| 2006-11-01 11:52:41 | UNSAT |
| | REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, |
| | FLORIDA ADMINISRTATIVE CODE, FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE |
| | COMPLIANCE. |
| | |
| | 1.FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | (NOTE: NUMBER TWO (2) IS MISSING FROM THE TITLE |
| | BLOCK.) |
| | |
| | 2. FAC-CODE-61G1-16001 ARCHITECT'S AND |
| | INTERIOR DESIGNER'S SEAL: (NOTE: THE SEAL IMPRESSION IS |
| | WEAK AND NOT LEGIBLE) |
| | |
| | 3. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE PROVIDE A COMPLETE FLOOR |
| | PLAN OF SAID RESIDENCE THAT CORRELATES WITH THE |
| | SANITARY RISER DIAGRAM. THE SANITARY RISER DIAGRAM |
| | INDICATES A NEW LAV THAT IS NOT INDICATED ON THE FLOOR |
| | PLAN. ALSO THERE IS A WATER CLOSET AND TUB WITH NO LAV |
| | INDICATED ON THE SANTARY RISER DIAGRAM THAT IS NOT |
| | INDICATED ON THE FLOOR PLAN. THIS IS CONFUSING, NOT TO |
| | MENTION UNSANITARY BY NOT HAVING A PLACE TO WASH HANDS |
| | AFTER USING WATER CLOSET. PLEASE CORRECT DRAWINGS FOR |
| | THE RESUBMITTAL. |
| | |
| | 4. PER FBC-2004 PLUMBING, SECTION 704.2: THE SIZE OF |
| | THE DRAINAGE PIPING SHALL NOT BE REDUCED IN SIZE IN THE |
| | DIRECTION OF FLOW. |
| | |
| | 5. PER FBC-2004 PLUMBING, SECTION |
| | 901.2.1 VENTING REQUIRED: EVERY TRAP AND |
| | TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING |
| | METHODS SPECIFIED IN THIS CHAPTER. (NOTE: THE LAVAND |
| | NEW LAV ARE NOT VENTED.) |
| | |
| | 6. PER FBC-2004,PLUMBING, SECTION 905.3 |
| | VENT CONNECTIONS TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE HORIZONTAL DRAIN PIPE. |
| | |
| | 7. PER FBC-2004 PLUMBING, SECTION 802.1.6 DOMESTIC |
| | DISHWASHING MACHINES: DOMESTIC DISHWASHING MACHINE |
| | SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON THE |
| | TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER |
| | CONNECTION OF A FOOD WASTE GRINDER. (NOTE: THE |
| | DISHWASHER CONNECTION INDICATED ON DRAWINGS IS WRONG, |
| | PLEASE SEE CORRECTED DRAWING FOR RESUBMITTAL.) |
| | |
| | 8. THE WATER CLOSETS INDICATED ON THE DRAWING INDICATE |
| | TRAPS. THIS IS WRONG PER FBC-2004 PLUMBING, SECTION |
| | 1002.1 FIXTURE TRAPS: A FIXTURE SHALL NOT BE DOUBLE |
| | TRAPPED. (NOTE: A WATER CLOSET HAS AN INTREGRAL TRAP |
| | WHICH MEANS ONE DOES NOT NEED TO BE PROVIDED.) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |