Plan Review Details - Permit 06100706
Plan Review Stops For Permit 06100706
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-21 Cont ID  
Sent By mwennerg Date 2008-05-21 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2008-05-21 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-14 Cont ID  
Sent By mawillia Date 2008-05-14 Time 13:13 Rev Time 0.00
Received By mawillia Date 2008-05-14 Time 12:31 Sent To  
Notes
2008-05-14 13:20:00*****UNSAT*****
  
  
 REVISED PLANS APPEAR TO BE CODE COMPLIANT, HOWEVER, THE
 ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-27 Cont ID  
Sent By mawillia Date 2006-11-27 Time 14:16 Rev Time 0.00
Received By mawillia Date 2006-11-27 Time 14:16 Sent To  
Notes
2006-11-27 14:19:33*****APPROVED*****
  
  
 NOTICE OF COMMENCEMENT (OR COPY THAT ONE HAS BEEN FILED
 FOR) NEEDED BEFORE PERMIT CAN BE ISSUED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By mawillia Date 2006-11-03 Time 11:42 Rev Time 0.00
Received By mawillia Date 2006-11-03 Time 11:42 Sent To  
Notes
2006-11-03 12:13:41****DENIED***
  
 1.SINCE THE SCOPE OF THE WORK IS GREATER THAN
 $2500.00, THE APPLICANT SHALL FILE WITH THE AHJ EITHER
 A RECORDED NOTICE OF COMMENCEMENT OR A NOTORIZED
 STATEMENT THAT THE NOTICE OF COMMENCEMENT HAS BEEN
 FILED FOR RECORDING, ALONG WITH A COPY THEREOF.
  
 2.THE SUBMITTED PLANS AND HYDRAULIC CALCULATIONS
 SHEETS SHOULD REFLECT THE LOCATION WHERE THE ACTUAL
 WORK IS BEING DONE.
  
 3.A SAFETY MARGIN OF AT LEAST 5.0 PSI SHOULD BE SHOWN
 IN THE HYDRAULIC CALCULATIONS.
  
 4.NFPA 13, 2002 EDITION, SHALL BE REFERENCED.
  
 **REMINDERS**
  
 5.WATERFLOW ACTIVATION SHALL INTIATE A GENERAL ALARM
 WITHIN 45 TO 60 SECONDS.
  
 6.SPRINKLER SYSTEM IS TO BE MONITORED.
  
 7.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
 COORDINATE WITH THE GENERAL AND/OR FIRE ALARM CONTRATOR
 BY FINAL SPRINKLER/FIRE ALARM INSPECTION.
  
 **TO EXPEDITE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.**
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 14:24 Sent To FIRE
Notes
2008-05-16 14:24:48TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 10:34 Sent To FIRE
Notes
2008-05-07 10:34:23TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 17:49 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 17:49 Sent To FIRE
Notes
2006-11-09 17:49:47TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-03 Cont ID  
Sent By mawillia Date 2006-11-03 Time 11:42 Rev Time 0.00
Received By mawillia Date 2006-10-23 Time 10:24 Sent To  
Notes
2006-10-23 10:24:58TO "F" BOX