Plan Review Details - Permit 06100906
Plan Review Stops For Permit 06100906
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By rmcdouga Date 2007-01-08 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2007-01-08 Time 07:00 Sent To  
Notes
2007-01-08 11:29:05DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS
 REQUIRED BY FBC RESIDENTIAL R807.1.
  
 3) FBC R803.2.3.1 REQUIRES ROOF SHEATHING FASTENERS 4"
 O.C. IN ZONE 3, WHICH INCLUDES MORE THAN GABLE ENDS.
 PLEASE CORRECT NOTE ON A3.
  
 4) TWO LAYERS OF UNDERLAYMENT ARE REQUIRED ON ROOF
 SLOPES LESS THAN 4:12 PER R905.2.7. PLEASE CORRECT NOTE
 ON A3.
  
 5) SPECIFY 8D RING SHANK NAILS IN DETAIL 6/SD-1 AND
 2/SD-1 AS REQUIRED BY R803.2.3.1.
  
 6) ON SHEET SD-1 PLEASE UPDATE CODE REFERENCES TO THE
 2004 FBC, ASCE7-02, ACI 318-02, ACI 402-02 AND ACI
 630-02. SEE 2004 FBC AND REFERENCED STANDARDS.
  
 7) THE ENERGY CALC. FORMS ARE REQUIRED TO BE SIGNED BY
 THE OWNER/AGENT PER FBC CHAPTER 13.
  
 8) THE SOIL REPORT SPECIFIES AN ALLOWABLE BEARING
 PRESSURE OF 2000 PSF AND THE DESIGN ON S-1 REQUIRES A
 2500 PSF SOIL BEARING CAPACITY.
  
 9) THE TRUSS LAYOUT AND DRAWINGS ARE REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 ADDITION.
  
 10) MOST OF THE UPLIFT VALUES SPECIFIED ON THE ROOF
 FRAMING PLAN ON S-1 ARE LESS THAN THOSE SHOWN THE TRUSS
 DRAWINGS, ALTHOUGH THE CAPACITIES OF THE SPECIFIED
 CONNECTORS ARE ADEQUATE.
  
 11) PLEASE CLARIFY THE ATTACHMENT OF THE GIRDER TRUSSES
 AT THE ENTRY PORCH TO THE COLUMNS ON S-1.
  
 12) ON S-1 AT THE REAR WALL OF THE PROPOSED FAMILY ROOM
 DETAIL 7/SD-1 IS SPECIFIED. THIS IS A NEW WALL AND
 IMBED CONNECTORS SHOULD BE SPECIFIED AT THIS LOCATION.
  
 13) GIRDER M1G HAS AN "E" CONNECTOR SPECIFIED AT THE
 NEW EXTERIOR WALL, HOWEVER THERE IS NO "E" CONNECTOR
 SPECIFIED IN THE CONNECTOR SCHEDULE.
  
 14)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE FRENCH DOOR AT
 REAR OF FAMILY ROOM.
  
 16) THE PRODUCT APPROVAL NOA FOR THE IMPACT RATED
 SINGLE HUNG WINDOWS IS EXPIRED PLEASE SUBMIT THE NEW
 ONE (06-0406.08).
  
 17) A PRODUCT APPROVAL FOR STORM SHUTTERS WAS
 SUBMITTED. PLEASE CLARIFY WHERE AND HOW THEY WILL BE
 INSTALLED. SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE
 INDICATE THE SPANS, FASTENERS, FASTENER SPACING,
 CONNECTION TYPE, EDGE DISTANCE, ETC. FOR EACH OPENING.
 THIS IS REQUIRED TO DETERMINE IF THE INSTALLATION WILL
 COMPLY WITH PRODUCT APPROVAL FOR THE PRESSURES AT THE
 OPENING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-08 Cont ID  
Sent By btrobaug Date 2006-11-08 Time 12:40 Rev Time 0.75
Received By btrobaug Date 2006-11-08 Time 12:03 Sent To P
Notes
2006-11-08 12:40:18 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} PROVIDE LOAD CALCULATIONS PER 220 SECTION I,
 STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR
 220.SECTION III, OPTIONAL CALCULATIONS. THE TOTAL LOADS
 AFTER DEMAND APPEAR TO BE LARGER THAN THE SERVICE
 RATING.
  
 2}AN EGUIPMENT GROUND SIZEDPER 250.122 IS REQUIRED
 TO BE RAN WITH THE FEED FOR THE SUBPANEL. INDICATE SAME
 ON THE RISER.
  
 3}THE BATH CIRCUIT REQUIRED BY 210.11(C)(3), MUST
 APPEAR IN THE PANEL SCHEDULE.
  
 4}PLEASE INDICATE THE REQUIRED ARC FAULT CIRCUITS
 (210.12) IN THE PANEL SCHEDULE .
  
 5}A RECEPTACLE NEEDS TO BE ADDED TO THE PROPOSED
 BEDROOM FOR SPACING REQUIREMENTS OF 210.52(A)(1).
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 11:25 Sent To E
Notes
2006-11-07 11:25:59TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-08 Cont ID  
Sent By rmcdouga Date 2007-01-08 Time 14:19 Rev Time 0.00
Received By rmcdouga Date 2006-10-25 Time 19:57 Sent To  
Notes
2006-10-25 19:58:07TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By tgordon Date 2006-11-21 Time 08:33 Rev Time 0.30
Received By tgordon Date 2006-11-21 Time 08:33 Sent To B
Notes
2006-11-21 08:40:26*** DENIED ***
 1) THE MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER ADAM J. GINSBURG AS HIS NAME AND INFORMATION
 IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 .
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 14:30 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 14:30 Sent To M
Notes
2006-11-18 14:36:22DENIED;
 PAGE A-3 SANITARY RISER DIAGRAM;
 1.AUTOMATIC CLOTHES WASHER TO DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP SEE FBC-2004 PLUMBING
 SECTION 909.1.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3"
 SECTION 406.3.
 3.CLEANOUT REQUIRED ON WASHER VENT 48" ABOVE
 FINISH FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-04 Cont ID  
Sent By mmclean Date 2006-11-04 Time 07:19 Rev Time 0.00
Received By mmclean Date 2006-11-04 Time 07:19 Sent To I
Notes
2006-11-04 07:24:16DENIED,
 1. PLEASE SHOW ON THE TWO COPY OF SURVEYS THE DISTANCE
 OF THE PROPOSED ADDITION FROM THE EXISTING SHED.THE
 MINIMUM SETBACK MUST BE 6FT.
 2. PLEASE SHOW THE LOCATION OF THE A/C UNIT ON TWO
 COPIES OF SURVEYS.
 3. SITEPLAN SHOWS TWO WOOD SHED AND THE SURVEY SHOWS
 ONLY ONE SHED, PLEASE CLARIFY.
 4. SURVEY WILL BE USED AS THE DOCUMENT FOR REVIEW OF
 PROPOSED WORK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720