOW | | | RECEPTS. PLEASE ALSO SEE 220.12A FOR LOAD WHICH IS | | | REQUIRED TO BE SHOWN IN THE BREAK DOWN OF THE LOAD | | | CALCULATIONS SUBMITTED. | | | PLEASE SEE PLANS, PER SCALE APPEAR TO HAVE A COUPLE | | | MISSING. | | | | | | 4) NOTE: PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN | | | VA TO BE SHOWN FOR SIGN CIRCUIT. 1200 MIN. | | | | | | 5) NOTE: PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING | | | CONDUCTOR" FROM THE METER TO THE MAIN DISCONNECT. | | | PLEASE 250.6, AND 250.24B AS THIS EQUP GRND IS ONLY | | | INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 6) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM | | | DETAIL. STATING CODE COMPLIANCE IN LIEU OF DETAIL IS | | | NOT PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS | | | KNOWN TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING | | | AND THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A | | | MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS | | | REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS | | | LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50, | | | 250.56 250.104 ETC. | | | | | | 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW | | | LT POLES. PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT | | | AREA) OF LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS | | | WHICH WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED | | | BY A FLORIDA PE. PLEASE ALSO BE SURE THE TITLE BLOCK | | | FOR THE DESIGN PROFESSIONAL IS ON PLANS. | | | | | | 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL | | | SCHEDULES. 310.16,240.4, | | | FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH. | | | 106.1.2 | | | PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION | | | AT THIS TIME. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT THE ELECTRICAL PLANS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | 2006-11-04 16:14:09 | REVIEW IN PROGRESS | | 2006-11-03 20:56:23 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-10-26 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-10-26 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-05-02 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-05-02 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-03-30 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-03-30 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2007-03-30 11:04:50 | PLEASE EXPLAIN THE FOLLOWINGS: | | | | | | 1. HOW DID YOU CALCULATE WATER QUALITY VOLUME? PLEASE | | | SHOW WHAT CRITERIA DID YOU YUO USE EITHER 1" OVER | | | ENTIRE SITE OR2.5"CRITERIA?? PLEASE SHOW THE | | | DETAILED CALCULATIONS OVER PERVIOUS/IMPERVIOUS AREAS. | | | | | | 2. ARE YOU USING EXFILTRATION TRENCH? IF YOU DO, PLEASE | | | SHOW HOW DID YOU CALCULATE LENGTH OF EXFILTRATION | | | TRENCH,ETC?OR DRY DETENTION POND VOLUME, ETC? | | | | | | 3. PLEASE INCLUDE ALL THESE CAL. IN YOUR REPORT WHEN | | | YOU SUBMIT NEXT TIME. | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-02-09 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-02-09 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2007-02-09 16:12:36 | PLEASE PROVIDE FOLLOWING INFO: | | | | | | 1. YOU NEED TO GET A C.D. FROM 1000 45TH STREET | | | ENG(494-1040) FOR ALL STANDARD NOTES OF CITY OF WPB | | | WITH WPB LOGO AND COPY/PASTE ON YOUR DRAWINGS. ALSO | | | PLEASE WRITE A NOTE ON YOUR GENERAL NOTES SECTION THAT | | | ALL CONSTRUCTION WORK WILL BE PERFORMED PER CITY OF | | | WPB'S LATEST STANDARDS. | | | 2. PLEASE WRITE A NOTE ON THE DRAWING THAT DUMPSTER | | | LOCATION MUST BE ACCESSIBLE FOR TRUCK PICKUP. | | | 3.FLOOR ELEVATION MUST INCLUDE CONSIDERATION OF 100 | | | YEAR FLOOD ELEVATION DATA, PLEASE PROVIDE FLOOR | | | ELEVATION ACCORDINGLY.PLEASE PROVIDE 100 YEAR FLOOD | | | INFO. | | | 4.PLEASE PROVIDE POLLUTION PREVENTION SILT FENCE | | | DETAILS, LIKE CLOTHES USED, POST HEIGHT, HEIGHT OF THE | | | FENCE ETC. | | | 5. UTILITIES DEPT AT 45TH STREET HAS TO APPROVE YOUR | | | PLAN BEFORE WE APPROVE, PLEASE SEND A APPROVAL COPY. | | | 6. ACCORDING TO YOUR INFO, ALL STORM WATER FROM YOUR | | | SITE, GOES INTO YOUR POND AND STAYS IN YOUR SITE, IS | | | THIS TRUE? PLEASE EXPLAIN | | | PLEASE RESUBMIT ALL STORM WATER CAL ETC WHEN YOU | | | RESUBMIT NEXT TIME. | | | | | | PLEASE EXPLAIN ALL OF THESE ITEM IN YOUR RESPOND TO | | | EXPEDITE THE PERMITTING PROCESS. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-11-17 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-11-17 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2006-11-17 16:25:27 | PLEASE PROVIDE FOLLOWING INFO: | | | 1. NEED TO PREPARE DRAINAGE/STORM WATERPLANS.LIKE | | | SHEET C-1, C-2, ETC, JUST A SUGESTION | | | 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | | MUST MEET PER ADA,,ETC., | | | 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | | ON THE DRAWINGS. | | | 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH | | | REPORT | | | 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA | | | YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE | | | OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN, | | | LAKES, ETC,IMPERVIOUS AREA CAL., | | | 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS | | | PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS | | | CAL. | | | 8. HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN | | | YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER | | | PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO | | | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM | | | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL | | | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ? | | | 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT | | | ETC., PLANS SHOWING SILT FENCE AROUND THE SITE | | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE | | | 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-23 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-23 |
Time |
15:33 |
Sent To |
P |
|
| Notes |
| 2007-08-23 16:19:47 | *****APPROVED***** | | | | | | | | | APPROVED THE ELIMINATION OF SHEET FP100 WHICH | | | REFERENCES THE BUILDING HAVING A FIRE ALARM AND FIRE | | | SPRINKLER SYSTEM.AS PER NFPA 101- 2003 EDITION, THESE | | | SYSTEMS ARE NOT REQUIRED SINCE THE OCCUPANT LOAD IS | | | LESS THAN 300. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-10 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-10 |
Time |
17:19 |
Sent To |
|
|
| Notes |
| 2007-05-10 17:22:14 | *****APPROVED***** | | | | | | | | | PLAN SHEET LS100,A200, FP100, AND E100 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-16 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-16 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2007-04-16 15:37:19 | *****PROVISO***** | | | | | | | | | THECOMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS | | | APPEAR TO HAVE BEEN ADDRESSED;THE APPROPIATE PLAN(S) | | | WILL BE STAMPED WHEN OTHER PLAN REVIEW HAVE BEEN | | | SATISFIED. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-01 |
Time |
19:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-01 |
Time |
19:10 |
Sent To |
|
|
| Notes |
| 2007-03-01 19:35:03 | *****DENIED***** | | | | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | | | | 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION | | | CODE, THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED. | | | LIST ON SHEET A000,FIRE CODE: 2004 FLORIDA FIRE | | | PREVENTION CODE;LIFE SAFETY: 2003 NFPA 101 | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | PLEASE SHOW ON THE PLANS | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEROF.PLEASE SHOW ON THE PLANS | | | | | | 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. | | | PLEASE SHOW ON THE PLANS | | | | | | 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE | | | ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS | | | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND 1" IN WIDTH.DISPLAYED NUMERICAL | | | ADDRESS SHALL BE ON THE STRUCTURE OF THE BUILDING, NOT | | | THE DOOR OF THE BUILDING. | | | | | | 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS | | | AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS. PLEASE | | | SHOW ON THE PLANS | | | | | | 8.INCLUDE A LAYOUT OF THE EXISTING AND/OR NEW FIRE | | | ALARM SYSTEM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH | | | COMMENTWAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-21 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-21 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2006-12-21 13:49:25 | *****DENIED***** | | | | | | | | | | | | 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION | | | CODE, THE 2003 EDITION OF NFPA 101 SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEROF. | | | | | | 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | | | 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE | | | ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS | | | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND 1" IN WIDTH. | | | | | | 6.PROVIDE FLAME RETARDIBILITY INFORMATION FOR THE | | | CANOPY. | | | | | | 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS | | | AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS. | | | | | | 8.INCLUDE A LAYOUT OF THE EXISTING FIRE SPRINKLER | | | AND/OR FIRE ALARM SYSTEM DEVICES.HOW WILL THEY BE | | | AFFECTED BY THE SCOPE OF WORK? | | | | | | 9.IF THE FIRE PROTECTION SYSTEMS ARE MODIFIED DUE TO | | | THE SCOPE OF WORK, SEPARATE PERMIT AND PLANS WILL BE | | | REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2007-02-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-02-17 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-02-17 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2007-02-17 12:33:31 | PROVISO: | | | SHT P-120 | | | TOTAL DEVELOPED LGTH SCALED OFF PLANS , AT 50' . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-12-16 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-12-16 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2006-12-16 07:11:40 | PAUL SCHMITZ | | | [email protected] FBC 2004 PLUMBING | | | CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | DENIED,PLAN REVIEW ONLY | | | | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304 | | | . | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | 12. SEC 409.5 EQUIPMENT SHUT OFF VALVE. | | | EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWNSTREAM OF MANUAL SHUT OFF VALVE. | | | | | | 13.)PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT PLUMBING | | | PLANS. | | | | | | 14)WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | QUESTIONS 561-805-6692PAUL SCHMITZ | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-11-01 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-11-01 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2007-11-01 15:51:02 | TO PLANNING INBOX FOR LINDA MIA FRANCO'S REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-26 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-26 |
Time |
13:19 |
Sent To |
Z |
|
| Notes |
| 2007-10-26 13:20:11 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-26 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-26 |
Time |
11:37 |
Sent To |
ENG |
|
| Notes |
| 2007-10-26 11:37:56 | TO "RCHKSHI" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-19 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-19 |
Time |
11:02 |
Sent To |
E |
|
| Notes |
| 2007-10-19 11:02:48 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-24 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-24 |
Time |
12:16 |
Sent To |
B |
|
| Notes |
| 2007-09-24 12:17:11 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-13 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-13 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2007-10-02 14:49:05 | TO "COMM" BD#30 | | 2007-09-13 16:14:08 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-10 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-10 |
Time |
16:29 |
Sent To |
Z |
|
| Notes |
| 2007-07-10 16:29:20 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-30 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2007-05-10 09:18:48 | TO "COMM" BD#11/PLANS ON RACK/ 4 ROLLS AND PAPERWORK | | 2007-04-30 08:45:27 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-19 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-03-27 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-19 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-03-19 14:46:21 | TO "COMM' BD#52/PLANS ON RACK--4 ROLLS AND PAPERWORK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2007-02-02 09:43:29 | TO "COMM" BD#53 | | 2007-01-24 17:02:26 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-21 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-26 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2006-10-31 10:21:19 | TO "COMM" BD#54 | | 2006-10-26 15:22:52 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-20 |
Time |
20:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-29 |
Time |
09:53 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-03-29 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2007-03-29 09:57:52 | ** APPROVED FOR PERMIT** | | | | | | 1) ADDITIONAL MECHANICAL PERMITS WILL BE REQUIRED FOR | | | WALK-IN COOLER, HOOD, AND FIRE SUPPRESSION, PLANS TO BE | | | SUBMITTED WITH APPLICATION WHEN APPLYING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-16 |
Time |
08:40 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-02-16 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2007-02-16 09:11:43 | *FOR PLAN REVIEW ONLY, NOT FOR PERMIT* | | | *** DENIED *** | | | 1) ONE SET OF THE ENERGY CALCULATIONS IS A PHOTO COPY, | | | PLEASE SUBMIT TWO SIGNED AND SEALED SETS. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) AS REQUESTED IN LAST REVIEW 10-31-06. PLEASE SUBMIT | | | COOLING LOAD CALCULATIONS, PER 2004 FBC | | | 13-407.1.ABC.1. | | | | | | 4) PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED | | | ROOF TOP CONDENSER UNIT STANDS, SEE FS 553.842 (1) AND | | | FAC 9B-72.010 (31) (G). | | | ** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5) AS REQUESTED IN LAST REVIEW 10-31-06 NOTE #9. NEED | | | DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT (WITH | | | ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 FBC | | | 1609). RESPONSEWAS SEE DETAIL "C"/S4 WHICH SHOWS RTU | | | NOT MAU IF DETAIL IS FOR BOTH UNITS, PLEASE STATE SO IN | | | THE DETAIL. | | | | | | 6) AS NOTED IN LAST REVIEW 10-31-06 NOTE #10. SEE PAGE | | | A-140 SHOWS ROOF TOP AIR HANDLER, PLANS HAVE NOT BEEN | | | CORRECTED TO SHOW THE MAKE UP AIR UNIT, AS RESPONSE | | | STATES. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-31 |
Time |
13:32 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2006-10-31 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2006-10-31 14:21:32 | *FOR PLAN REVIEW ONLY, NOT FOR PERMIT* | | | *** DENIED *** | | | 1) ENGINEERING FIRM'S CERTIFICATE OF AUTHORIZATION | | | NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 2) THE ENGINEER RICHARD JONES PRINTED NAME AND LICENSE | | | NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 3) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.3. | | | | | | 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 5) PLEASE SHOW OUTDOOD AIR CALCULATIONS ON MECHANICAL | | | PLANS, PER 2004 FBC/M 403.2. | | | | | | 6) PLEASE SHOW A/C SYSTEM'S SEER OR EER ON EQUIPMENT | | | SCHEDULE. | | | | | | 7) NEED DETAIL FOR HANGING KITCHEN HOOD TO ROOF | | | STRUCTURE. | | | | | | 8) NEED DETAIL FOR SECURING COOLER CONDENSER UNIT AND | | | STAND, TO ROOF, TO WITHSTAND 140 MPH WINDS, PER 2004 | | | FBC 1609. | | | | | | 9) NEED DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT | | | (WITH ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 | | | FBC 1609). | | | | | | 10) SEE PAGE A-140 SHOWS ROOF TOP AIR HANDLER, MECH. | | | PLANS DO NOT LIST A ROOF TOP AIR HANDLER, DO YOU MEAN | | | THE MEKE UP AIR UNIT, PLEASE EXPLAIN OR CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-11-19 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-11-19 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2007-11-19 14:49:42 | REVIEWED AND APPROVED LAWN IRRIGATION PLAN SUBMITED | | | WITH APPROVED BUILDING PLANS. OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-30 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-30 |
Time |
10:29 |
Sent To |
B |
|
| Notes |
| 2007-08-30 10:36:51 | REVISION APPROVED: SHEET P100, PLAN NOTE ITEM #8 | | | REMOVED. SHEET P110, AS BUILT U/G SANITARY AND GREASE. | | | | | | ****************PROVISO**************** | | | PER FBC-2004 SECTION 604.9 WATER HAMMER ARRESTORS SHALL | | | BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S | | | SPECIFICATIONS. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-08-03 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-08-03 |
Time |
09:58 |
Sent To |
PC |
|
| Notes |
| 2007-08-03 10:01:19 | REVISION TO U/G HORIZONANTAL WASTE VENT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-03-31 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-03-31 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2007-03-31 10:09:20 | COULD HAVE EXPITEDPLANS MORE EFFICENTLY,IF LOCATION | | | OF INFORMATION REQUESTED HAD BEEB ADDRESSED, AS | | | REQUESTED IN PREVIIOUS NOTE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-02-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-02-17 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-02-17 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2007-02-17 13:23:34 | PAUL SCHMITZ | | | [email protected] FBC 2004 PLUMBING | | | CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED,2ND PLAN | | | REVIEW | | | EACH PREVIOUS COMMENT,WILL BE ADDRESSED,AS OK OR | | | DENIED. | | | NEW COMMENTS ADDRESSED SEPARATELY. | | | | | | 1)OK | | | | | | 2) DENIED, PROVIDE LOCATION OF WORK AND STAMPED SHTS | | | FROM DBPR | | | PLANS SHALL BE ROUTED TO DBPR | | | BUSINESS AND HOTEL DIVISION FOR | | | REVIEW. MINIMUM 2 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED | | | AND THE TWO PAGE ?WORKSHEETS? | | | ATTACHED TO EACH SET OF PLANS | | | PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH FOR | | | REVIEW. PLEASE CONTACT DBPR | | | AT (850) 487-1395. | | | | | | 3)DENIED, SEE ATTACHED RESPONSE FROM WPBUD,DATED | | | 12-26-06, 2-1250 GAL GREASE TANKS REQUIRED. | | | SHT P 200, GREASE TRAP SIZE. TO BE CONFIRMED BY | | | CONTACT W P BEACHWATERPLANT LAB SUPERVISOR | | | INDUSTRIAL COORDINATOR, | | | LYNN MASSON | | | OFFICE 561-822-2271E-MAIL [email protected] | | | | | | 4)OK | | | | | | 5) DENIED, SHT P-100 PLUMBING ISOMETRIC SHOWS PIPING | | | OVER HEAD. WITH DOWN FEED PIPE. | | | SHT P-100 DETAIL 7PLUMBING ISOMETRIC | | | SEC 606.1 LOCATION OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | ONTHE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES | | | OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL | | | OCCUPANCIES. | | | | | | 6)DENIED,SHT A-121, P-100; REFERENCES A DISHWASHER | | | #48, THEREFORE QUICK OPENING VALE. | | | SHT P100 SEC 604.9 WATER HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | 7) DENIED, NEW COMMENT | | | SHT CS LISTS L-1, L -2 , L-3 IRRIGATION, NOT WITH THIS | | | SET OF PLANS. | | | SHT P- 100, 110 PLAN NOTES #1, #9 REFERENCE TO TO SITE | | | UTILITY PLANS. | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION | | | 106.3.5). | | | | | | 8) OK | | | | | | END OF COMMENTS, QUESTIONS; 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-12-16 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-12-16 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2006-12-16 07:12:33 | PAUL SCHMITZ | | | [email protected] FBC 2004 PLUMBING | | | CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED,PROJECT, PLAN REVIEW ONLY. | | | | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) | | | PLANS SHALL BE ROUTED TO DBPR | | | BUSINESS AND HOTEL DIVISION FOR | | | REVIEW. MINIMUM 2 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED | | | AND THE TWO PAGE ?WORKSHEETS? | | | ATTACHED TO EACH SET OF PLANS | | | PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH FOR | | | REVIEW. PLEASE CONTACT DBPR | | | AT (850) 487-1395. | | | | | | 3) SHT P 200, GREASE TRAP SIZE. TO BE CONFIRMED BY | | | CONTACT W P BEACHWATERPLANT LAB SUPERVISOR | | | INDUSTRIAL COORDINATOR, LYNN MASSON | | | | | | OFFICE 561-822-2271E-MAIL [email protected] | | | | | | 4)SHT A-000 NUMBER OF REQUIRED PLUMBING FIXTURES | | | 403.1 MINIMUM NUMBER OF FIXTURES. | | | PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF | | | OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE | | | 403.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 403.1 | | | SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. | | | THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE | | | FLORIDA BUILDING CODE, BUILDING. OCCUPANCY | | | CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 403.5 LOCATION OF EMPLOYEE TOILET FACILITIES IN | | | MERCANTILE AND ASSEMBLY OCCUPANCIES. | | | EMPLOYEES SHALL BE PROVIDED WITH TOILET FACILITIES IN | | | BUILDING AND TENANT SPACES UTILIZED AS RESTAURANTS, | | | NIGHTCLUBS, PLACES OF PUBLIC ASSEMBLY AND MERCANTILE | | | OCCUPANCIES. THE EMPLOYEE FACILITIES SHALL BE EITHER | | | SEPARATE FACILITIES OR COMBINED EMPLOYEE AND PUBLIC | | | FACILITIES. THE REQUIRED TOILET FACILITIES SHALL BE | | | LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE | | | EMPLOYEES? WORK AREA AND THE PATH OF TRAVEL TO SUCH | | | FACILITIES, IN OTHER THAN COVERED MALLS, SHALL NOT | | | EXCEED A DISTANCE OF 500 FEET (152 M). THE PATH OF | | | TRAVEL TO REQUIRED FACILITIES IN COVERED MALLS SHALL | | | NOT EXCEED A DISTANCE OF 300 FEET (91 M). | | | | | | 403.1.1 POTTY PARITY. | | | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO | | | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS | | | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER | | | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE | | | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH | | | ?553.86, FLORIDA STATUTES. | | | | | | 5) SHT P-100 DETAIL 7PLUMBING ISOMETRIC | | | SEC 606.1 LOCATION OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | ONTHE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES | | | OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL | | | OCCUPANCIES. | | | | | | 6)SHT P100 SEC 604.9 WATER HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | 7)SHT P- 100, 110 PLAN NOTES #1, #9 REFERENCE TO TO | | | SITE UTILITY PLANS. | | | SITE PLANS NOT INCLUDED. | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION | | | 106.3.5). | | | | | | 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT PLUMBING | | | PLANS. | | | | | | END OF COMMENTS, QUESTIONS; 561-805-6692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-11-02 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-11-02 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-10-26 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-10-26 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2007-10-26 15:15:13 | PLANNING AND ZONING:***** PASSED WITH PROVISO **** | | | | | | 1.RESPOND TO COMMENTS IN WRITING. | | | | | | PROVISO- PRIOR TO OBTAINING FINAL CO:A TEMPORY CO | | | MAY BE OBTAINED IN THE MEANTIME ONLY. | | | | | | 2.THE SITE PLAN, LANDSCAPE PLANS AND PERTINENT PLANS | | | NEED TO BE REVISED TO REFLECT ADDED SIDEWALK/STAIR | | | CONNECTIONS AS REFLECTED IN THIS PERMIT.SUBMIT PLANS | | | TO THE PLANNING AND ZONING DEPARTMENT/CONSTRUCTION | | | SERVICES ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL:[email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-07-16 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-07-16 |
Time |
16:28 |
Sent To |
I |
|
| Notes |
| 2007-07-17 16:53:49 | PLANNING AND ZONING: **** PASSED WITH PROVISO**** | | | | | | 1.PROVIDE A COPY TO THE PLANNING AND ZONING DEPT. OF | | | THE NEW ELEVATIONS, REFLECTING THE CHANGE OF THE | | | MATERIALS FOR OUR FILE.PLEASE SEND IT TO MY | | | ATTENTION. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONINGDEPARTMENT | | | TEL:(561) 822-1443 | | | EMAIL:[email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-05-10 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-05-10 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2007-05-10 11:32:38 | PLANNING AND ZONING:PASSED WITH PROVISO | | | | | | 1.SURVEYS IN PACKET ARE NOT SIGNED AND SEALED. | | | REVISE ACCORDINGLY, WHEN RE-SUBMITTING PACKET. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT, | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | TEL:(561) 822-1443 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-03-27 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-03-23 |
Time |
10:54 |
Sent To |
I |
|
| Notes |
| 2007-03-27 17:52:23 | PLANNING AND ZONING: **** FAILED **** | | | | | | 1. PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 2. SHEET L-1 SHOWS PROPOSED PALM TREES (FLORIDA ROYAL | | | PALMS) ON TOP OF THE PROPOSED FREESTANDING SIGN. REVISE | | | LANDSCAPE PLAN OR SIGNAGE LOCATION TO ACCOMMODATE FOR | | | BOTH.KEEP IN MIND TO COMPLY WITH SIGHT TRIANGLE | | | CLEARANCE REQUIREMENTS. | | | | | | 3. NOTE: A SIGNAGE PERMIT FOR THE FREESTANDING SIGN | | | HAS BEEN SUBMITTED AND APPROVED (PERMIT NO. 07030246), | | | BASED ON AN EMAIL BY TRACY KIRKLAND (INTERPLAN) SENT | | | TODAY, 3-28-07, AT NOON, SHOWING THAT THE FREESTANDING | | | SIGN WILL REMAIN IN PLACE, BUT THE LANDSCAPE PLAN, | | | SHEET LP-1, WILL BE REVISED TO REFLECTTHE PALM TREES | | | SHIFTED AND CLUSTERED AWAY FROM BEING ON TOP OF THE | | | FREESTANDING SIGN. | | | | | | WHEN RE-SUBMITTING , PLEASE PROVIDE THREE (3) COPIES OF | | | THE REVISEDLANDSCAPE PLAN LP-1 (2 FOR THE BUILDING | | | DEPT. PACKET AND 1 FOR THE P& Z FILE) SIGNED AND SEALED | | | ONCE THE BLDG. PERMIT IS RETURNED TO YOU, AFTER FULL | | | REVIEW, WITH COMMENTS FROM CONSTRUCTION SERVICES. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-02-23 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-02-23 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2007-02-23 17:34:36 | PLANNING AND ZONING:*** FAILED *** | | | | | | 1.PLEASE PROVIDE RESPONSES TO COMMENTS IN WRITING. | | | | | | 2. THE SITE PLAN/DRAWINGS DO NOT MATCH THE APPROVED | | | PLANS FROM THE PLANNING AND ZONING DEPARTMENT.REFER | | | TO APPROVAL LETTER AND DRAWINGS.THEY HAVE BEEN MAILED | | | TO INTERPLAN, THE AGENT FOR THE PROJECT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL: | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | TEL: (561) 822-1443 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2006-11-16 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2006-11-16 |
Time |
14:30 |
Sent To |
I |
|
| Notes |
| 2006-11-16 18:02:46 | PLANNING AND ZONING ***** FAILED****** | | | | | | 1.THE SITE PLAN IS CURRENTLY UNDER REVIEW FOR AN | | | INFORMAL SITE PLAN REVIEW.ONCE ALL OUTSTANDING | | | COMMENTS ARE ADDRESSED, AN APPROVAL LETTER FROM THE | | | PLANNING AND ZONING DEPARTMENT WILL BE ISSUED. | | | PLEASE SUBMIT A COPY OF THE LETTER WITH PLANS WHEN | | | SUBMITTING FOR BUILDING PERMIT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT THE NUMBER | | | BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | TEL: (561) 822-1435 |
|
|
|
Account Summary | Usage Policy | Privacy Policy