Plan Review Details - Permit 06100845
Plan Review Stops For Permit 06100845
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 14:14 Sent To P
Notes
2006-11-30 14:14:23TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-30 Cont ID  
Sent By mperson Date 2006-10-30 Time 13:17 Rev Time 0.00
Received By mperson Date 2006-10-25 Time 10:01 Sent To  
Notes
2006-10-30 14:17:04 
  
  
2006-10-25 10:01:40TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-07 Cont ID  
Sent By mperson Date 2006-12-07 Time 14:16 Rev Time 0.33
Received By mperson Date 2006-12-07 Time 14:16 Sent To PC
Notes
2006-12-07 14:21:21 
 **************PROVISO**************
 PER FBC-2004 CHAPTER 11, FIGURE 29, TOILET PAPER
 MINIMUM 19" NOT THE INDICATED 15".

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By mperson Date 2006-10-30 Time 13:16 Rev Time 1.25
Received By mperson Date 2006-10-30 Time 13:16 Sent To PC
Notes
2006-10-30 14:48:21UNSAT
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1
 ADMINISRTRATIVE, FBC-2004 CHAPTER 11 FLORIDA
 ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION.
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING PLAN
 REVIEW:
  
 1. ALL TOILET ROOMS SHALL BE ACCESSIBLE: SUBMIT A
 FLOOR PLAN DETAIL AND AN ELEVATION DETAIL SHOWING
 COMPLIANCE WITH FBC-2004 CHAPTER 11 FLORIDA
 ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION, SECTIONS
 11-4.16, 11-4.19 AND 11-4.22 AND ALL SUBSECTIONS.
  
 2. PER FBC-2004 PLUMBING, TABLE 403.1. A MINIMUM OF
 ONE (1) SERVICE SINK REQUIRED FOR THE BUILDING. WITH
 THE CONVERSION OF THE FIFTH AND SIXTH FLOOR MOP SINKS
 TO WATER CLOSETS. PLEASE SHOW THAT THEBUILDING IS IN
 COMPLIANCE.
  
 3. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3
 PLUMBING:
 (A) SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, AND TRAPS WITH SIZES FOR
 THE PROPOSED FIFTH AND SIXTH FLOOR STAFF BATHROOMS.
 (B) SUBMIT A WATER ISOMETRIC OF THE PROPOSED STAFF
 BATHROOMS WITH SIZES, SHUT OFF VALVES, WATER HAMMER
 ARRESTORS AND PLEASE INDICATE A POINT OF TIE INTO THE
 EXISTING POTABLE WATER SYSTEM WITH SIZING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND
 PROVIDE ONE COPY OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K. STEVENS
 (561) 805-6721