Plan Review Details - Permit 06100720
Plan Review Stops For Permit 06100720
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-09 Cont ID  
Sent By alange Date 2006-11-09 Time 08:26 Rev Time 0.00
Received By alange Date 2006-11-09 Time 08:26 Sent To  
Notes
2006-11-09 08:42:56DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.PLANS SHALL BE DESIGNED TO THE 2004 FLORIDA
 RESIDENTIAL CODE.SHOW ON PLANS.
  
  
 3.ADJUST PERMIT VALUATION TO INCLUDE ALL MATERIALS
 AND LABOR.ADDITIONAL PERMIT FEES ARE DUE.
  
 4.SECTION USED 1606 IS FROM THE 2001 FBC.SHOW
 CURRENT CODE SECTION FOR THE 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5.PRODUCT APPROVALS REQUIRED FOR STRAPS AND
 TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 10.CLEARLY SHOW EXISTING AREAS AND AREAS OF NEW WORK.
 CLEARLY IDENTIDY EXISTING AND NEW WALLS.SCOPE OF WOK
 ON APPLICATION IS NOT CLEAR.SHOW SCOPE OF WORK ON
 PLANS.
  
 11. CLARITY OF PLANS WEST PALM BEACH AMMENDMENT TO THE
 2004 FBC:INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 15:13 Rev Time 0.50
Received By btrobaug Date 2006-10-30 Time 14:07 Sent To P
Notes
2006-10-30 15:13:27NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).
  
 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 5} 210.52(E) OUTDOOR OUTLETS. FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (61/2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. SEE 210.8(A)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-09 Cont ID  
Sent By alange Date 2006-11-09 Time 08:43 Rev Time 0.00
Received By alange Date 2006-10-23 Time 10:32 Sent To  
Notes
2006-10-23 10:32:40TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 15:54 Rev Time 0.30
Received By tgordon Date 2006-11-01 Time 15:54 Sent To B
Notes
2006-11-01 16:00:24*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE SUBMIT MECHANICAL (A/C) PLANS SHOWING ANY A/C
 WORK THAT WILL BE DONE, PER 2004 FBC WPB AMEND.
 106.3.5.4 (10).
  
 2) SEE PLUMBING REVIEW NOTES 1 AND 2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By mperson Date 2006-11-01 Time 09:30 Rev Time 1.25
Received By mperson Date 2006-11-01 Time 09:30 Sent To M
Notes
2006-11-01 11:52:41UNSAT
 REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1,
 FLORIDA ADMINISRTATIVE CODE, FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE.
  
 1.FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 (NOTE: NUMBER TWO (2) IS MISSING FROM THE TITLE
 BLOCK.)
  
 2. FAC-CODE-61G1-16001 ARCHITECT'S AND
 INTERIOR DESIGNER'S SEAL: (NOTE: THE SEAL IMPRESSION IS
 WEAK AND NOT LEGIBLE)
  
 3. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE PROVIDE A COMPLETE FLOOR
 PLAN OF SAID RESIDENCE THAT CORRELATES WITH THE
 SANITARY RISER DIAGRAM. THE SANITARY RISER DIAGRAM
 INDICATES A NEW LAV THAT IS NOT INDICATED ON THE FLOOR
 PLAN. ALSO THERE IS A WATER CLOSET AND TUB WITH NO LAV
 INDICATED ON THE SANTARY RISER DIAGRAM THAT IS NOT
 INDICATED ON THE FLOOR PLAN. THIS IS CONFUSING, NOT TO
 MENTION UNSANITARY BY NOT HAVING A PLACE TO WASH HANDS
 AFTER USING WATER CLOSET. PLEASE CORRECT DRAWINGS FOR
 THE RESUBMITTAL.
  
 4. PER FBC-2004 PLUMBING, SECTION 704.2: THE SIZE OF
 THE DRAINAGE PIPING SHALL NOT BE REDUCED IN SIZE IN THE
 DIRECTION OF FLOW.
  
 5. PER FBC-2004 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING
 METHODS SPECIFIED IN THIS CHAPTER. (NOTE: THE LAVAND
 NEW LAV ARE NOT VENTED.)
  
 6. PER FBC-2004,PLUMBING, SECTION 905.3
 VENT CONNECTIONS TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE.
  
 7. PER FBC-2004 PLUMBING, SECTION 802.1.6 DOMESTIC
 DISHWASHING MACHINES: DOMESTIC DISHWASHING MACHINE
 SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. (NOTE: THE
 DISHWASHER CONNECTION INDICATED ON DRAWINGS IS WRONG,
 PLEASE SEE CORRECTED DRAWING FOR RESUBMITTAL.)
  
 8. THE WATER CLOSETS INDICATED ON THE DRAWING INDICATE
 TRAPS. THIS IS WRONG PER FBC-2004 PLUMBING, SECTION
 1002.1 FIXTURE TRAPS: A FIXTURE SHALL NOT BE DOUBLE
 TRAPPED. (NOTE: A WATER CLOSET HAS AN INTREGRAL TRAP
 WHICH MEANS ONE DOES NOT NEED TO BE PROVIDED.)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  