Plan Review Details - Permit 06100943
Plan Review Stops For Permit 06100943
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By btrobaug Date 2006-11-02 Time 10:56 Rev Time 0.33
Received By btrobaug Date 2006-11-02 Time 10:19 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-30 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 08:23 Rev Time 0.33
Received By btrobaug Date 2006-10-30 Time 07:48 Sent To I
Notes
2006-10-30 08:23:17 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 2} THE SERVICE ENTRANCE CONDUCTORS MUST COMPLY WITH
 310.15(B)(6) OR 310.16. MINIMUM 2/0 FOR 200 AMPS.
  
 3 } THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. MINIMUM #4 COPPER.
  
 4} ALL CODES REFERENCED ON THE PLANS ARE INCORRECT. THE
 CURRENT BUILDING CODE IS 2004, THERE IS NO MORE SBCCI
 CODES IN THE STATE OF FLORIDA. THE CURRENT NEC IS THE
 2002 EDITION . CORRECT ALL REFERENCES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 17:54 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 17:54 Sent To E
Notes
2006-11-01 17:54:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-30 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 08:23 Rev Time 0.00
Received By btrobaug Date 2006-10-26 Time 14:27 Sent To PC
Notes
2006-10-26 14:28:11TO "E" BOX