| 2006-11-14 10:48:24 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- CLARIFY INFORMATION GIVEN IN THE INSTALLATION |
| | SCHEDULE: |
| | A) NUMBER OF OPENINGS SHOWN ON APARTMENT LAYOUT |
| | DON'TMATCH NUMBER OF OPENINGS SHOWN ON THE |
| | INSTALLATION SCHEDULE. |
| | B) IS NOT CLEAR WHICH OPENING IS GOING TO BE USED |
| | FOR EMERGENCY ESCAPE AND HOW IS IT COMPLYING WITHSEC. |
| | R310.4 2004 RESIDENTIAL CODE. |
| | C) CLARIFY SIZE OF OPENING AND SIZE OF SHUTTER SPAN. |
| | SIZES SHOWN ON INSTALLATION SCHEDULE DON'T WORK. |
| | D) WHERE ARE THE DESIGN PRESSURES TAKEN FROM? . THEY |
| | DON'T REFLECT REAL DESIGN PRESSURES. SEE TABLE 1609.6B |
| | 2004 FBC 2004 OR TABLES IN ASCE 7-02. |
| | E) WHAT IS 1"BO INDICATED IN THE SHUTTERS MOUNTING |
| | AND CONNECTION TYPE COLUMN?. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | F) CLEARLY SPECIFY THE MINIMUM EDGE DISTANCE |
| | CONSIDERED FOR INSTALLATION. |
| | G) CLEARLY SPECIFY ANCHOR TYPE. THERE ARE SEVERAL |
| | TYPES OF TAPCONS WITH DIFFERENT DESIGN PRESSURES |
| | CAPACITY. |
| | H) CLEARLY SPECIFY SUBSTRATE TO BE ATTACHED TO: |
| | CONCRETE, CONCRETE BLOCK OR WOOD TO VERIFY COMPLIANCE |
| | WITH PROPOSED CONNECTOR INSTALLATION. |
| | I) STATEWIDE FLORIDA PRODUCT APPROVAL THAT |
| | CORRESPONDS TO SUBMITTED DRAWINGS IS FL2249(SEE |
| | ATTACHED COPY) NOT SSTD 12-99.REVISE AS REQUIRED. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |