Plan Review Details - Permit 06100743
Plan Review Stops For Permit 06100743
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-26 Cont ID  
Sent By rmcdouga Date 2007-01-26 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2007-01-26 Time 10:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By rmcdouga Date 2007-01-09 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2007-01-09 Time 16:44 Sent To  
Notes
2007-01-09 17:49:16DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) EGRESS DOORS ARE REQUIRED TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50
 OR MORE PERSONS PER FBC 1008.1.2. ON SHEET A2 THE FIFTH
 FLOOR PLAN SHOWS AN EGRESS DOOR "A" AT STAIR 1 WHICH
 DOES NOT SWING IN THE DIRECTION OF EGRESS TRAVEL.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-08 Cont ID  
Sent By rmcdouga Date 2006-11-08 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2006-11-08 Time 07:03 Sent To  
Notes
2006-11-14 07:06:02DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC
 DESIGNATIONS AS SPECIFIED IN FBC TABLE 601. SPECIFY A
 OR B.
  
 3) THE DOORS TO ONE SET OF EGRESS STAIRS ARE NOT SHOWN
 ON THE FLOOR PLANS ON SHEETS A2-A7.
  
 4)EGRESS DOORS ARE REQUIRED TO SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50
 OR MORE PERSONS PER FBC 1008.1.2.
  
 5) PROVIDE THE FLAME SPREAD AND SMOKE DEVELOPED INDEXES
 FOR THE WOOD VENEER PANELS IN THE CORRIDORS AT THE
 ELEVATORS. SEE FBC 803.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-13 Cont ID  
Sent By dpalmer Date 2007-08-13 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2007-08-13 Time 11:39 Sent To PC
Notes
2007-08-13 16:38:06REV FOR BATH ROOMS/HALLWAYS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-30 Cont ID  
Sent By dpalmer Date 2006-10-30 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 07:01 Sent To I
Notes
2007-01-11 13:20:34PLANS ROUTED BACK TO ELEC FOR PROCESSING 1/11/07
2006-10-30 07:08:24ELEC OK, STAMPED "E" SHEETS, SENT BACK TO INCOMING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 13:44 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 13:44 Sent To  
Notes
2007-01-09 13:45:24*****APPROVED*****
  
  
  
 ALL FIRE PLAN REVIEW COMMENTS OF 11/20/2006 HAVE BEEN
 ADDRESSED.PLAN SHEETS A-8 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 13:31 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 13:31 Sent To  
Notes
2006-11-20 14:14:14*****DENIED*****
  
  
  
 1.IN ADDITION TO THE 2003 EDITION OF NFPA 101,
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION - SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST
 AND DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 4.THE BUILDING'S FIRE PROTEDCTION SYSTEMS SHALL BE
 MAINTAINED OPERATIONAL AT ALL TIMES.
  
 5.HOW MANY FLOORS WILL BE DONE AT A TIME?IF THE
 FLOOR(S) IS/ARE BE OCCUPIED DURING THE SCOPE OF WORK,
 HOW WILL THE REQUIRED MEANS OF EGRESS INCLUDING DOORS,
 WALKWAYS, STAIRS, ETC BE MAINTAINED TO ENSURE
 REASONABLE LIFE SAFETY?
  
 6.IF THE FIRE ALARM OR FIRE SPRINKLER SYSTEM ARE TO
 BE MODIFIEDDUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 7.INDICATE INTERIOR FINISH FOR WALLS AND CEILINGS.
 CLASS A OR B IS REQUIRED IN THE MEANS OF EGRESS AREAS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 09:19 Sent To E
Notes
2007-08-10 09:20:11TO DP'S INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-25 Cont ID  
Sent By adarroug Date 2007-01-25 Time 10:28 Rev Time 0.00
Received By adarroug Date 2007-01-25 Time 10:28 Sent To B
Notes
2007-01-25 10:28:59TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 16:05 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 16:05 Sent To  
Notes
2006-12-30 16:11:15TO BOB #16 12/30
2006-12-14 16:05:52WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 14:17 Rev Time 0.00
Received By mawillia Date 2006-10-24 Time 13:33 Sent To  
Notes
2006-11-01 10:16:39TO "BOB"#7
2006-10-24 13:56:52WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 13:57 Rev Time 0.40
Received By tgordon Date 2006-11-01 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-11-15 Cont ID  
Sent By jleech Date 2006-11-15 Time 07:57 Rev Time 0.00
Received By jleech Date 2006-11-15 Time 07:57 Sent To  
Notes
2006-11-15 07:57:35FIXTURE CHANGE ONLY