Plan Review Details - Permit 06100953
Plan Review Stops For Permit 06100953
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By alange Date 2006-10-31 Time 08:13 Rev Time 0.00
Received By alange Date 2006-10-31 Time 08:13 Sent To  
Notes
2006-10-31 08:17:10DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $477,533.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.PLEASE DO NOT ATTACH PRODUCT APPROVALS TO PLANS.
  
 5.PRODUCT APPROVALS REQUIRED FOR LINTELS.
  
 6.INCORRECT STATE PRODUCT APROVAL PAGES SUBMITTED FOR
 TOWN AND COUNTRY, PGT EXTERIOR DOOR AND FIXED WINDOW.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 09:56 Sent To Z
Notes
2006-10-27 10:36:55 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE 2002 NFPA-72 FOR SMOKE DEVICES AND
 PLACEMENT. PLEASE KNOW AS AN OFFICAL INTERPRETATION HAS
 COME FROM NFPA, IF INDEED THE SMOKE DEVICE SHOWN ARE
 DETECTION AND ALRAM DEVICES, THESE SHOULD BE SHOWN AS
 "SA". PLEASE SEE DEFINITIONS IN NFPA-72AS "SD" ARE ONLY
 DETECTION DEVICES AND WUOLD BE PRAT OF AFIRE ALARM
 SYSTEM. THIS IS A CHANGE OF THEPREVIOUS ACCEPTANCE OF
 "SD".
 PLEASE ALSO SEE LOCATION OF A "SA" REQUIRED IN THE
 STUDY ROOM AS THIS WILL BE CONSIDERED AN ADAPTABLE
 SLEEPING ROOM.
 PLEASE SEE SOME LOCATIONS OF THE "SA" DEVICES ARE
 REQUIRED TO BE MOVED TO BE INSTALLED WITHIN 12" OF THE
 HIGHEST POINT IN ANY ROOM FLAT CIELING ETC. PLEASE SEE
 11.8.3.
  
 2) NOTE: PLEASE SEE 310.15B6, 310.16 AS THE MINIMUM
 SIZE FOR THE SEC'S SHALL BE BASED ON THE 300A SERVICE
 AS SHOWN.
 PLEASE CONDUCTORS AS SHONW ARE NOT LARGE ENOUGH.
  
 3) NOTE: PLEASE INDICATE THE SPECIFIC ROOM AND AREAS
 WHIHC THE BRNACH CIRCUIT SFEED. EXAMPLE: BEDRM#2
 LTS/RECETPS, MASTER BDRM RECETPS. BATH #4 , KIT LTS
 ETC.
 310.16,240.4,408.4.
 IT IS KNOWN TO THIS OFFICE DURING CONSTRUCTION THESE
 WILL CHANGE, HOWEVER MIN SHOULD BE INIDCATED AT THIS
 TIME.
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND AND CORRELATE WITH LOAD CALCULATIONS.
  
 5) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE
 RECEPTS PER 210.52C1
  
 6) NOTE: PLEASE SEE NOTE #5 PER 210.8A6 AS ALL COUNTER
 SPACE RECEPTS IN KITCHEN(S) SHALL BE INDICATED AS GFI.
  
 7) NOTE: PLEASE SEE CONFLICT ON PLANS FOR MIN AIC
 RATINGS. SHOWS 10K AND 22K. PLEASE VERIFY DISTANCE FROM
 TEH FPL TRANSFORMER AS IT IS KNOWN TO THIS OFFICE THAT
 MANY OF THE OLDER TRANSFORMERS FROM FPL ARE OR HAVE
 BEEN GETTING CHANGED OUT WHICH WILL GIVE A HIGHER
 AVAILABLE FAULT CURRENT AT THE SERVICE. PLEASE VERIFY
 AS MOST OF THE MAINS ARE RATED AT 22K. 110.9. PLEASE
 SEE 240.12 FOR SLECTIVE COORDINATION.
  
 ** PLEASE SEE THERE ARE SOME AREAS ON ELECTRICLA PLANS
 AND PLANS WHICH REFERENCE "PALM BEACH COUNTY"
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-31 Cont ID  
Sent By alange Date 2006-10-31 Time 08:17 Rev Time 0.00
Received By alange Date 2006-10-26 Time 16:01 Sent To  
Notes
2006-10-26 16:01:57TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By tgordon Date 2006-10-27 Time 11:32 Rev Time 0.35
Received By tgordon Date 2006-10-27 Time 11:32 Sent To Z
Notes
2006-10-27 11:38:09*** DENIED ***
 1) SEE COMBUSTION AIR FOR GAS DRYER = 18 SQ. IN., WOULD
 REQUIRE A 5" ROUND DUCT, PLEASE CORRECT.
  
 2) RETURN AIR TRANSFER GRILL TH BEDROOM #3 NEEDS TO BE
 75 SQ. IN., SEE NOTE #3 (B).
  
 3) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By jleech Date 2006-10-30 Time 07:47 Rev Time 0.00
Received By jleech Date 2006-10-30 Time 07:47 Sent To B
Notes
2006-10-30 07:55:121. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3",
 FIXTURE DRAIN AND TRAP CAN BE 2"SEC. 406.3.
 2. HORIZONTAL DRY VENTS ARE NOT PERMITED IN DRAINAGE
 SYSTEM. SECTION 905.3. (SECOND FLOOR BATHROOM)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By mmclean Date 2006-10-28 Time 09:32 Rev Time 0.00
Received By mmclean Date 2006-10-28 Time 09:32 Sent To P
Notes
2006-10-28 09:43:28DENIED,
 1. PLEASE PROVIDE THE DIMENSION OF PROPOSED DRIVEWAY
 (LENGTH & WIDTH).
  
 MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR WALL/GATE WITH
 UTILITY EASEMENT APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
 NOTE: MUST PROVIDE A WALL DETAIL WHEN SUBMITTED FOR
 SEPARATE PERMIT FOR WALL.
 NOTE:THE PROPOSED A/C UNIT SHALL NOT BE CLOSER THAN
 1.20FT FROM SIDE PROPERTY LINE AND MUST BE SCREENED BY
 A LANDSCAPE BUFFER.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved