Plan Review Details - Permit 06100956
Plan Review Stops For Permit 06100956
Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2007-11-02 Cont ID  
Sent By jwitmer Date 2007-11-02 Time 13:19 Rev Time 0.77
Received By jwitmer Date 2007-11-02 Time 13:19 Sent To PC
Notes
2007-11-02 13:20:59NEW C-3 REVISION TO PATIO AREAS, OK EQUIVALANT
 FACILITATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-10-26 Cont ID  
Sent By jwitmer Date 2007-10-26 Time 16:25 Rev Time 1.22
Received By jwitmer Date 2007-10-26 Time 16:25 Sent To PC
Notes
2007-10-26 16:41:08BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BEACH LAKES BLVD
 CONT: COLUMBIA CONSTRUCTION
 TEL: (321)246-4825
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 18 SHEET C3REVIEW
 ACTION: DENIED
  
 1)THE ORIGINAL PERMITTED PLANS INDICATED AN ACCESSIBLE
 ROUTE FROM THE PUBLIC WAY TO THE FRONT OF THE BUILDING.
 REVISION# 18 NOW INDICATES APPROXIMATELY 2'-0"
 DIFFERENCE IN GRADE AND EXTERIOR STAIRS.
 THE REVISION FAILS TO SHOW "EQUIVALENT FACILITATION"
 11-2.2 WHICH WILL REQUIRE A DISABLED PERSON TO HAVE TO
 USE THE DISABLED ACCES POINT BEHIND THE BUILDING. IF
 THE GRADE DIFFERENCE IN FRONT WAS MADE UP THROUGH AN
 ACCESSIBLE RAMP WTIH THE CORRECT SLOPE HANDRAILS AND
 LANDINGS BOTH DISABLED AND THOUGHS NOT DISSABLED WOULD
 BE ABLE TO USE THE FRONT ACCESSBLE ENTRY ROUTE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-10-22 Cont ID  
Sent By jwitmer Date 2007-10-22 Time 10:10 Rev Time 0.88
Received By jwitmer Date 2007-10-22 Time 10:10 Sent To PC
Notes
2007-10-22 10:11:13REVISION# 12 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-10-15 Cont ID  
Sent By jwitmer Date 2007-10-15 Time 11:11 Rev Time 1.55
Received By jwitmer Date 2007-10-15 Time 11:11 Sent To PC
Notes
2007-10-15 11:26:22BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BCH LAKES BLVD
 CONT: COLUMBIA CONSTRUCTION
 TEL: (321)246-4825
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION NO.12 8/16/07REVIEW
 ACTION: DENIED
  
 SHEETS A.300, A.305 & A.315DENIED. THIS BUILDING IS
 CLASSIFIED AS A TYPE II-B, UNPROTECTED, UNSPRINKLED.
 THE SHEETS LISTED ABOVE NOW INDICATE THE USE OF 5/8"
 CDX PLYWOOD FOR SHEATHING ON BEARING WALLS WHEN
 REVIEWING SECTION 603.1 AND TABLE 603 FOR A TYPE II-B
 STRUCTURE THERE CAN BE NO PLYWOOD SHEATHING FOR A II-B
 BUILDING.
 HOWEVER THIS IS THE DESIGN THAT YOU ELECTED TO USE, THE
 MINIMUM BUILDING TYPE BY CODE IS A TYPE V-B FOR A A-2
 OCCUPANCY GROUPWITH AN ALLOWABLE 6000 SQ FT/ SINGLE
 STORY.
  
 IF THIS BUILDING WAS TO BE DECLARED A TYPE V-B BUILDING
 AND TO USE PLYWOOD SUBSHEATHING THEREWOULD STILL BE
 CONCERNS IN AREAS WHERE THE SHEATHING WOULD BE WITHIN
 SIX INCHES OF GRADE. PLEASE REVIEW 2304.11.2.5 FOR WOOD
 SUBSHEATHING REQUIREMENTS.
  
 THE ORIGINAL PLANS WERE ALSO PULLED TO SEE IF THERE HAD
 BEEN REFRENCE MADE TO THE USE OF WOOD SUBSHEATHING OR
 POSSIBLE DENSE-GLASS SINCE THERE IS TO BE AN EFIS
 FINISH SYSTEM. I HADN'T FOUND ANY PRODUCT APPROVALS FOR
 THE EFIS WALL SYSTEMS.
 A BUILDING PROVISO # 1 WASISSUED WITH THE ISSUANCE
 OF THE PLANS:
 1) PLEASE PROVIDE PRODUCT APPROVAL REPORT FOR STO CORP.
 THE FLORIDA COVER SHEET INDICATE THE CORRESPONDING
 REPORT TO BE A ES REPORT NOT THE SUBMITTED MIAMI-DADE
 NOA.
 PLEASE INDICATE WHICH SUB-SYSTEM WILL BE USED IN
 CONJUCTION WITH THIS PROJECT. WILL BE REQUIRED WITHIN
 30 DAYS OF ISSUANCE.
 TO DATE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED AND
 THIS ISSUE STILL REMAINS AS "OPEN".
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-10-15 Cont ID  
Sent By jwitmer Date 2007-10-15 Time 11:09 Rev Time 2.22
Received By jwitmer Date 2007-10-15 Time 11:09 Sent To PC
Notes
2007-10-15 11:11:19REVIEWED SHEETSFOR REVISION# 12 8/16/07
 A.000
 A.021
 A.101
 A.110
 A.120
 A.125
 A.130
 A.201
 A.215

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-09-25 Cont ID  
Sent By jwitmer Date 2007-09-25 Time 13:53 Rev Time 1.33
Received By jwitmer Date 2007-09-25 Time 13:53 Sent To PC
Notes
2007-09-25 13:54:27YKK UPDATES TO PRODUCT APPROVALS FOE CURTAINWALL,
 STOREFRONT AND DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 08:49 Rev Time 1.33
Received By jwitmer Date 2007-09-14 Time 08:49 Sent To PC
Notes
2007-09-14 08:59:55BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BEACH LAKES BLVD
 CONT: COLOMBIA CONSTRUCTION
 TEL: (615)497-7032
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND SHOP DRAWING REVIEW:
 ACTION: DENIED
  
 1)THE SHOP DRAWINGS IDENTIFIED THREE YKK PRODUCTS TO
 BE USED IN THIS INSTALLATION.T HE CONTRACTOR FAILED TO
 SUBMIT ONE OF THE PRODUCTS LISTED ON THE SHOP DRAWINGS
 YHS-50 A STOREFRONT SYSTEM. THE CONTRACTOR FAILED TO
 PROVIDE THE FLORIDA COVER SHEETS FOR ALL PRODUCTS, 2 OF
 THE 3 PRODUCTS REQUIRE A PE TO VERIFY THE REPORTS
 ANCHOR CALCULATIONS AND STRUCTURAL ANALYSIS SINCE THEY
 WERE DESIGNED AND TESTED BEFORE THE 2004 FBC WHEN
 DESIGNERS TOOK A 1.33 INCREASE IN STEEL AND STEEL
 FASTENERS. THE FLORIDA COVER SHEET INDICATES WHICH
 PRODUCTS HAVE THE CALCULATIONS REVISED. PLEASE HAVE THE
 PE DO AN ANALYSIS ON THE FASTENERS AND INDICATE SUCH IN
 WRITING. PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL
 NUMBER AND BACK UP REPORT, THIS BEING A MIAMI-DADE
 NOA.
  
 2) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-08-31 Cont ID  
Sent By jwitmer Date 2007-08-31 Time 13:32 Rev Time 0.77
Received By jwitmer Date 2007-08-31 Time 13:32 Sent To PC
Notes
2007-08-31 13:33:03REVISION 11 & 12.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-08-29 Cont ID  
Sent By jwitmer Date 2007-08-29 Time 11:24 Rev Time 1.22
Received By jwitmer Date 2007-08-29 Time 11:24 Sent To PC
Notes
2007-08-29 11:31:08BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BEACH LAKES BLVD
 CONT: COLOMBIA CONSTRUCTION
 TEL: (615)497-7032
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWING REVIEW:
 ACTION: DENIED
  
 1)THE SHOP DRAWINGS FAIL TO INDICATE THE PRODUCT
 MANUFACTURERAND THE MODEL NUMBER AND OR NAME ON THE
 SUBMITTAL.
 PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER AND
 BACK UP REPORT, THIS BEING A MIAMI-DADE NOA.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-07-18 Cont ID  
Sent By jwitmer Date 2007-07-18 Time 14:00 Rev Time 1.22
Received By jwitmer Date 2007-07-18 Time 14:00 Sent To PC
Notes
2007-07-18 14:01:45REVISION# 9 STOREFRONT CHANGE TO YKK CURTAIN WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-10 Cont ID  
Sent By jwitmer Date 2007-05-10 Time 15:31 Rev Time 4.44
Received By jwitmer Date 2007-05-10 Time 15:31 Sent To PC
Notes
2007-05-10 15:38:23 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT#06100956
 ADDRESS: 2380 PALM BEACH LAKES
 CONT:
 TELL # (561)
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF PLANS.106.1.1
 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISOS:
  
 1) PLEASE PROVIDE PRODUCT APPROVAL REPORT FOR STO CORP.
 THE FLORIDA COVER SHEET INDICATE THE CORRESPONDING
 REPORT TO BE A ES REPORT NOT THE SUBMITTED MIAMI-DADE
 NOA.
 PLEASE INDICATE WHICH SUB-SYSTEM WILL BE USED IN
 CONJUCTION WITH THIS PROJECT. WILL BE REQUIRED WITHIN
 30 DAYS OF ISSUANCE.
  
 2 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3) ) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By jwitmer Date 2007-04-25 Time 09:40 Rev Time 1.33
Received By jwitmer Date 2007-04-25 Time 09:39 Sent To PC
Notes
2007-04-25 09:41:15BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BCH LAKES BLVD
 CONT:""PLAN REVIEW""
 TEL: (407)645-5008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 2004 BUILDING PLAN REVIEW
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 3RD REQUEST COMMENT# 11 FROM THE PREVIOUS REIEW,
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 MISSING REPORTS:
 A) KAWNEER CURTAIN WALL SYSTEM PLANS INDICATE THE USE
 OF SEERIES 1600 SYSTEM 2 MISSING REPORT# 04-0908.05 AND
 THE TECHNICAL SHEETS
 B) STO- EFIS, SUBSYSEMS ARE NOT MARKED AS TO WHICH
 SYSTEM TO BE USED, NO REPORTS SUBMITTED, SEE
 LIMITATIONS.
 C) ROOFING ASSEMBLIES: JOHN MANVILLE, SINGLE PLY
 SYSTEM, SUBSYSTEM IS NOT MARKED AS TO WHICH SYSTEM IS
 TO BE USED.
  
 4) THE PERMIT APPLICATION INDICATES THIS IS DEMOLITION
 OF AN EXISTING BUILDING AND A NEW SMALLER RESTARAUNT.
 PLEASE TAKE YOUR PLANS TO THE PALM BEACH COUNTY
 BUILDING DEPARTMENT FOR IMPACT FEE ASSESSMENT, THERE
 MAY BE A CREDIT DUE?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By jwitmer Date 2007-03-02 Time 09:47 Rev Time 3.33
Received By jwitmer Date 2007-03-02 Time 09:47 Sent To PC
Notes
2007-03-02 10:55:55BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BCH LAKES BLVD
 CONT:""PLAN REVIEW""
 TEL: (407)645-5008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 2004 BUILDING PLAN REVIEW
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)2ND REQUEST, RESPONSE INDICATES SHEET S-1 G-3 STATES
 ADJACENT
 ONSITE FACILITIES, STRUCTURES & UTILITY LINES NO
 MENTION OF
 ADVERSELY IMPACT OF ADJACENT PROPERTY WHICH INCLUDES
 BUT NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER
 DEBRIS
 AND THE STORAGE OF CONSTRUCTION MATERIAL. 109.3.10*
 IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) COMPLIED.
  
 5) 2ND REQUEST,5C TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6 TABLE 601/
 RESPONSE IS TYPE II BUILDING, DOES THIS MEAN
 THAT YOU WANT TO DESIGNTO THE MORE RESTRICTIVE TYPE
 II REQUIREMENTS?
 THIS BUILDING BEING A A-2 OCCUPANCY, MINIMUM BUILDING
 TYPE OF V-B WITH 6,000 SQ FT / 1 STORY.
  
 6) 2ND REQUEST, PLEASE SUBMIT REPORT PRODUCED BY
 GEOSYNTEC CONSULANTS 5/01/06
 FBC 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) COMPLIED WITH SUBMITTALS PROVIDED, MISSING
 SUBMITTALS.
  
 8) COMPLIED, NEW CONSTRUCTION.
  
 9) COMPLIED.
  
 10A) SHEET S-1 DESIGN CRITERIA,D-1 STATES ASCE 7-??
 DOES NOT PROVIDE THE EDITION?
  
 10B) ROOF ZONE 3 THE TRTIBUTARY AREA OF THE FASTENER IS
 LESS THAN 10 SQ FT THE NEGATIVE PRESSURES REQUIRED TO
 HOLD THE SYSTEM DOWN IS -89.0.
  
 11) 2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 MISSING REPORTS:
 D) EXTERIOR METAL DOOR
 F ) LOUVERS
 G) TRUSS ANCHOR FOR THE METALC CHANNELS
 I) ROOFING ASSEMBLIES FLAT ROOF AS WELL AS THE METAL
 CANOPY
  
 11B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT
 12)ENERGY CALCS PLEASE PROVIDE 2 ORIGINAL SIGNED AND
 SEALED ENERGY REPORTS
 PLEASE HAVE THE OWNER/ AGENT SIGN THE ENERGY
 CALCULATIONS.
  
 SINCE THIS IS A DEMO AND NEW STURCTURE REVIEW BY P.B.
 COUNTY IMPACT FEE OFFICE WILL BE REQUIRED.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By jwitmer Date 2006-11-22 Time 14:16 Rev Time 5.55
Received By jwitmer Date 2006-11-22 Time 14:16 Sent To  
Notes
2006-11-22 15:16:45BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BCH LAKES BLVD
 CONT:""PLAN REVIEW""
 TEL: (407)645-5008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 2004 BUILDING PLAN REVIEW
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 5 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) . FT. LIV SPACE/ FL
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
 J ) OCCUPANT LOAD
 K ) FLOOD ZONE
  
 6)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 7)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8)SHEET A110 INDICATES THAT THIS IS AN EXISTING
 RERAUNT
 AND THERE IS ONLY MODIFICATIONS TO THE EXISTING
 STRUCTURE,
 THE PLAN REVIEW APPLICATION INDICATES THIS IS A
 COMPLETE
 DEMO AND TO CONSTRUCT A NEW CHIPOTLE RESTRAUNT. PLEASE
  
 CORRECT. DISCREPANCY!!!
  
 9)SHEET S-1WIND DESIGN THE BUILDING CATEGORY IS
 LABELED AS A I NOT A II.
 BUILDING CATEGORY I IS FARM OUT BUILDINGS OR SMALL SHED
 CONSTRUCTION. CORRECT.
  
 10) PLEASE PROVIDE THE POSITIVE AND NEGATIVE PRESSURES
 ON THE ELEVATIONS, INDICATE THE INTERIOR ZONE 4 AND END
 ZONES, ZONE 5.
 ALSO PROVIDE A ROOF TOP VIEW WITH ZONES 1,2 & 3 WITH
 THE ASSOCIATED PRESSURES.
  
 11)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
 11A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED, STOREFRONT
 B) OPERATABLE WINDOWS
 C) GLAZED DOORS
 D) EXTERIOR METAL CORE DOORS
 E) MULLIONS
 F) LOUVERS
 G) TRUSS ANCHORS FOR METAL C CHANNELS
 H) EFIS SYSTEMS & SOFFITS
 I) ROOFING ASSEMBLIES
 J) PRE-ENGINEERED A/C STANDS
  
 11B)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11C) ROOFING ASSEMBLIES NEED THE FOLOWING INFORMATION
 PROVIDED WITH THE REPORT:) THIS ROOF IS MISSING OR
 NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 12)PROVIDE ENGINEERING FOR THE CANOPY TO BE LOCATED
 ON
 THE SOUTH SIDE OF THE BUILDING. PLANS,
 SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 13)) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
 FBC 13-103.1.1.1THE PROFESSIONALS RESPONSIBLE FOR
 THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, TO CERTIFY COMPLIANCE.
  
 14) PROVIDE DOCUMENTATION OF COMPLIANCE WITH 11-5.2 &
 11-5.5.5& 11-5.6.
  
 15) PLANS ARE TO INDICATE COMPLIANCE WITH: 2603.9.2
 CLEARANCE BETWEEN EARTH AND FOAM PLASTICS APPLIED TO
 THE
 EXTERIOR WALL SHALL BE NOT LESS THAN 6 INCHES (152
 MM).
  
  
 16)SHEET S2 NEEDS TO INDICATE COMPLIANCE WITH: 1816.1
 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 1816.1.1
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, THE INITIAL CHEMICAL SOIL TREATMENT INSIDE
 THE FOUNDATION PERIMETER SHALL BE DONE AFTER ALL
 EXCAVATION, BACKFILLING AND COMPACTION IS COMPLETE.
  
 1816.1.2
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL
 SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL
 TREATMENT, INCLUDING SPACES BOXED OR FORMED.
  
 1816.1.3
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SPACE IN CONCRETE FLOORS BOXED OUT OR
 FORMED FOR THE SUBSEQUENT INSTALLATION OF PLUMBING
 TRAPS, DRAINS OR ANY OTHER PURPOSE SHALL BE CREATED BY
 USING PLASTIC OR METAL PERMANENTLY PLACED FORMS OF
 SUFFICIENT DEPTH TO ELIMINATE ANY PLANNED SOIL
 DISTURBANCE AFTER INITIAL CHEMICAL SOIL TREATMENT.
  
 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.
  
 1816.1.5
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CONCRETE OVERPOUR OR MORTAR ACCUMULATED
 ALONG THE EXTERIOR FOUNDATION PERIMETER SHALL BE
 REMOVED PRIOR TO EXTERIOR CHEMICAL SOIL TREATMENT, TO
 ENHANCE VERTICAL PENETRATION OF THE CHEMICALS.
  
 1816.1.6
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICAL SOIL TREATMENTS SHALL ALSO BE
 APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN 1
 FOOT (305 MM) OF THE PRIMARY STRUCTURE SIDEWALLS. ALSO,
 A VERTICAL CHEMICAL BARRIER SHALL BE APPLIED PROMPTLY
 AFTER CONSTRUCTION IS COMPLETED, INCLUDING INITIAL
 LANDSCAPING AND IRRIGATION/SPRINKLER INSTALLATION. ANY
 SOIL DISTURBED AFTER THE CHEMICAL VERTICAL BARRIER IS
 APPLIED SHALL BE PROMPTLY RETREATED.
  
 17) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 NOTE WITH THE DEMOLITION OF THE OLD BUILDING BE CERTAIN
 TO GET THE CREDIT FROM THE DEMO-ED BUILDING!!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 08:40 Sent To B
Notes
2007-10-20 08:56:23 
 ** ELECTRICAL PLANS REDINED AS PANEL "C" IS TO MEET
 110.11,110.26, 240.24C,D.
  
  
  
  
  
  
  
 REVIEWED PER ROBERT BROWN.ABO
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-10-05 Cont ID  
Sent By dpalmer Date 2007-10-05 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2007-10-05 Time 15:32 Sent To  
Notes
2007-10-05 15:32:21 
 *** DENIED REVISION ***
  
  
 1) NOTE: PLANS ARE NOW SHOWING A NEW SUB PANEL BEING
 LISTED ON PANEL *B* HOWEVER THIS NEW SUB PANEL DOES NOT
 EXIST ON RISER.
 PLEASE SHOW WHERE THIS NEW PANEL IS.
 PLEASE SEE THE PLANS INDICATE A J-BOX FOR CONNECTION OF
 THESE NEW FEEDERS/BRANCH CIRCUITS YET THE LOCATION OF
 THIS PANEL CAN NOT BE CONFIRMED.
 PLEASE SEE THE PANEL SCHEDULE *B* DOES NOT INDICATE ANY
 NEUTRAL CONDUCTOR WITH THE OTHER CONDUCTORS AS LISTED.
 CLARIFY WHERE THE PREVIOUS 120V CIRCUITS NOW OBTAIN A
 NEUTRAL IF NONE IS INSTALLED.
 DOES THIS PANEL CONTAIN OVER CURRENT PROTECTION
 DEVICES?
 DOES THIS PANEL MEET THE MINIMUM CLEARANCE REQUIREMENTS
 PER 110.26, 240.24?
 DOES THIS PANEL MEET THE LOCATION FOR ITS ENVIRONMENT?
 110.3
 PLEASE SUBMIT THE PANEL SCHEDULE FOR THIS NEW CHEF
 TABLE PANEL.
 PLEASE SHOW LOCATION AND MEETING 110.26
 PLEASE PROVIDE LISTING FOR EQUIPMENT TO REVIEW. THIS
 WILL NEED TO SHOW ALL ITEMS BEING FED/EQUIPMENT
 SCHEDULE. 90.7, 110.3
  
 FBC 106.1.2
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-03 Cont ID  
Sent By dpalmer Date 2007-05-03 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2007-05-03 Time 16:53 Sent To  
Notes
2007-05-03 16:54:16PLANS REMOVED FROM INCOMING, ELEC OK, AND PLANS ROUTED
 BACK TO INCOMING WAITING FOR COMM BOARD.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 16:25 Sent To  
Notes
2007-03-24 16:30:26PLANS WERE REVIEW WHILE IN ZONING, PLANS REMAIN IN
 ZONING ON 3/24
2007-03-24 16:27:07*** UNSAT 3RD REVIEW **
 * FIRST REVIEW UNDER PERMIT.
  
  
 1) NOTE: PLEASE CLARIFY SHEETS 2 AND 3 OF THE FLORIDA
 ENERGY CALCULATIONS. PLEASE SEE THE FOLLOWING AS THEY
 DO NOT CORRELATE WITH THE ELECTRICAL PLANS.
  
 A) PLEASE SEE THAT THERE IS NOT EXTERIOR LIGHTING
 ENTERED AND PARKING EXTERNAL LIGHTING ON CALCULATIONS
 YET THE PLANS CONTAIN BOTH.
 B) PLEASE SEE THE BATH FIXTURES, WATTAGE AND CONTROLS
 DO NOT CORRELATE. THE INPUT DATA ONLY CONTAINS ONE
 FIXTURE OF EACH TYPE WHEN THERE ARE TWO FIXTURES OF
 EACH TYPE ON PLANS.(ONE OF EACH TYPE OF FIXTURE IN EACH
 BATH)
 PLEASE ALSO SEE THE TYPE OF CONTROL ENTERED IS
 *CENTRAL* WHICH IS NOT POSSIBLE WHEN THE PLANS DO NOT
 HAVE A *CENTRAL CONTROL*. PLANS DO INDICATE *OCCUPANCY
 SENSOR TYPE CONTROL*.
 C) PLEASE SEE DINING TYPE E WHICH STATES *CENTRAL
 CONTROL*, HOWEVER NO CENTRAL LIGHTING CONTROL SYSTEM IS
 PROVIDED. THIS TYPE OF FIXTURE IS WIRED AHEAD OF ANY
 CONTROLS OR SWITCHES PER 700.12E ANYWAY. PLEASE
 ADJUST.
 D) PLEASE SEE SIGNAGE IN KITCHEN AREA, SHOWS C-1 AS 17W
 AND 16W ON CALCULATIONS.
 E) PLEASE SEE KITCHEN EM TYPE FIXTURES WHICH INDICATE
 *CENTRAL CONTROL* FOR THESE ALSO. SAME AS NOTED ON *C*
 ABOVE.
  
 PLEASE COORDINATE. IF A LIGHTING SYSTEM IS BEING
 INSTALLED PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT
 ALL INFORMATION FOR SAID SYSTEM.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 19:05 Sent To  
Notes
2007-02-04 19:55:52******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
  
 ** PLEASE KNOW THAT PLANS STILL HAVE NOT BEEN SUBMITTED
 FOR PERMIT APPLICATION ANS SINCE THE LAST REVIEW THE
 STATE OF FLORIDA HAS ADOPTED NEW CODES. PLANS HAVE BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN
 SUBMITTED FOR PERMIT.
 ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT, THEY
 ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS
 THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH
 CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT
 MAY CHANGE.
  
  
 1) NOTE:NO/OK, PLEASE SEE MOST OF THE PREVIOUS NOTE
 WAS ADDRESSED HOWEVER PLEASE SEE THE STATE OF FLORIDA
 HAS ADOPTED NEW CODES AND THE FOLLOWING SHALL BE
 STATED.
 2005 NFPA-70 NEC.
 PLANS INDICATE A 2004 NEC WHICH IS NOT VALID.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE THAT THE FOLLOWING CODES AT A MINIMUM SHALL
 BE STATED ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72
 ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA
 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE
 NFPA-70 WILL BE THE 2005.)
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK/NO, PLEASE SEE THE SIGN CIRCUITS WERE ADDED
 WHICH IS OK, HOWEVER PLEASE SEE THE LOAD ON THESE IS
 SHOWN AT 1500VA AND 10AMPS? PLEASE SEE 1500VA @120VOLTS
 IS 12.5. THIS COULD HAVE BEEN REDLINED, HOWEVER THE
 PLANS ARE NOT IN FOR PERMIT AND ARE COMING BACK FOR
 OTHER COMMENTS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN VA TO BE
 SHOWN FOR SIGN CIRCUIT. 1200 MIN.
  
 5) NOTE: OK.
  
 6) NOTE: OK, HOWEVER PLEASE SEE THE FOOTER IS BEING
 SHOWN FOR AN ATTACHMENT, PLEASE VERIFY IF EXISTING OR
 IS IT THE SPECIFICATION OF THE ENGINEER FOR THE
 EXISTING FOOTER TO BE *CHIPPED* INTO TO OBTAIN THIS
 CONNECTION IF NOT EXISTING?
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM DETAIL.
 STATING CODE COMPLIANCE IN LIEU OF DETAIL IS NOT
 PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS KNOWN
 TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING AND
 THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A
 MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS
 REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS
 LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50,
 250.56 250.104 ETC.
  
 7) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS
 INFORMATION WAS SUBMITTED IN PACKAGE HOWEVER THIS COULD
 NOT BE LOCATED.
 PLEASE SEE TWO SEPARATE ELECTRICAL SITE PLANS WERE
 SUBMITTED SHOWING TWO SEPARATE PHOTO-METRICS ETC.
 PLEASE SEE TWO SEPARATE DESIGN PROFESSIONALS ALSO.
 PLEASE SEE THAT THE PLANS SHALL STATE THE MINIMUM 2004
 FBC WIND LOAD OF 140MPH (3 SECOND GUST) EVEN IF THE
 CALCULATIONS ARE SEPARATE. PLEASE KNOW THAT IF THE
 POLES ARE NOT ORDERED AND OBTAINED AT THE TIME OF
 PERMIT APPLICATION THE CALCULATIONS CAN BE A *PROVISO*
 AS LONG AS THE PLANS INDICATE THE CORRECT INFORMATION.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW LT POLES.
 PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT AREA) OF
 LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS WHICH WILL
 BE REQUIRED TO BE SIGNED, DATED AND SEALED BY A FLORIDA
 PE. PLEASE ALSO BE SURE THE TITLE BLOCK FOR THE DESIGN
 PROFESSIONAL IS ON PLANS.
  
 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL
 SCHEDULES. 310.16,240.4,
 FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH.
 106.1.2
 PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION
 AT THIS TIME.
  
  
 ** NEW NOTES **
  
 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGN
 PROFESSIONAL. PLEASE SEE THE CALCULATIONS SUBMITTED ARE
 PHOTO-COPIES OF SIGNED AND SEALED ONES.
 PLEASE SEE FS 471.025, FAC 61G15-23.002 AND FBC
 13-103.1.1.1
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 20:56 Sent To  
Notes
2006-11-04 16:59:23*** UNSAT ***
  
  
 ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN SUBMITTED FOR
 PERMIT.
 ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT , THEY
 ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS
 THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH
 CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT
 MAY CHANGE.
 PLEASE KNOW, THE NFPA-70 WILL BE CHANGING AND THE 2005
 MAY BE ADOPTED BY THE STATE IN THE NEXT COUPLE OF
 MONTHS.
  
  
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A
 MINIMUM SHALL BE STATED ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72
 ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA
 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE
 NFPA-70 WILL BE THE 2005.)
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF
 RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF ENGINEER AND MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR FIRM.
 PLEASE SEE FLORIDA STATUTES 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE ALSO SEE FRONT COVER SHEET.
  
 3) NOTE: PLEASE SEE 210.62 FOR SPACING OF WINDOW
 RECEPTS. PLEASE ALSO SEE 220.12A FOR LOAD WHICH IS
 REQUIRED TO BE SHOWN IN THE BREAK DOWN OF THE LOAD
 CALCULATIONS SUBMITTED.
 PLEASE SEE PLANS, PER SCALE APPEAR TO HAVE A COUPLE
 MISSING.
  
 4) NOTE: PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN
 VA TO BE SHOWN FOR SIGN CIRCUIT. 1200 MIN.
  
 5) NOTE: PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING
 CONDUCTOR" FROM THE METER TO THE MAIN DISCONNECT.
 PLEASE 250.6, AND 250.24B AS THIS EQUP GRND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM
 DETAIL. STATING CODE COMPLIANCE IN LIEU OF DETAIL IS
 NOT PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS
 KNOWN TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING
 AND THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A
 MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS
 REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS
 LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50,
 250.56 250.104 ETC.
  
 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW
 LT POLES. PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT
 AREA) OF LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS
 WHICH WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED
 BY A FLORIDA PE. PLEASE ALSO BE SURE THE TITLE BLOCK
 FOR THE DESIGN PROFESSIONAL IS ON PLANS.
  
 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL
 SCHEDULES. 310.16,240.4,
 FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH.
 106.1.2
 PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION
 AT THIS TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-11-04 16:14:09REVIEW IN PROGRESS
2006-11-03 20:56:23IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2007-10-26 Cont ID  
Sent By rchokshi Date 2007-10-26 Time 13:14 Rev Time 0.00
Received By rchokshi Date 2007-10-26 Time 13:14 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-05-02 Cont ID  
Sent By rchokshi Date 2007-05-02 Time 10:50 Rev Time 0.00
Received By rchokshi Date 2007-05-02 Time 10:50 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-03-30 Cont ID  
Sent By rchokshi Date 2007-03-30 Time 11:04 Rev Time 0.00
Received By rchokshi Date 2007-03-30 Time 10:55 Sent To  
Notes
2007-03-30 11:04:50PLEASE EXPLAIN THE FOLLOWINGS:
  
 1. HOW DID YOU CALCULATE WATER QUALITY VOLUME? PLEASE
 SHOW WHAT CRITERIA DID YOU YUO USE EITHER 1" OVER
 ENTIRE SITE OR2.5"CRITERIA?? PLEASE SHOW THE
 DETAILED CALCULATIONS OVER PERVIOUS/IMPERVIOUS AREAS.
  
 2. ARE YOU USING EXFILTRATION TRENCH? IF YOU DO, PLEASE
 SHOW HOW DID YOU CALCULATE LENGTH OF EXFILTRATION
 TRENCH,ETC?OR DRY DETENTION POND VOLUME, ETC?
  
 3. PLEASE INCLUDE ALL THESE CAL. IN YOUR REPORT WHEN
 YOU SUBMIT NEXT TIME.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By rchokshi Date 2007-02-09 Time 16:12 Rev Time 0.00
Received By rchokshi Date 2007-02-09 Time 15:43 Sent To  
Notes
2007-02-09 16:12:36PLEASE PROVIDE FOLLOWING INFO:
  
 1. YOU NEED TO GET A C.D. FROM 1000 45TH STREET
 ENG(494-1040) FOR ALL STANDARD NOTES OF CITY OF WPB
 WITH WPB LOGO AND COPY/PASTE ON YOUR DRAWINGS. ALSO
 PLEASE WRITE A NOTE ON YOUR GENERAL NOTES SECTION THAT
 ALL CONSTRUCTION WORK WILL BE PERFORMED PER CITY OF
 WPB'S LATEST STANDARDS.
 2. PLEASE WRITE A NOTE ON THE DRAWING THAT DUMPSTER
 LOCATION MUST BE ACCESSIBLE FOR TRUCK PICKUP.
 3.FLOOR ELEVATION MUST INCLUDE CONSIDERATION OF 100
 YEAR FLOOD ELEVATION DATA, PLEASE PROVIDE FLOOR
 ELEVATION ACCORDINGLY.PLEASE PROVIDE 100 YEAR FLOOD
 INFO.
 4.PLEASE PROVIDE POLLUTION PREVENTION SILT FENCE
 DETAILS, LIKE CLOTHES USED, POST HEIGHT, HEIGHT OF THE
 FENCE ETC.
 5. UTILITIES DEPT AT 45TH STREET HAS TO APPROVE YOUR
 PLAN BEFORE WE APPROVE, PLEASE SEND A APPROVAL COPY.
 6. ACCORDING TO YOUR INFO, ALL STORM WATER FROM YOUR
 SITE, GOES INTO YOUR POND AND STAYS IN YOUR SITE, IS
 THIS TRUE? PLEASE EXPLAIN
 PLEASE RESUBMIT ALL STORM WATER CAL ETC WHEN YOU
 RESUBMIT NEXT TIME.
  
 PLEASE EXPLAIN ALL OF THESE ITEM IN YOUR RESPOND TO
 EXPEDITE THE PERMITTING PROCESS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By rchokshi Date 2006-11-17 Time 16:25 Rev Time 0.00
Received By rchokshi Date 2006-11-17 Time 16:13 Sent To  
Notes
2006-11-17 16:25:27PLEASE PROVIDE FOLLOWING INFO:
 1. NEED TO PREPARE DRAINAGE/STORM WATERPLANS.LIKE
 SHEET C-1, C-2, ETC, JUST A SUGESTION
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH
 REPORT
 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 8. HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER
 PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE
 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-08-23 Cont ID  
Sent By mawillia Date 2007-08-23 Time 16:22 Rev Time 0.00
Received By mawillia Date 2007-08-23 Time 15:33 Sent To P
Notes
2007-08-23 16:19:47*****APPROVED*****
  
  
 APPROVED THE ELIMINATION OF SHEET FP100 WHICH
 REFERENCES THE BUILDING HAVING A FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.AS PER NFPA 101- 2003 EDITION, THESE
 SYSTEMS ARE NOT REQUIRED SINCE THE OCCUPANT LOAD IS
 LESS THAN 300.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 17:22 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 17:19 Sent To  
Notes
2007-05-10 17:22:14*****APPROVED*****
  
  
 PLAN SHEET LS100,A200, FP100, AND E100 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-16 Cont ID  
Sent By mawillia Date 2007-04-16 Time 16:09 Rev Time 0.00
Received By mawillia Date 2007-04-16 Time 15:32 Sent To  
Notes
2007-04-16 15:37:19*****PROVISO*****
  
  
 THECOMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS
 APPEAR TO HAVE BEEN ADDRESSED;THE APPROPIATE PLAN(S)
 WILL BE STAMPED WHEN OTHER PLAN REVIEW HAVE BEEN
 SATISFIED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-01 Cont ID  
Sent By mawillia Date 2007-03-01 Time 19:11 Rev Time 0.00
Received By mawillia Date 2007-03-01 Time 19:10 Sent To  
Notes
2007-03-01 19:35:03*****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
  
 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION
 CODE, THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
 LIST ON SHEET A000,FIRE CODE: 2004 FLORIDA FIRE
 PREVENTION CODE;LIFE SAFETY: 2003 NFPA 101
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
 PLEASE SHOW ON THE PLANS
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEROF.PLEASE SHOW ON THE PLANS
  
 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
 PLEASE SHOW ON THE PLANS
  
 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.DISPLAYED NUMERICAL
 ADDRESS SHALL BE ON THE STRUCTURE OF THE BUILDING, NOT
 THE DOOR OF THE BUILDING.
  
 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS. PLEASE
 SHOW ON THE PLANS
  
 8.INCLUDE A LAYOUT OF THE EXISTING AND/OR NEW FIRE
 ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH
 COMMENTWAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 12:56 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 12:56 Sent To  
Notes
2006-12-21 13:49:25*****DENIED*****
  
  
  
 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION
 CODE, THE 2003 EDITION OF NFPA 101 SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEROF.
  
 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
 6.PROVIDE FLAME RETARDIBILITY INFORMATION FOR THE
 CANOPY.
  
 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS.
  
 8.INCLUDE A LAYOUT OF THE EXISTING FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM DEVICES.HOW WILL THEY BE
 AFFECTED BY THE SCOPE OF WORK?
  
 9.IF THE FIRE PROTECTION SYSTEMS ARE MODIFIED DUE TO
 THE SCOPE OF WORK, SEPARATE PERMIT AND PLANS WILL BE
 REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-02-17 Cont ID  
Sent By pschmitz Date 2007-02-17 Time 12:35 Rev Time 0.00
Received By pschmitz Date 2007-02-17 Time 12:20 Sent To  
Notes
2007-02-17 12:33:31PROVISO:
 SHT P-120
 TOTAL DEVELOPED LGTH SCALED OFF PLANS , AT 50' .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-16 Cont ID  
Sent By pschmitz Date 2006-12-16 Time 07:10 Rev Time 0.00
Received By pschmitz Date 2006-12-16 Time 07:10 Sent To  
Notes
2006-12-16 07:11:40PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED,PLAN REVIEW ONLY
  
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. SEC 409.5 EQUIPMENT SHUT OFF VALVE.
 EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWNSTREAM OF MANUAL SHUT OFF VALVE.
  
 13.)PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 14)WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 QUESTIONS 561-805-6692PAUL SCHMITZ
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-11-01 Cont ID  
Sent By rbrown Date 2007-11-01 Time 15:50 Rev Time 0.00
Received By rbrown Date 2007-11-01 Time 15:50 Sent To  
Notes
2007-11-01 15:51:02TO PLANNING INBOX FOR LINDA MIA FRANCO'S REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 13:19 Rev Time 0.00
Received By shill Date 2007-10-26 Time 13:19 Sent To Z
Notes
2007-10-26 13:20:11TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 11:37 Rev Time 0.00
Received By shill Date 2007-10-26 Time 11:37 Sent To ENG
Notes
2007-10-26 11:37:56TO "RCHKSHI" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 11:02 Rev Time 0.00
Received By shill Date 2007-10-19 Time 11:02 Sent To E
Notes
2007-10-19 11:02:48TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 12:16 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 12:16 Sent To B
Notes
2007-09-24 12:17:11TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 16:13 Sent To  
Notes
2007-10-02 14:49:05TO "COMM" BD#30
2007-09-13 16:14:08WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 16:29 Sent To Z
Notes
2007-07-10 16:29:20TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 08:45 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 08:45 Sent To  
Notes
2007-05-10 09:18:48TO "COMM" BD#11/PLANS ON RACK/ 4 ROLLS AND PAPERWORK
2007-04-30 08:45:27WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-19 Cont ID  
Sent By lfranco Date 2007-03-27 Time 17:55 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 14:45 Sent To  
Notes
2007-03-19 14:46:21TO "COMM' BD#52/PLANS ON RACK--4 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 17:02 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 17:02 Sent To  
Notes
2007-02-02 09:43:29TO "COMM" BD#53
2007-01-24 17:02:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 12:55 Rev Time 0.00
Received By mawillia Date 2006-10-26 Time 15:22 Sent To  
Notes
2006-10-31 10:21:19TO "COMM" BD#54
2006-10-26 15:22:52WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2007-10-20 Time 20:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 09:53 Rev Time 0.45
Received By tgordon Date 2007-03-29 Time 09:53 Sent To  
Notes
2007-03-29 09:57:52** APPROVED FOR PERMIT**
  
 1) ADDITIONAL MECHANICAL PERMITS WILL BE REQUIRED FOR
 WALK-IN COOLER, HOOD, AND FIRE SUPPRESSION, PLANS TO BE
 SUBMITTED WITH APPLICATION WHEN APPLYING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-16 Cont ID  
Sent By tgordon Date 2007-02-16 Time 08:40 Rev Time 0.45
Received By tgordon Date 2007-02-16 Time 08:39 Sent To  
Notes
2007-02-16 09:11:43*FOR PLAN REVIEW ONLY, NOT FOR PERMIT*
 *** DENIED ***
 1) ONE SET OF THE ENERGY CALCULATIONS IS A PHOTO COPY,
 PLEASE SUBMIT TWO SIGNED AND SEALED SETS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) AS REQUESTED IN LAST REVIEW 10-31-06. PLEASE SUBMIT
 COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 4) PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 ROOF TOP CONDENSER UNIT STANDS, SEE FS 553.842 (1) AND
 FAC 9B-72.010 (31) (G).
 ** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) AS REQUESTED IN LAST REVIEW 10-31-06 NOTE #9. NEED
 DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT (WITH
 ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 FBC
 1609). RESPONSEWAS SEE DETAIL "C"/S4 WHICH SHOWS RTU
 NOT MAU IF DETAIL IS FOR BOTH UNITS, PLEASE STATE SO IN
 THE DETAIL.
  
 6) AS NOTED IN LAST REVIEW 10-31-06 NOTE #10. SEE PAGE
 A-140 SHOWS ROOF TOP AIR HANDLER, PLANS HAVE NOT BEEN
 CORRECTED TO SHOW THE MAKE UP AIR UNIT, AS RESPONSE
 STATES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 13:32 Rev Time 1.30
Received By tgordon Date 2006-10-31 Time 13:32 Sent To  
Notes
2006-10-31 14:21:32*FOR PLAN REVIEW ONLY, NOT FOR PERMIT*
 *** DENIED ***
 1) ENGINEERING FIRM'S CERTIFICATE OF AUTHORIZATION
 NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002.
  
 2) THE ENGINEER RICHARD JONES PRINTED NAME AND LICENSE
 NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.3.
  
 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 5) PLEASE SHOW OUTDOOD AIR CALCULATIONS ON MECHANICAL
 PLANS, PER 2004 FBC/M 403.2.
  
 6) PLEASE SHOW A/C SYSTEM'S SEER OR EER ON EQUIPMENT
 SCHEDULE.
  
 7) NEED DETAIL FOR HANGING KITCHEN HOOD TO ROOF
 STRUCTURE.
  
 8) NEED DETAIL FOR SECURING COOLER CONDENSER UNIT AND
 STAND, TO ROOF, TO WITHSTAND 140 MPH WINDS, PER 2004
 FBC 1609.
  
 9) NEED DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT
 (WITH ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004
 FBC 1609).
  
 10) SEE PAGE A-140 SHOWS ROOF TOP AIR HANDLER, MECH.
 PLANS DO NOT LIST A ROOF TOP AIR HANDLER, DO YOU MEAN
 THE MEKE UP AIR UNIT, PLEASE EXPLAIN OR CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-11-19 Cont ID  
Sent By jleech Date 2007-11-19 Time 14:48 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 14:48 Sent To  
Notes
2007-11-19 14:49:42REVIEWED AND APPROVED LAWN IRRIGATION PLAN SUBMITED
 WITH APPROVED BUILDING PLANS. OK

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-08-30 Cont ID  
Sent By mperson Date 2007-08-30 Time 10:29 Rev Time 0.00
Received By mperson Date 2007-08-30 Time 10:29 Sent To B
Notes
2007-08-30 10:36:51REVISION APPROVED: SHEET P100, PLAN NOTE ITEM #8
 REMOVED. SHEET P110, AS BUILT U/G SANITARY AND GREASE.
  
 ****************PROVISO****************
 PER FBC-2004 SECTION 604.9 WATER HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
 SPECIFICATIONS.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-03 Cont ID  
Sent By pschmitz Date 2007-08-03 Time 09:58 Rev Time 0.00
Received By pschmitz Date 2007-08-03 Time 09:58 Sent To PC
Notes
2007-08-03 10:01:19REVISION TO U/G HORIZONANTAL WASTE VENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-31 Cont ID  
Sent By pschmitz Date 2007-03-31 Time 08:56 Rev Time 0.00
Received By pschmitz Date 2007-03-31 Time 07:59 Sent To  
Notes
2007-03-31 10:09:20COULD HAVE EXPITEDPLANS MORE EFFICENTLY,IF LOCATION
 OF INFORMATION REQUESTED HAD BEEB ADDRESSED, AS
 REQUESTED IN PREVIIOUS NOTE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-17 Cont ID  
Sent By pschmitz Date 2007-02-17 Time 12:19 Rev Time 0.00
Received By pschmitz Date 2007-02-17 Time 07:54 Sent To  
Notes
2007-02-17 13:23:34PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED,2ND PLAN
 REVIEW
 EACH PREVIOUS COMMENT,WILL BE ADDRESSED,AS OK OR
 DENIED.
 NEW COMMENTS ADDRESSED SEPARATELY.
  
 1)OK
  
 2) DENIED, PROVIDE LOCATION OF WORK AND STAMPED SHTS
 FROM DBPR
 PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH FOR
 REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 3)DENIED, SEE ATTACHED RESPONSE FROM WPBUD,DATED
 12-26-06, 2-1250 GAL GREASE TANKS REQUIRED.
 SHT P 200, GREASE TRAP SIZE. TO BE CONFIRMED BY
 CONTACT W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR,
 LYNN MASSON
 OFFICE 561-822-2271E-MAIL [email protected]
  
 4)OK
  
 5) DENIED, SHT P-100 PLUMBING ISOMETRIC SHOWS PIPING
 OVER HEAD. WITH DOWN FEED PIPE.
 SHT P-100 DETAIL 7PLUMBING ISOMETRIC
 SEC 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ONTHE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 6)DENIED,SHT A-121, P-100; REFERENCES A DISHWASHER
 #48, THEREFORE QUICK OPENING VALE.
 SHT P100 SEC 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 7) DENIED, NEW COMMENT
 SHT CS LISTS L-1, L -2 , L-3 IRRIGATION, NOT WITH THIS
 SET OF PLANS.
 SHT P- 100, 110 PLAN NOTES #1, #9 REFERENCE TO TO SITE
 UTILITY PLANS.
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 8) OK
  
 END OF COMMENTS, QUESTIONS; 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-16 Cont ID  
Sent By pschmitz Date 2006-12-16 Time 10:07 Rev Time 0.00
Received By pschmitz Date 2006-12-16 Time 06:07 Sent To  
Notes
2006-12-16 07:12:33PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED,PROJECT, PLAN REVIEW ONLY.
  
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)
 PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH FOR
 REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 3) SHT P 200, GREASE TRAP SIZE. TO BE CONFIRMED BY
 CONTACT W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
  
 OFFICE 561-822-2271E-MAIL [email protected]
  
 4)SHT A-000 NUMBER OF REQUIRED PLUMBING FIXTURES
 403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 403.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 403.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL.
 THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 403.5 LOCATION OF EMPLOYEE TOILET FACILITIES IN
 MERCANTILE AND ASSEMBLY OCCUPANCIES.
 EMPLOYEES SHALL BE PROVIDED WITH TOILET FACILITIES IN
 BUILDING AND TENANT SPACES UTILIZED AS RESTAURANTS,
 NIGHTCLUBS, PLACES OF PUBLIC ASSEMBLY AND MERCANTILE
 OCCUPANCIES. THE EMPLOYEE FACILITIES SHALL BE EITHER
 SEPARATE FACILITIES OR COMBINED EMPLOYEE AND PUBLIC
 FACILITIES. THE REQUIRED TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE
 EMPLOYEES? WORK AREA AND THE PATH OF TRAVEL TO SUCH
 FACILITIES, IN OTHER THAN COVERED MALLS, SHALL NOT
 EXCEED A DISTANCE OF 500 FEET (152 M). THE PATH OF
 TRAVEL TO REQUIRED FACILITIES IN COVERED MALLS SHALL
 NOT EXCEED A DISTANCE OF 300 FEET (91 M).
  
 403.1.1 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 ?553.86, FLORIDA STATUTES.
  
 5) SHT P-100 DETAIL 7PLUMBING ISOMETRIC
 SEC 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ONTHE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 6)SHT P100 SEC 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 7)SHT P- 100, 110 PLAN NOTES #1, #9 REFERENCE TO TO
 SITE UTILITY PLANS.
 SITE PLANS NOT INCLUDED.
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 END OF COMMENTS, QUESTIONS; 561-805-6692

Review Stop Z ZONING
Rev No 7 Status P Date 2007-11-02 Cont ID  
Sent By lfranco Date 2007-11-02 Time 12:25 Rev Time 0.00
Received By lfranco Date 2007-11-02 Time 12:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2007-10-26 Cont ID  
Sent By lfranco Date 2007-10-26 Time 15:07 Rev Time 0.00
Received By lfranco Date 2007-10-26 Time 14:52 Sent To  
Notes
2007-10-26 15:15:13PLANNING AND ZONING:***** PASSED WITH PROVISO ****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 PROVISO- PRIOR TO OBTAINING FINAL CO:A TEMPORY CO
 MAY BE OBTAINED IN THE MEANTIME ONLY.
  
 2.THE SITE PLAN, LANDSCAPE PLANS AND PERTINENT PLANS
 NEED TO BE REVISED TO REFLECT ADDED SIDEWALK/STAIR
 CONNECTIONS AS REFLECTED IN THIS PERMIT.SUBMIT PLANS
 TO THE PLANNING AND ZONING DEPARTMENT/CONSTRUCTION
 SERVICES ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL:[email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2007-07-16 Cont ID  
Sent By lfranco Date 2007-07-16 Time 16:28 Rev Time 0.00
Received By lfranco Date 2007-07-16 Time 16:28 Sent To I
Notes
2007-07-17 16:53:49PLANNING AND ZONING: **** PASSED WITH PROVISO****
  
 1.PROVIDE A COPY TO THE PLANNING AND ZONING DEPT. OF
 THE NEW ELEVATIONS, REFLECTING THE CHANGE OF THE
 MATERIALS FOR OUR FILE.PLEASE SEND IT TO MY
 ATTENTION.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONINGDEPARTMENT
 TEL:(561) 822-1443
 EMAIL:[email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-05-10 Cont ID  
Sent By lfranco Date 2007-05-10 Time 11:28 Rev Time 0.00
Received By lfranco Date 2007-05-10 Time 11:28 Sent To  
Notes
2007-05-10 11:32:38PLANNING AND ZONING:PASSED WITH PROVISO
  
 1.SURVEYS IN PACKET ARE NOT SIGNED AND SEALED.
 REVISE ACCORDINGLY, WHEN RE-SUBMITTING PACKET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 TEL:(561) 822-1443
  

Review Stop Z ZONING
Rev No 3 Status F Date 2007-03-27 Cont ID  
Sent By lfranco Date 2007-03-27 Time 17:55 Rev Time 0.00
Received By lfranco Date 2007-03-23 Time 10:54 Sent To I
Notes
2007-03-27 17:52:23PLANNING AND ZONING: **** FAILED ****
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. SHEET L-1 SHOWS PROPOSED PALM TREES (FLORIDA ROYAL
 PALMS) ON TOP OF THE PROPOSED FREESTANDING SIGN. REVISE
 LANDSCAPE PLAN OR SIGNAGE LOCATION TO ACCOMMODATE FOR
 BOTH.KEEP IN MIND TO COMPLY WITH SIGHT TRIANGLE
 CLEARANCE REQUIREMENTS.
  
 3. NOTE: A SIGNAGE PERMIT FOR THE FREESTANDING SIGN
 HAS BEEN SUBMITTED AND APPROVED (PERMIT NO. 07030246),
 BASED ON AN EMAIL BY TRACY KIRKLAND (INTERPLAN) SENT
 TODAY, 3-28-07, AT NOON, SHOWING THAT THE FREESTANDING
 SIGN WILL REMAIN IN PLACE, BUT THE LANDSCAPE PLAN,
 SHEET LP-1, WILL BE REVISED TO REFLECTTHE PALM TREES
 SHIFTED AND CLUSTERED AWAY FROM BEING ON TOP OF THE
 FREESTANDING SIGN.
  
 WHEN RE-SUBMITTING , PLEASE PROVIDE THREE (3) COPIES OF
 THE REVISEDLANDSCAPE PLAN LP-1 (2 FOR THE BUILDING
 DEPT. PACKET AND 1 FOR THE P& Z FILE) SIGNED AND SEALED
 ONCE THE BLDG. PERMIT IS RETURNED TO YOU, AFTER FULL
 REVIEW, WITH COMMENTS FROM CONSTRUCTION SERVICES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By lfranco Date 2007-02-23 Time 17:31 Rev Time 0.00
Received By lfranco Date 2007-02-23 Time 17:31 Sent To  
Notes
2007-02-23 17:34:36PLANNING AND ZONING:*** FAILED ***
  
 1.PLEASE PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2. THE SITE PLAN/DRAWINGS DO NOT MATCH THE APPROVED
 PLANS FROM THE PLANNING AND ZONING DEPARTMENT.REFER
 TO APPROVAL LETTER AND DRAWINGS.THEY HAVE BEEN MAILED
 TO INTERPLAN, THE AGENT FOR THE PROJECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 TEL: (561) 822-1443

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By lfranco Date 2006-11-16 Time 17:50 Rev Time 0.00
Received By lfranco Date 2006-11-16 Time 14:30 Sent To I
Notes
2006-11-16 18:02:46PLANNING AND ZONING ***** FAILED******
  
 1.THE SITE PLAN IS CURRENTLY UNDER REVIEW FOR AN
 INFORMAL SITE PLAN REVIEW.ONCE ALL OUTSTANDING
 COMMENTS ARE ADDRESSED, AN APPROVAL LETTER FROM THE
 PLANNING AND ZONING DEPARTMENT WILL BE ISSUED.
 PLEASE SUBMIT A COPY OF THE LETTER WITH PLANS WHEN
 SUBMITTING FOR BUILDING PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT THE NUMBER
 BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 CITY OF WEST PALM BEACH
 TEL: (561) 822-1435