Plan Review Details - Permit 06100752
Plan Review Stops For Permit 06100752
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-20 Cont ID  
Sent By alange Date 2006-11-20 Time 09:04 Rev Time 0.00
Received By alange Date 2006-11-20 Time 09:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By alange Date 2006-11-02 Time 08:17 Rev Time 0.00
Received By alange Date 2006-11-02 Time 08:17 Sent To  
Notes
2006-11-02 08:24:14DENIED
  
 1.FBC 3105.4.1 AND FBC 3105.4.2.1DESIGN OF THE
 FRAMING MEMBERS SHALL NOT BE BASED ON REMOVAL OR
 REPOSITIONING OF PARTS, OR THE WHOLE, DURING PERIODS OF
 75 MPH WIND VELOCITY.
 EITHER DESIGN IT WITH COVERING ATTACHED OR SHOW HOW THE
 COVERING WILL BE QUICK RELEASE OR DETACHABLE.
  
 2.PERMIT VALUATION SHALL INCLUDE ALL MATERIALS AND
 LABOR.ADJUST THE PERMIT VALUATION AS NEEDED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 11:25 Sent To B
Notes
2006-11-15 11:26:04TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 16:49 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 16:49 Sent To Z
Notes
2006-11-07 16:49:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 16:03 Sent To B
Notes
2006-10-27 16:03:42TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By alange Date 2006-11-02 Time 08:24 Rev Time 0.00
Received By alange Date 2006-10-25 Time 11:39 Sent To  
Notes
2006-10-25 11:39:37TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By jroach Date 2006-11-13 Time 16:47 Rev Time 0.00
Received By jroach Date 2006-11-13 Time 16:47 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By jroach Date 2006-10-27 Time 12:59 Rev Time 0.00
Received By jroach Date 2006-10-27 Time 12:59 Sent To I
Notes
2006-10-27 13:00:38***FAILED***
  
 1) TWO SETS OF ALL PLANS SHALL BE PROVIDED.ONLY ONE
 SET WAS INCLUDED IN THE SUBMITTAL PACKAGE.
  
 2) PLEASE HIGHLIGHT THE LOCATION OF THE CANOPY ON THE
 SITE PLAN.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.