Plan Review Details - Permit 06100955
Plan Review Stops For Permit 06100955
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-09 Cont ID  
Sent By alange Date 2006-11-09 Time 14:06 Rev Time 0.00
Received By alange Date 2006-11-09 Time 14:06 Sent To  
Notes
2006-11-09 14:09:33DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 2.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 3.SHOW SERVICE COUNTERS COMPLYING WITH FBC 11-7.2
 SHOW HEIGHT AND WIDTH COMPLYING WITH THIS SECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By dpalmer Date 2006-11-01 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 09:59 Sent To  
Notes
2006-11-01 14:26:06****** UNSAT ********
  
 1) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL/ENGINEER FIRM AS
 REQUIRED UNDER FAC 61G1-16.004, FAC 61G15-23.002, FS
 481.219, AND FS471.023.
 PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS FIRM ON
 SEVERAL OCCASIONS ON OTHER PROJECTS. AT THIS TIME ONE
 SET OF PLANS ARE BEING RETAINED FOR POSSIBLE REVIEW
 FROM THE STATE'S LEGAL COUNSEL TO THE FLORIDA BOARD OF
 ARCHITECT'S.
 PLEASE ADDRESS THIS COMMON AND OBTAIN THE CORRECT
 LICENSURE AS REQUIRED.
 PLEASE ALSO SEE OTHER INFORMATION REQUIRED ON THE SAME
 SAID TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S)>
  
 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE LISTED ON SAID PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND THE 2004
 FBC.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-101.1.3,
 13-415.1.ABC.1.1, .1.2 AND .1.3,
 PLEASE PROVIDE SCHEDULING FOR SYSTEM, PLEASE PROVIDE
 THE MAX TIMES FOR OVER RIDING DEVICES. (30MINS MAX ON
 OC SENSOR TYPE DEVICES, 4HRS MAX FOR TIME TYPE.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1, AND TABLES.
 ** PLEASE KNOW AT THIS TIME, A "SYSTEM" CAN NOT BE
 REVIEWED AS NONE WAS SHOWN OR SUBMITTED.
  
 4) NOTE: PLEASE SEE RISER WHICH SHOWS LINE AND LOAD IN
 THE SAME GUTTER.
 230.7 THIS IS NOT PERMITTED.
  
 5) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTORS ARE
 NOT PERMITTED BEFORE THE FIRST MEANS OF DISCONNECT.
 250.6,250.24B
  
 6) NOTE: PLEASE KNOW, THAT RISER NOTES A AND B ARE NOT
 ON RISER AT THIS TIME?
 NOT COMPLETE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 230.2, AN ADDITIONAL NEW SERVICE
 FROM FPL IS NOT GRANTED AT THIS TIME. PLEASE PROVIDE
 ALL INFORMATION AND DOCUMENTATION FOR REVIEW.
  
 8) NOTE: PLEASE SEE 250.66 FOR CORRECT SIZING OF THE
 GROUNDING ELECTRODE CONDUCTOR.
  
 9) NOTE: PLEASE SUBMIT AND SHOW COORDINATION WITH AIC
 RATINGS OF ALL EQUIPMENT AS SHOWN. THIS MAY CHANGED DUE
 TO POSSIBLE CHANGES IN SERVICE.
 110.9,240.12
  
 10) NOTE: PLEASE PROVIDE LOADS AND SHOW LOADS FOR TRACK
 LIGHTS PER 220.12B AND LOADS ON SHOW/DISPLAY WINDOWS
 PER 220.12A.
  
 11) NOTE: PLEASE SEE MINIMUM VA FOR SIGN CIRCUIT PER
 600.5, 220.3(B)(6).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-30 09:59:30REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 14:44 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 14:42 Sent To  
Notes
2006-11-20 15:16:41*****DENIED*****
  
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 3.INDICATE ON APPROPRIATE ELEVATION FRONT THE SUITE
 NUMBER FOR THIS TENANT SPACE.BE ADVISED THAT THE
 NUMBER IS TO BE VISIBLE BEFORE, DURING, AND AFTER
 CONSTRUCTION/DEMOLITION OPERATIONS.
  
 4.INTERIOR FINISH FOR WALLS AND CEILING SHALL BE
 CLASS "A" OR CLASS "B".
  
