Plan Review Details - Permit 06100865
Plan Review Stops For Permit 06100865
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 13:47 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 11:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By mjacobs Date 2006-11-22 Time 11:14 Rev Time 0.00
Received By mjacobs Date 2006-11-22 Time 08:10 Sent To PC
Notes
2006-11-22 11:14:20BUILDING PLAN REVIEW
 PERMIT:06100865
 ADD: 1200 S. FLAGLER DR. #1902
 CONT: CLASSIC WINDOW SYSTEMS
 TEL: (561)649-9961
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 2ND
 ACTION: DENIED
  
  
 1) SEE PREVIOUS NOTES #S 2 AND 4 WHICH WERE NOT
 ADDRESSED.THE INSTALLATION SCHEDULE SUBMITTED IS
 INCOMPLETE.SEE THE REQUIREMENTS FOR IMPACT PROTECTION
 IN THE PACKAGE. ON THE ENGINEERED SHEET, CIRCLE OR
 HI-LIGHT ALL NECESSARY INFORMATION PERTAINING TO THE
 PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By mjacobs Date 2006-11-02 Time 11:47 Rev Time 0.00
Received By mjacobs Date 2006-11-02 Time 10:55 Sent To PC
Notes
2006-11-02 11:46:58****CORRECTIONS****
 MYRON JACOBS BUILDING PLANS EXAMINER
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 _XX__ 1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 _XX__2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7-02, FBC1609.1.1. DOCUMENTSPREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 _XX__3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX__4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE REQUIRED INFORMATION IN A SIMILAR FORMAT.
  
 ____ 5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 _XX__6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB. PAGE 9-11 NEED TO BE
 COMPLETED. INDICATE THE FASTENER
 SPACING.
  
 _XX__7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.SUBMIT A COMPLETE FLOOR PLAN SHOWING
 THE ENERGENCY ESCAPE.BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 SCALE UPON
 SUBSTANTIAL PAPER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 15:34 Sent To B
Notes
2006-11-30 15:36:13TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 16:00 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 16:00 Sent To B
Notes
2006-11-20 16:01:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-11-02 Time   Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 17:16 Sent To  
Notes
2006-10-25 17:16:19TO "MISC' BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved