Plan Review Details - Permit 06100844
Plan Review Stops For Permit 06100844
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-07 Cont ID  
Sent By rnuquist Date 2007-01-07 Time 20:07 Rev Time 0.00
Received By rnuquist Date 2007-01-07 Time 19:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By alange Date 2006-11-01 Time 08:18 Rev Time 0.00
Received By alange Date 2006-11-01 Time 08:18 Sent To  
Notes
2006-11-01 08:39:58DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.HAND DRAWN CHANGES TO PLANS NOT PERMITTED.FBC
 106.1.3 WPB AMMENDMENTS.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $167,128.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.SEPERATE ROOFING PERMIT REQUIRED.
  
 5.PRODUCT APPROVALS REQUIRED FOR LINTELS.
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 7.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 06:47 Rev Time 0.50
Received By btrobaug Date 2007-06-04 Time 06:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-05-25 Cont ID  
Sent By btrobaug Date 2007-05-25 Time 13:00 Rev Time 0.50
Received By btrobaug Date 2007-05-25 Time 10:20 Sent To PC
Notes
2007-05-25 14:02:55 
  
 REVISION DENIED/INCOMPLETE INFORMATION.
  
 1} PLEASE CORRECT THE PANEL SCHEDULE. THE REQUIRED BATH
 CIRCUITS HAVE BEEN REMOVED, THERE IS NO DISHWASHER,
 DISPOSAL OR LIGHTING CIRCUITS SHOWN. SEE PERMITTED
 PLANS, USE THE SAME FORMAT.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). SEE MASTER BATH NEEDS ADDED
 RECEPTACLE.
  
 3} THE DEMAND CALCULATION FOR THEAHU @100%=3150 AND
 HTR@65%, IS INCORRECT. THE HEAT LOAD IS IN THE AHU, AND
 8000 WATTS IS NOT 65% OF ANY COMMON SYSTEM ON THE
 MARKRT. THE PERMITTED SET OF MECHANICAL PLANS INDICATE
 A 8000 WATT AHU. SEE NOTE #7 OF THE PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-05-16 Cont ID  
Sent By dpalmer Date 2007-05-16 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2007-05-16 Time 11:02 Sent To PC
Notes
2007-05-16 15:12:55** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE SEE THE ELECTRICAL PLANS AND RISER DIAGRAM
 HAS BEEN REVISED FROM PREVIOUS REVIEWED PLANS WHICH
 HAVE CREATED NEW COMMENTS.
  
 1) NOTE: PLEASE SEE PLANS ARE NOT INDICATING ANY
 REVISIONS BY CLOUDS/TRIANGLES OR DATES IN TITLE BLOCK.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE MISSING AIC RATING FOR NEW MAIN.
 110.9
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE THE RISER DIAGRAM IS NOW REVISED
 SHOWING NEW MAIN, YET PLANS STILL INDICATE NO MAIN
 DISCONNECT OUTSIDE?
 PLEASE ALSO SEE THE SERVICE WAS REVISED ON THE PREVIOUS
 PLANS AND RISER TO INDICATE A 200A SERVICE HOWEVER THE
 PANEL SCHEDULE NOW SHOWS PANEL AT 150AMPS??
 PLEASE REVISE TO SHOW LOCATION OF ALL SERVICE EQUIPMENT
 ON PLANS.
 110.26, FBC 106.1.2
  
 4) NOTE: PLEASE SEE 250.6, 250.24 AS THE RISER IS
 MISSING THE EQUIPMENT GROUNDING CONDUCTOR FROM MAIN TO
 THE PANEL.
 * EQUIPMENT GROUNDS ARE INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT*
  
 5) NOTE: PLEASE SEE PLANS ARE MISSING THE RECEPTACLE
 OUTLET FOR DISHWASHER. ONLY THE COUNTER SPACE
 RECEPTACLE REQUIRED PER 210.52C IS SHOWN.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE GFI WHICH IS BEING SHOWN
 DIRECTLY BEHIND THE SINK WHICH IS NOT PERMITTED. THIS
 WAS REDLINED ON PREVIOUS PLANS; HOWEVER IT IS STILL
 BEING SHOWN AT THE SAME LOCATION.
 210.52C
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT
 CORRELATE THE LOADS ON PANEL SCHEDULE WITH THAT OF THE
 LOAD ON LOAD CALCULATIONS FOR THE AHU/A/C SYSTEM.
 PLEASE SEE THE MECHANICAL PLANS ON FILE ALSO DO NOT
 COORDINATE WITH EITHER OF THESE TWO AS SHOWN.
 PLEASE COORDINATE AND REVISED.
 PLEASE SEE 220, 424.
 FBC106.1.2
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE FOR WALL SPACE
 IN BREAKFAST/KITCHEN/DINING AREA.
 250.10
  
 9) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOWS A NEW
 MICROWAVE CIRCUIT IN THE SPACE OF A SPARE AND PLANS DO
 NOT INDICATE CONDUCTORS, OCP, OR LOADS.
 PLEASE REVISED ALL AND CORRELATE.
 FBC 106.1.2
 310.16, 240.4, 408.4
  
 10) NOTE: PLEASE SEE PLANS DO CONTAIN A NOTE FOR WATER
 HEATER TO BE HARDWIRED HOWEVER THE PLANS STILL INDICATE
 A RECEPTACLE FOR THIS.
 PLEASE SEE 422.31, 422.30
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE MUST BE REVISED FOR
 ALL CIRCUITS TO BE SPECIFIC TO ALL ROOMS AND AREAS IN
 WHICH THEY FEED. THE USE OF *GENERAL LIGHTS* IS NOT
 PERMITTED PER 408.4.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-07 Cont ID  
Sent By dpalmer Date 2007-04-07 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2007-04-07 Time 15:20 Sent To PC
Notes
2007-04-07 15:31:10REDLINED PLANS*
 WATER HEATER TO BE HARDWRIED, DISCONNECT MAY BE IN
 PANEL.422.30
 GFI AT SINK TO BE RELOCATED PER 210.52C1, NOT TO BE
 BEHIND SINK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-03 Cont ID  
Sent By dpalmer Date 2006-12-03 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2006-12-03 Time 19:01 Sent To P
Notes
2006-12-03 19:21:01**** REDLINED PLANS*****
  
 PLANS INDICATE A 200A PANEL LOCATED ON GARAGE, HOWEVER
 RISER AND PANEL SCHEDULE SHOWS PANEL AS 150A W/ 150A
 MCB.
  
  
  
  
  
 ***** ONLY NOTED, THE TRUSS PLANS CONTAIN A
 "RUBBERSTAMP" FOR THE REQUIRED ORIGINAL SIGNATURE. SEE
 BUILDING REVIEW COMMENTS FOR THIS , ALONG WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 11:13 Sent To Z
Notes
2006-10-25 11:32:17**** UNSAT *****
  
 *** PLEASE KNOW, ONCE AN ADDRESS IS GRANTED AND GIVEN,
 THIS NEW ADDRESS SHALL BE STATED IN THE TITLE BLOCKS OF
 SAID PLANS.
 FAC 61G1-16.004
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS. 2002 NFPA-70(NEC), 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT ALL AIC RATINGS FOR NEW SERVICE
 EQUIPMENT. 110.9, 240.12
  
 3) NOTE; PLEASE SEE NFPA-72 DEFINITIONS AS IT HAS BEEN
 COMMON ACCEPTANCE THAT THE SMOKE ALARMS ARE SHOWN
 TYPICALLY AS SD'S WHICH IS ACTUALLY CONSIDERED SMOKE
 DEETCTORS WHICH ONLY DETECT SMOKE AND ARE PART OF A
 FIRE ALARM SYSTEM. PLEASE KNOW AS THE IS A SFR AND IT
 DOES NOT REQUIRE A FA SYSTEM,. PLEASE INDICATE THESE AS
 "SA"'S SMOKE ALARMS AS THESE ARE DEVICES THAT DETECT
 AND PROVIDE AN AUDIBLE SIGNAL AS REQUIRED. PLEASE SEE
 THIS HAS BEEN CONFIRMED WITH AN INTERPRETATION FROM
 NFPA- ON A RECENT CODE PANEL MEETING.
  
 4) NOTE: PLEASE SEE MISSING EGRESS LITHING CONTROL AND
 LT FIXTURE OF SOME SORT AT REAR OF DWELLING. 210.70,
 AND NFPA-101 7.8.
  
 5) NOTE: PLEASE INDICATE THE REQUIRED DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3. DOES NOT INDICATE
 BATH ON PANEL SCHEDULE. PLEASE KNOW THAT THE PANEL
 SCHEDULE SHALL BE SPECIFIC IN ORDER TO REVIEW FOR CODE
 COMPLIANCE.,
 408.4.310.16,240.4 TEC.
  
 6) NOTE: PLEASE SHOW LOAD CALCULATIONS PER NEC 220.31,
 METHOD CHOSEN IS UP TO DESIGNER, HOWEVER PLEASE SEE MIN
 VA/WATTS PER SQ FT ETC SHALL BE SHOWN.
  
 ** A A NOTE TO DESIGN PROFESSIONALS , PLEASE SEE FS
 481.229(1) FS 471.025
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 15:20 Sent To E
Notes
2007-06-01 15:21:27TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 10:13 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 10:13 Sent To E
Notes
2007-05-22 10:13:27TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 16:35 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 16:35 Sent To E
Notes
2007-05-14 16:36:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:06 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:06 Sent To P
Notes
2007-04-05 17:06:31TO JOHN LEECH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:05 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:05 Sent To E
Notes
2007-04-05 17:06:01TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:12 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:11 Sent To E
Notes
2006-11-29 17:12:36SENT TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 11:45 Sent To Z
Notes
2006-11-20 11:45:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-01 Cont ID  
Sent By alange Date 2006-11-01 Time 08:18 Rev Time 0.00
Received By alange Date 2006-10-25 Time 09:04 Sent To  
Notes
2006-10-25 09:04:14TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By tgordon Date 2006-10-26 Time 16:35 Rev Time 0.25
Received By tgordon Date 2006-10-26 Time 16:35 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-18 Cont ID  
Sent By jleech Date 2007-04-18 Time 14:20 Rev Time 0.00
Received By jleech Date 2007-04-18 Time 14:20 Sent To  
Notes
2007-04-18 14:21:00REVISED PLUMBING DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 13:27 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 13:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By mmclean Date 2006-10-26 Time 13:43 Rev Time 0.00
Received By jleech Date 2006-10-30 Time 07:04 Sent To B
Notes
2006-10-30 07:11:10DENIED;
 1. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 ONLY 2 BATHROOMS ON FLOOR PLAN.
 2. THE FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES WASHER IS
 2"THE BRANCH DRAIN SHALL BE 3"
 AND A CLEANOUT SHALL BE INSTALLED AT 48" AFF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-26 Cont ID  
Sent By mmclean Date 2006-11-25 Time 21:50 Rev Time 0.00
Received By mmclean Date 2006-11-25 Time 21:50 Sent To I
Notes
2006-11-26 21:52:34PROVISO: THE PROPOSED PAVER DRIVEWAY CAN ONLY BE SAND
 BASE IN ORDER TO MEET THE ZONING REQUIREMENTS FOR
 LANDSCAPE WITHIN THE FIRST 25FT FRONT SETBACK.
 DRIVEWAY NOT TO BE SEALED.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mmclean Date 2006-10-26 Time 13:17 Rev Time 0.00
Received By mmclean Date 2006-10-26 Time 13:17 Sent To P
Notes
2006-10-26 13:43:08DENIED,
 1. THE PROPOSED A/C UNIT MUST BE SHOWN ON TWO COPIES OF
 SURVEYS.
 2. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 DRIVEWAY & WALKWAY (LENGTH & WIDTH). CAN ONLY HAVE
 312.62SQ FT OF CONCRETE WITHIN THE FIRST 25FT FRONT
 SETBACK.
  
 MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720