 5.IF THE FIRE SPRINKLER AND (OR) FIRE ALARM SYSTEM IS
 TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 6.IN REGARDS TO FIRE SPRINKLER COVERAGE, NFPA 13 -
 2002 EDITION - SHALL BE REFERENCED.(MAKE CHANGE ON
 SHEET P1.0, FIRE PROTECTION GENERAL NOTE B)
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 14:42 Rev Time 0.00
Received By mawillia Date 2006-10-25 Time 16:39 Sent To  
Notes
2006-11-02 09:28:39TO "BOB"#2
2006-10-25 16:40:26WAITING FOR "BOB"--OK TO ROUTE TO "BOB" PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By tgordon Date 2006-11-02 Time 10:37 Rev Time 0.45
Received By tgordon Date 2006-11-02 Time 10:37 Sent To  
Notes
2006-11-02 11:06:38*** DENIED ***
 1) THE ARCHITECT FIRM'S LICENSE NUMBER MUST ALSO APPEAR
 IN THE TITLE BLOCK, PER FAC 61G-16.004.
  
 2) THE ENGINEER"S NAME, ADDRESS, AND LICENSE NUMBER
 MUST APPEAR IN THE TITLE BLOCK, PER FAC 61G15-23.002.
  
 3) IT APPEARS THAT THE SPACE ABOVE THE CEILING IS AN
 OPEN RETURN AIR PLENUM, AS THEIR IS NO RETURN AIR DUCT
 WORK SHOWING, IF SO PLEASE NOTE ON PLANS,MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84. PER 2004 FBC/M 602.2.1.
 IF NOT PLEASE CORRECT.
  
 4) SEE PLANS PAGE M1.0, CODES, PLEASE REFER TO THE 2004
 FBC.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-16 Cont ID  
Sent By kstevens Date 2006-11-16 Time 14:24 Rev Time 0.00
Received By kstevens Date 2006-11-16 Time 14:24 Sent To  
Notes
2006-11-16 14:56:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE FOLLOWING INFORMATION
 IS REQUIRED: THE CERTIFICATE OF AUTHORIZATION,
 (BUSINESS NUMBER), AND THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055. (SEE ATTACHED SHEET FROM DBPR
 WEBSITE). (ALSO SEE ELECTRICAL REVIEW ON THE SUBJECT).
  
 2. ALL PME SHEETS. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE UMBER ON EACH SHEET,
 AND IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL, AS WELL, INDICATE THE NAME
 ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025.
  
 3. SHT P1.0 MISC. PLUMBING FIXTURES. THE REVERSE
 OSMOSIS FILTER SHALL BE NSF-58, OR WQAS S-300
 COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATIONS
 INDICATING COMPLIANCE. SECTION 611.2.
  
 4. SHT P2.0 SUPPLY PIPING WATER SYSTEM. A BACKFLOW
 PREVENTER IS REQUIRED ON THE ICE MACHINE AS WELL AS A
 WATER HAMMER ARRESTOR. SECTIONS 608.3 & 604.9.-A
 WATER HAMMER ARRESTOR IS REQUIRED ON THE DISHWASHER.
 SECTION 604.9.-FULL OPEN VALVES ARE REQUIRED ON ALL
 WATER DOWN-FEED PIPES. SECTION 606.1(4).
  
 5. SHT P2.0 KEYED PLAN NOTES 16 & 19 WERE NOT LOCATED
 ON THE PLUMBING SUPPLY PLAN. PLEASE CLARIFY. SECTION
 106.1.1.-NOTE 23 IS SHOWN TWICE ON THE FLOOR PLAN.
 THIS IS NOT REFLECTED IN THE RISER DIAGRAM. PLEASE
 CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1.-NOTE
 28 RPZV BACKFLOW REQUIRED. MAXIMUM 4' ABOVE THE FLOOR
 FOR TESTING & CERTIFICATION. SHOW ON PLAN. SECTION
 106.1.1.
  
 6. SHT P3.0 WASTE VENT RISER DIAGRAM. SUBMIT THE RISER
 DIAGRAM IN AN ISOMETRIC FORM THAT REFLECT THE FLOOR
 PLAN. SECTION 106.1.3.-A TRAP IS REQUIRED FOR THE
 FLOOR DRAIN. SECTION 1002.1.-A 4" AIR GAP IS
 REQUIRED FOR THE 3 COMPARTMENT SINK, AND A 2-1/2" AIR
 GAP IS REQUIRED FOR THE DISHWASHER. SECTION 80.2.1.
  
 7. SHT P3.0 PLAN KEY NOTE 14 & THE PLUMBING WASTE/DRAIN
 PLAN RISER DIAGRAM. THE GREASE TRAP IS NOT APPROVED IN
 THE SPACE. ALL GREASE TRAPS ARE TO BE SIZED BY THE
 UTILITY DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER BY PHONE
 (561) 822-2271, BY FAX (561) 822-2279, OR E-MAIL
 [email protected]. UTILITY ORD. 3434.
  
 8. SHT P4.0 DETAIL 5. DIELECTRIC UNIONS ARE NOT
 APPROVED FOR THE POTABLE WATER SYSTEM. USE A DIELECTRIC
 NIPPLE OR DIELECTRIC COUPLING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved