| Plan Review Stops For Permit 06100734 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-30 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-30 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-28 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-28 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2007-12-28 13:09:29 | | | | BUILDING PLAN REVIEW | | | PERMIT: 06100734 | | | ADD: 3111 S. DIXIE HWY #101 | | | CONT: LEIGHTON MC GINN CO. | | | TEL: (561)863-4455 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: REV. 12/28/07 | | | ACTION: DENIED | | | | | | 1)) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS | | | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT THE | | | PRODUCT APPROVAL FOR THE NEW EXTERIOR DOOR #175 AND THE | | | GLAZED AREA WHERE DOOR #167C WAS REMOVED.NOTE: ALL | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET OF GRADE SHALL | | | MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. SHOW | | | COMPLIANCE. | | | | | | 2)SHEET A-3.0 IS MISSING THE DETAIL FOR WALL TYPE | | | WT-1. SUBMIT ALL WALL TYPES FOR THE PROJECT ON THE | | | DETAIL SHEET. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-30 |
Time |
16:13 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-09 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-09 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2007-03-09 11:28:44 | BUILDING PLAN REVIEW | | | PERMIT:06100734 | | | ADD: 3111 S. DIXIE HWY | | | CONT: LEIGHTON MCGINN CO. | | | TEL: (561)863-4455 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)11-4.13.6MINIMUM MANEUVERING CLEARANCES AT DOORS | | | THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS | | | SHOWN IN FIGURE 25 (18"MIN). THE FLOOR OR GROUND AREA | | | WITHIN THE REQUIRED CLEARANCES SHALL BE LEVEL AND | | | CLAEAR. SEE SHEET A-1.0. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-02 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-11-02 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-29 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-29 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2008-01-29 12:35:09 | ELEC OK, STAMPED SHEETS. | | | NEED TO RETAIN ONE COPY OF ELECTRICAL SHEETS ONCE FIRE | | | REVIEW IS DONE AND OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-27 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-26 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2007-12-27 08:11:20 | *** DENIED REVISION ** | | | | | | 1) NOTE: PLEASE SEE NOTES AND PROVISO GIVEN ON 3/4/07 | | | AND 3/26/07 AS PLANS WERE REDLINED AND NEEDED TO BE | | | REVISED TO SHOW MINIMUM CODE COMPLAINCE. | | | PLEASE SEE NOTES FROM BOTH OF THOSE REVIEWS ARE | | | ATTACHED. | | | PLEASE KNOW THAT UNTIL PROVISO NOTES ARE ADDRESSED NO | | | FURTHER ELECTRICAL REVISIONS WILL BE | | | RED-LINED/PROVISO. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-26 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-26 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2007-03-26 13:13:22 | PLANS NOT REVISED, PROVISO FROM 3/4/07 IS STILL IN | | | EFFECT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-04 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2007-03-04 10:34:08 | ***PROVISO/REVISON*** | | | | | | 1) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING | | | CONDUCTORS* SHOWN ON THE LINE SIDE OF THE METER AND | | | MAINS ARE NOT TO BE INSTALLED AS THIS WOULD PARALLEL | | | THE NEUTRAL FOR OBJECTIONABLE CURRENTS. | | | PLEASE SEE 250.6 AND 250.24B AS *EQUIPMENT GROUNDING | | | CONDUCTORS* ARE INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | | | | 2) NOTE: PLEASE BE SURE TO UPDATE PANEL SCHEDULES AND | | | PLANS TO SHOW ALL NEW CIRCUITING TO THE NEW PANELS AND | | | ALL CIRCUITS IN PANELS TO EACH OF THESE | | | LOCATIONS/ROOMS. | | | PLEASE SEE SECTION OF COMMENTARY WHICH REQUIRES ALL | | | CIRCUITS TO BE SPECIFIC TO AREAS AND ROOMS IN WHICH | | | THEY FEED. THE FOLLOWING IS TAKEN DIRECTLY FORM THAT | | | COMMENTARY. | | | ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY | | | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE | | | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND | | | STAMPING. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-30 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-30 |
Time |
07:09 |
Sent To |
I |
|
| Notes |
| 2006-10-30 07:50:52 | ******** UNSAT ************ | | | | | | 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECT ADDRESS | | | OF JOB AT 4100 OKEECHOBEE BLVD AS WELL AS 3111 S | | | DIXIE. | | | | | | PLEASE ALSO SEE THE JURISDICTION IS NOT IN PALM BEACH | | | COUNTY. JOB-SITE LOCATION IN THE CITY OF WEST PALM | | | BEACH. | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE FAC | | | 61G1-16.004 AND FS 481.219. | | | MISSING CERTIFICATE OF AUTHORIZATION NUMBER/ FIRM | | | LICENSE NUMBER. | | | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 3) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE | | | REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72, 2003 | | | NFPA-101 . | | | **AS STATED ON PLANS, THE "LATEST EDITION " WHICH IS | | | AVAIABLE IS NOT YET ADOPTED BY THE STATE> (NEC). | | | | | | 4) NOTE; PLEASE SEE AREAS WHICH ARE SHOWN AS COMMON | | | AREA CORRIDORS YET SHOW ELECTRICAL FOR RECEPT AND HVAC | | | BEING FED FROM A TENANT SPACE. PLEASE KNOW, NO COMMON | | | AREAS MAY BE FED FROM FROM AN TENANT OCCUPANCY. 210.25, | | | 90.4. | | | | | | 5) NOTE: PLEASE SEE PANEL SCHEDULE FOR "H2" SHOWS OTHER | | | ELECTRICAL HOWEVER COULD NOT LOCATE WHAT OR WHERE THESE | | | ITEMS ARE?? | | | PLEASE ALSO SEE LOADS ON THIS PANEL IS SHOWN AS XXXXX | | | (BLANK), PLEASE COMPLETE. | | | 220, 215.5, | | | FBC 106.1.2 ADMIN SECT. | | | | | | 6) NOTE: PLEASE SEE RISER AND EXPLAIN HOW FEEDERS FROM | | | FPL ARE ROUTED TO THE GUTTER. RISER SEEMS TO SHOW THE | | | CT/METER ON THE LOAD SIDE OF THE MDP??? | | | PLEASE CLARIFY AND REVISE RISER. AS SHOWN DOES NOT | | | CORRELATE WITH MIN FPL SERVICE STANDARDS OR NEC. 230. | | | | | | 7) NOTE: PLEASE SEE PANEL INDICATE CIRCUITING FOR NEW | | | ROOMS. | | | PLEASE SEE PANEL "G" IS BEING SHOWN BEING SHOWN AS 125A | | | RATED, YET RISER SHOWS A 150A MAIN DISCONNECT FEEDING | | | SAID PANEL. | | | PLEASE SEE 240, 230 ETC | | | | | | 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW | | | DISCONNECTS ARE SHOWN ON RISER. PLEASE SEE 110.9, | | | 240.12 | | | | | | 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3, 230.42 | | | | | | 10) NOTE: PLEASE BE SURE ALL SEALS ARE RAISED, CLEAR | | | AND VISABLE WITH ALL INFORMATION AS REQUIRED ON SAID | | | SEAL. | | | PLEASE SEE SOME ARE NOT VISABLE EVEN WHEN SHADING WITH | | | PENCIL. | | | FS471.025 | | | PLEASE BE SURE THEY ARE ALSO SIGNED WITH LEGAL | | | SIGNATURE. | | | | | | 11) NOTE: PLEASE SEE FBC 13-101.1.3, METHOD "A" MAY NOT | | | BEUSED. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-04 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-04 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2008-02-04 11:11:49 | *****REVISIONS APPROVED***** | | | | | | | | | REVISED PLAN SHEETS E-2.1, E-2.2, AND FP-1.0 WERE | | | STAMPED, INITIALED, AND DATED.. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6622 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-31 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-31 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2007-12-31 11:38:22 | *****STAMPING NEEDED***** | | | | | | | | | REVISED PLAN SHEETS E-2.1, E-2.2, AND FP-1.0 TO BE | | | FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6622 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-30 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-30 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2007-03-30 14:00:00 | *****APPROVED***** | | | | | | | | | ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN | | | ADDRESSED;PLAN SHEETS A-1.1, E-2.1, E-2.2, AND FP-1.0 | | | WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-14 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-14 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2007-03-14 13:07:59 | ****UNSAT***** | | | | | | | | | THE FIVE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN | | | REVIEW HAVE BEEN SATISFIED WITH THE EXCEPTION OF THE | | | FOLLOWING WHICH STILL NEED TO BE ADDRESSED: | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | INSERT ON SHEET A-1.0 | | | | | | 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE | | | RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO | | | NOTE #11.ON SHEET A-1.0, DELETE "THE PALM BEACH | | | COUNTY FIRE DEPARTMENT (PBFD)";INSERT "WEST PALM | | | BEACH FIRE RESCUE (WPBFR)." | | | | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A | | | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-05 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-05 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2006-12-05 11:32:46 | *****DENIED***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.CONSTRUCTION AND (OR) DEMOLITION OPERATIONS IN THE | | | WORK SITE AREA SHALL NOT INTERFERE OR HINDER ACCESS OR | | | EGRESS FROM OTHER AREA AREAS OF THE BUILDING. | | | | | | 3.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE | | | SCOPE OF THE WORK, SEPARATE PERMIT AND PLANS ARE | | | REQUIRED. | | | | | | 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE | | | RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO | | | NOTE #10. | | | | | | 5.AS PER WPBFR, DUCT DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM.AMEND GENERAL FIRE ALARM NOTE #17, | | | SHEET E-2.2. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A | | | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-28 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-28 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2008-01-28 09:04:13 | TO "BOB"#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-12-26 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-12-26 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-12-26 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2007-12-26 15:42:08 | TO "BOB" # 8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-12-20 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-12-20 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2007-12-20 17:47:22 | WAITING FOR BOB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-25 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-25 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2007-03-25 13:46:02 | TO "BOB"#14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-01 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-01 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2007-03-01 09:18:47 | TO "BOB"#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-05 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-24 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2006-11-01 10:00:10 | TO "BOB"#4 | | 2006-10-24 14:03:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-27 |
Time |
09:28 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2007-12-27 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2007-12-27 09:30:43 | REVISION TO MECH. PLANS PAGES AC-1.0, AC-2.0, AND | | | AC-2.1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-01 |
Time |
13:57 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-03-01 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-01 |
Time |
11:52 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-11-01 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2006-11-01 12:20:19 | *** DENIED *** | | | 1) SEE PLANS PG. AC-2.1, HP-E4 NEW 10X8 FRESH AIR DUCT | | | THROU FIRE WALL AT PORTFOLIO MANAGER ROOM #163 , NEEDS | | | A FIRE DAMPER, PER 2004 FBC/M 607.5.1. | | | | | | 2) SEE PLANS PG. AC-2.1, NEW 6" FLEX DUCT THROU FIRE | | | WALL FROM CORRIDOR #2 TO CORR. #3A NEEDS A FIRE DAMPER, | | | PER 2004 FBC/M 607.5.1. | | | | | | 3) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-11-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-09 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-09 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|