| 2007-01-08 11:29:05 | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS |
| | REQUIRED BY FBC RESIDENTIAL R807.1. |
| | |
| | 3) FBC R803.2.3.1 REQUIRES ROOF SHEATHING FASTENERS 4" |
| | O.C. IN ZONE 3, WHICH INCLUDES MORE THAN GABLE ENDS. |
| | PLEASE CORRECT NOTE ON A3. |
| | |
| | 4) TWO LAYERS OF UNDERLAYMENT ARE REQUIRED ON ROOF |
| | SLOPES LESS THAN 4:12 PER R905.2.7. PLEASE CORRECT NOTE |
| | ON A3. |
| | |
| | 5) SPECIFY 8D RING SHANK NAILS IN DETAIL 6/SD-1 AND |
| | 2/SD-1 AS REQUIRED BY R803.2.3.1. |
| | |
| | 6) ON SHEET SD-1 PLEASE UPDATE CODE REFERENCES TO THE |
| | 2004 FBC, ASCE7-02, ACI 318-02, ACI 402-02 AND ACI |
| | 630-02. SEE 2004 FBC AND REFERENCED STANDARDS. |
| | |
| | 7) THE ENERGY CALC. FORMS ARE REQUIRED TO BE SIGNED BY |
| | THE OWNER/AGENT PER FBC CHAPTER 13. |
| | |
| | 8) THE SOIL REPORT SPECIFIES AN ALLOWABLE BEARING |
| | PRESSURE OF 2000 PSF AND THE DESIGN ON S-1 REQUIRES A |
| | 2500 PSF SOIL BEARING CAPACITY. |
| | |
| | 9) THE TRUSS LAYOUT AND DRAWINGS ARE REQUIRED TO BE |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE |
| | ADDITION. |
| | |
| | 10) MOST OF THE UPLIFT VALUES SPECIFIED ON THE ROOF |
| | FRAMING PLAN ON S-1 ARE LESS THAN THOSE SHOWN THE TRUSS |
| | DRAWINGS, ALTHOUGH THE CAPACITIES OF THE SPECIFIED |
| | CONNECTORS ARE ADEQUATE. |
| | |
| | 11) PLEASE CLARIFY THE ATTACHMENT OF THE GIRDER TRUSSES |
| | AT THE ENTRY PORCH TO THE COLUMNS ON S-1. |
| | |
| | 12) ON S-1 AT THE REAR WALL OF THE PROPOSED FAMILY ROOM |
| | DETAIL 7/SD-1 IS SPECIFIED. THIS IS A NEW WALL AND |
| | IMBED CONNECTORS SHOULD BE SPECIFIED AT THIS LOCATION. |
| | |
| | 13) GIRDER M1G HAS AN "E" CONNECTOR SPECIFIED AT THE |
| | NEW EXTERIOR WALL, HOWEVER THERE IS NO "E" CONNECTOR |
| | SPECIFIED IN THE CONNECTOR SCHEDULE. |
| | |
| | 14)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE FRENCH DOOR AT |
| | REAR OF FAMILY ROOM. |
| | |
| | 16) THE PRODUCT APPROVAL NOA FOR THE IMPACT RATED |
| | SINGLE HUNG WINDOWS IS EXPIRED PLEASE SUBMIT THE NEW |
| | ONE (06-0406.08). |
| | |
| | 17) A PRODUCT APPROVAL FOR STORM SHUTTERS WAS |
| | SUBMITTED. PLEASE CLARIFY WHERE AND HOW THEY WILL BE |
| | INSTALLED. SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE |
| | INDICATE THE SPANS, FASTENERS, FASTENER SPACING, |
| | CONNECTION TYPE, EDGE DISTANCE, ETC. FOR EACH OPENING. |
| | THIS IS REQUIRED TO DETERMINE IF THE INSTALLATION WILL |
| | COMPLY WITH PRODUCT APPROVAL FOR THE PRESSURES AT THE |
| | OPENING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |