| Plan Review Stops For Permit 06100770 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-26 |
Time |
13:12 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-10-26 |
Time |
13:12 |
Sent To |
PC |
|
| Notes |
| 2006-10-26 13:55:37 | | | | | | | ******PROVISO****** | | | A) FBC-2004 FUEL GAS SEC. 404.12 OUTLET | | | CLOSURES: GAS OUTLETS THAT DO NOT CON- | | | NECT TO APPLIANCES SHALL BE CAPPED GAS | | | TIGHT. | | | | | | B) FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | | GEN/RES PERMIT REQUIRED WITH ZONING, ELECTRICAL, AND | | | GAS APPROVAL OF GENERATOR PLACEMENT. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 9,000 CUBIC FEET REQUIRED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-26 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-10-24 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2006-10-24 17:34:14 | TO "G" BOX |
|
|
|