Plan Review Details - Permit 06100782
| Plan Review Stops For Permit 06100782 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-04 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-04 |
Time |
13:12 |
Sent To |
PC |
|
| Notes |
| 2007-01-04 14:35:14 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB | | | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS | | | MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.PLEASE CALL 561-233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL | | | OF ALTERATION, FBC EB CHAPTER 3. | | | | | | 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | | OF RECORD, FBC*106.3.3. | | | | | | 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED | | | IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 6.)PRODUCT APPROVALS REQUIRED FOR THE EXTERIOR DOOR | | | (CABANA BATH) AND THE FIXED GLASS WINDOW. | | | | | | 7.)SHOW ATTIC ACCESS LOCATION FBC R807.1. | | | | | | 8.)SHOW VENTILATION IN COMPLIANCE WITH FBC R806. | | | | | | 9.)SMOKE DETECTORS REQUIRED FBC R313.1. | | | | | | 10.)SHOW DIMENSIONS FROM GRADE TO BOTTOM OF FOOTING | | | AND TOP OF SLAB. | | | | | | 11.)SHOW DRAINAGE FBC R401.3. | | | | | | 12.)A7, FOUNDATION NOTE 3, REFERS TO THE INCORRECT | | | ACI REFERENCE, FBC 35. | | | | | | 13.)A7, WOOD TRUSSES, NOTE REFERS TO INCORRECT | | | ANSI/TPI REFERENCE, FBC35. | | | | | | 14.)SHOW EMERGENCY EGRESS FOR PROPOSED NEW BEDROOMS, | | | FBC R310. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-08 |
Time |
10:39 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-11-08 |
Time |
06:34 |
Sent To |
P |
|
| Notes |
| 2006-11-08 10:37:44 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | 2} SUBMIT PANEL SCHEDULES PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. ALL PANELS SO CALCULATIONS CAN BE | | | REVIEWED, AND BRANCH CIRCUIT AND OVERCURRENT PROTECTION | | | REQUIREMENT MAY BE REVIEWED FOR COMPLIANCE. | | | | | | 3}PROVIDE LOAD CALCULATIONS PER 220 SECTION I, | | | STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR | | | 220.SECTION III, OPTIONAL CALCULATIONS. IT WOULD APPEAR | | | THE LOAD AFTER DEMAND IS GREATER THAN THE SERVICE | | | PROVIDED. | | | | | | 4} GFI,S ARE REQUIRED FOR BATH RECEPTACLES PER | | | 210.8(A)(1), 2002 NEC. INDICATE ON PLANS. | | | | | | 5} BATHROOM RECEPTACLES (AT LEAST ONE) MUST BE WITHIN | | | 3' OF THE BASIN PER 210.52, SEE MASTER BATH. | | | | | | 6} THE MASTER AND GUEST BEDROOM NEED ADDED RECEPTACLES | | | TO COMPLY WITH 210.52(A)(1) &( 2), SEE REVIEWED SET FOR | | | EXAMPLE. | | | | | | 7} THE HALLWAY MUST HAVE ONE RECEPTACLE TO COMPLY WITH | | | 210.52(H). | | | | | | 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-07 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-07 |
Time |
14:58 |
Sent To |
E |
|
| Notes |
| 2006-11-07 14:59:25 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-01-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-04 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-10-24 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2006-10-24 17:33:14 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-21 |
Time |
08:00 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-11-21 |
Time |
07:59 |
Sent To |
B |
|
| Notes |
| 2006-11-21 08:11:12 | *** DENIED *** | | | 1) NEED SIZE OF RETURN AIR TRUNK LINE TO AHU. | | | | | | 2) PROVIDE COMBUSTION AIR FOR GAS WATER HEATER IN | | | CLOSET, PER 2004 FBC/R M1701.1. | | | | | | 3) OPEN GRILL IN COVERED PATIO WILL NEED AN APPROVED | | | EXHAUST HOOD, PER 2004 FBC/M 505.3. | | | | | | 4) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | HOOD. | | | | | | 5) SEECOPRE LINE SIZES ON MECHANICAL PLANS 3/8 AND | | | 1/8, DO YOU MEAN 1 1/8 ? PLEASE PLEASE CORRECT IN TWO | | | PLACES SHOWING COPPER LINE SIZES OR SUBMIT | | | MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-17 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-17 |
Time |
15:04 |
Sent To |
M |
|
| Notes |
| 2006-11-17 15:06:58 | THE PERSON TAKING RESPONABILITY FOR DRAWINGS IS | | | REQUIRED TO PRINT AND SIGN THEIR NAME TO SAID | | | DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-11-03 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-03 |
Time |
18:12 |
Sent To |
M |
|
| Notes |
| 2006-11-03 18:28:23 | DENIED, | | | 1. THE SITEPLANS DOES NOT PROVIDE ANY SETBACKS THAT IS | | | MATCHING TO THE EXISTING SURVEY & THE PROPOSED | | | ADDITION. | | | 2. PLEASE NOTE IF THE WOOD DECK HAS AN EXISTING ROOF. | | | IF DECK HAS ROOF, THE ADDITION MUST BE 6FT FROM | | | STRUCTURE (BUILDING SEPARATION). | | | 3. THE SITEPLANS SHOW THE LOCATION OF A/C UNIT, BUT THE | | | SURVEY DOES NOT, PLEASE MARK ON THE TWO COPY OF | | | SURVEYS. | | | 4. PLEASE USE TWO COPIES OF SURVEYS TO SHOW THE | | | PROPOSED WORK WITH SETBACKS (LEGAL DOCUMENT). | | | 5. A SEPERATE PERMIT IS NEEDED FOR THE GENERATOR AND | | | CAN ONLY ENCROACH 4FT INTO REQUIRED SETBACK | | | (GENERATOR/SLAB MUST BE 9.44FT FROM THE REAR PROPERTY | | | LINE. | | | 6. PLEASE IDENTIFY THE ROOMS THAT THE PROPOSED ADDITION | | | WILL HAVE INTERIOR ACCESS. ADDITION MUST HAVE INTERIOR | | | ACCESS FROM THE EXISTING STRUCTURE. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
|