 |
Plan Review Details - Permit 06100955
| Plan Review Stops For Permit 06100955 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-09 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-09 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-11-09 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2006-11-09 14:09:33 | DENIED | | | | | | | | | 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION | | | | | | 2.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR | | | A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS | | | WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC | | | EXISTING BUILDING 301.5 | | | | | | 3.SHOW SERVICE COUNTERS COMPLYING WITH FBC 11-7.2 | | | SHOW HEIGHT AND WIDTH COMPLYING WITH THIS SECTION. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE | | | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-01 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-30 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2006-11-01 14:26:06 | ****** UNSAT ******** | | | | | | 1) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON | | | TITLE BLOCKS FOR ARCHITECTURAL/ENGINEER FIRM AS | | | REQUIRED UNDER FAC 61G1-16.004, FAC 61G15-23.002, FS | | | 481.219, AND FS471.023. | | | PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS FIRM ON | | | SEVERAL OCCASIONS ON OTHER PROJECTS. AT THIS TIME ONE | | | SET OF PLANS ARE BEING RETAINED FOR POSSIBLE REVIEW | | | FROM THE STATE'S LEGAL COUNSEL TO THE FLORIDA BOARD OF | | | ARCHITECT'S. | | | PLEASE ADDRESS THIS COMMON AND OBTAIN THE CORRECT | | | LICENSURE AS REQUIRED. | | | PLEASE ALSO SEE OTHER INFORMATION REQUIRED ON THE SAME | | | SAID TITLE BLOCKS. | | | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS | | | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S)> | | | | | | 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT | | | CODES ARE LISTED ON SAID PLANS. | | | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND THE 2004 | | | FBC. | | | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-101.1.3, | | | 13-415.1.ABC.1.1, .1.2 AND .1.3, | | | PLEASE PROVIDE SCHEDULING FOR SYSTEM, PLEASE PROVIDE | | | THE MAX TIMES FOR OVER RIDING DEVICES. (30MINS MAX ON | | | OC SENSOR TYPE DEVICES, 4HRS MAX FOR TIME TYPE. | | | PLEASE SEE 13-415.2, 13-415.2.ABC.1, AND TABLES. | | | ** PLEASE KNOW AT THIS TIME, A "SYSTEM" CAN NOT BE | | | REVIEWED AS NONE WAS SHOWN OR SUBMITTED. | | | | | | 4) NOTE: PLEASE SEE RISER WHICH SHOWS LINE AND LOAD IN | | | THE SAME GUTTER. | | | 230.7 THIS IS NOT PERMITTED. | | | | | | 5) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTORS ARE | | | NOT PERMITTED BEFORE THE FIRST MEANS OF DISCONNECT. | | | 250.6,250.24B | | | | | | 6) NOTE: PLEASE KNOW, THAT RISER NOTES A AND B ARE NOT | | | ON RISER AT THIS TIME? | | | NOT COMPLETE. | | | FBC 106.1.2 | | | | | | 7) NOTE: PLEASE SEE 230.2, AN ADDITIONAL NEW SERVICE | | | FROM FPL IS NOT GRANTED AT THIS TIME. PLEASE PROVIDE | | | ALL INFORMATION AND DOCUMENTATION FOR REVIEW. | | | | | | 8) NOTE: PLEASE SEE 250.66 FOR CORRECT SIZING OF THE | | | GROUNDING ELECTRODE CONDUCTOR. | | | | | | 9) NOTE: PLEASE SUBMIT AND SHOW COORDINATION WITH AIC | | | RATINGS OF ALL EQUIPMENT AS SHOWN. THIS MAY CHANGED DUE | | | TO POSSIBLE CHANGES IN SERVICE. | | | 110.9,240.12 | | | | | | 10) NOTE: PLEASE PROVIDE LOADS AND SHOW LOADS FOR TRACK | | | LIGHTS PER 220.12B AND LOADS ON SHOW/DISPLAY WINDOWS | | | PER 220.12A. | | | | | | 11) NOTE: PLEASE SEE MINIMUM VA FOR SIGN CIRCUIT PER | | | 600.5, 220.3(B)(6). | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2006-10-30 09:59:30 | REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-11-20 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-11-20 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2006-11-20 15:16:41 | *****DENIED***** | | | | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF. | | | | | | 3.INDICATE ON APPROPRIATE ELEVATION FRONT THE SUITE | | | NUMBER FOR THIS TENANT SPACE.BE ADVISED THAT THE | | | NUMBER IS TO BE VISIBLE BEFORE, DURING, AND AFTER | | | CONSTRUCTION/DEMOLITION OPERATIONS. | | | | | | 4.INTERIOR FINISH FOR WALLS AND CEILING SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 5.IF THE FIRE SPRINKLER AND (OR) FIRE ALARM SYSTEM IS | | | TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS | | | AND PERMIT ARE REQUIRED. | | | | | | 6.IN REGARDS TO FIRE SPRINKLER COVERAGE, NFPA 13 - | | | 2002 EDITION - SHALL BE REFERENCED.(MAKE CHANGE ON | | | SHEET P1.0, FIRE PROTECTION GENERAL NOTE B) | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-11-20 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-25 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2006-11-02 09:28:39 | TO "BOB"#2 | | 2006-10-25 16:40:26 | WAITING FOR "BOB"--OK TO ROUTE TO "BOB" PER "RBROWN" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-02 |
Time |
10:37 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-11-02 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2006-11-02 11:06:38 | *** DENIED *** | | | 1) THE ARCHITECT FIRM'S LICENSE NUMBER MUST ALSO APPEAR | | | IN THE TITLE BLOCK, PER FAC 61G-16.004. | | | | | | 2) THE ENGINEER"S NAME, ADDRESS, AND LICENSE NUMBER | | | MUST APPEAR IN THE TITLE BLOCK, PER FAC 61G15-23.002. | | | | | | 3) IT APPEARS THAT THE SPACE ABOVE THE CEILING IS AN | | | OPEN RETURN AIR PLENUM, AS THEIR IS NO RETURN AIR DUCT | | | WORK SHOWING, IF SO PLEASE NOTE ON PLANS,MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL | | | HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED | | | IN ACCORDANCE WITH ASTM E 84. PER 2004 FBC/M 602.2.1. | | | IF NOT PLEASE CORRECT. | | | | | | 4) SEE PLANS PAGE M1.0, CODES, PLEASE REFER TO THE 2004 | | | FBC. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-16 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-16 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2006-11-16 14:56:16 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | MUNICIPAL CODE | | | | | | 1. ALL ARCHITECTURAL SHEETS. THE FOLLOWING INFORMATION | | | IS REQUIRED: THE CERTIFICATE OF AUTHORIZATION, | | | (BUSINESS NUMBER), AND THE PRINTED NAME OF THE PERSON | | | SEALING THE DOCUMENT. FAC 61G1-16.004(2)(6) & FS | | | 481.219, 481.2055. (SEE ATTACHED SHEET FROM DBPR | | | WEBSITE). (ALSO SEE ELECTRICAL REVIEW ON THE SUBJECT). | | | | | | 2. ALL PME SHEETS. ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE UMBER ON EACH SHEET, | | | AND IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL, AS WELL, INDICATE THE NAME | | | ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) | | | & FS 471.025. | | | | | | 3. SHT P1.0 MISC. PLUMBING FIXTURES. THE REVERSE | | | OSMOSIS FILTER SHALL BE NSF-58, OR WQAS S-300 | | | COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATIONS | | | INDICATING COMPLIANCE. SECTION 611.2. | | | | | | 4. SHT P2.0 SUPPLY PIPING WATER SYSTEM. A BACKFLOW | | | PREVENTER IS REQUIRED ON THE ICE MACHINE AS WELL AS A | | | WATER HAMMER ARRESTOR. SECTIONS 608.3 & 604.9.-A | | | WATER HAMMER ARRESTOR IS REQUIRED ON THE DISHWASHER. | | | SECTION 604.9.-FULL OPEN VALVES ARE REQUIRED ON ALL | | | WATER DOWN-FEED PIPES. SECTION 606.1(4). | | | | | | 5. SHT P2.0 KEYED PLAN NOTES 16 & 19 WERE NOT LOCATED | | | ON THE PLUMBING SUPPLY PLAN. PLEASE CLARIFY. SECTION | | | 106.1.1.-NOTE 23 IS SHOWN TWICE ON THE FLOOR PLAN. | | | THIS IS NOT REFLECTED IN THE RISER DIAGRAM. PLEASE | | | CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1.-NOTE | | | 28 RPZV BACKFLOW REQUIRED. MAXIMUM 4' ABOVE THE FLOOR | | | FOR TESTING & CERTIFICATION. SHOW ON PLAN. SECTION | | | 106.1.1. | | | | | | 6. SHT P3.0 WASTE VENT RISER DIAGRAM. SUBMIT THE RISER | | | DIAGRAM IN AN ISOMETRIC FORM THAT REFLECT THE FLOOR | | | PLAN. SECTION 106.1.3.-A TRAP IS REQUIRED FOR THE | | | FLOOR DRAIN. SECTION 1002.1.-A 4" AIR GAP IS | | | REQUIRED FOR THE 3 COMPARTMENT SINK, AND A 2-1/2" AIR | | | GAP IS REQUIRED FOR THE DISHWASHER. SECTION 80.2.1. | | | | | | 7. SHT P3.0 PLAN KEY NOTE 14 & THE PLUMBING WASTE/DRAIN | | | PLAN RISER DIAGRAM. THE GREASE TRAP IS NOT APPROVED IN | | | THE SPACE. ALL GREASE TRAPS ARE TO BE SIZED BY THE | | | UTILITY DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT | | | LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER BY PHONE | | | (561) 822-2271, BY FAX (561) 822-2279, OR E-MAIL | | | [email protected]. UTILITY ORD. 3434. | | | | | | 8. SHT P4.0 DETAIL 5. DIELECTRIC UNIONS ARE NOT | | | APPROVED FOR THE POTABLE WATER SYSTEM. USE A DIELECTRIC | | | NIPPLE OR DIELECTRIC COUPLING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |