| 2006-11-09 07:33:37 | BUILDING PLAN REVIEW |
| | PERMIT: 06100696UNIT# 1 |
| | 06100693UNIT# 2 |
| | 06100695UNIT# 3 |
| | 06081555UNIT# 4 |
| | ADD: 255 EVERNIA ST |
| | UNITS MU1-MU4 |
| | CONT: INPROSFL, INC |
| | TEL: (954)2020500 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) COMPLIED. |
| | |
| | 3)2ND REQUEST,SINCE EACH UNIT WILL REQUIRE ITS OWN |
| | PERMIT APPLICATION,A NOTICE OF |
| | COMMENCEMENT WILL ALSO NEED TO BE |
| | RECORDED AT THE CLERK OF THE COURT. |
| | FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6A) COMPLIED. |
| | |
| | 6B)2ND REQUEST, USE AND OCCUPANCY, IN ACCORDANCE WITH |
| | THE PROVISIONS OF SECTION 302.1.FBC. |
| | |
| | 6C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. PLANS INDICATE TYPE V-PROTECTED TABLE 500, |
| | SEE THE HEIGHT AND AREA REQUIREMENTS TABLE 503, THIS IS |
| | FOR THE ENTIRE BLDG, HIGHRISE!!!!! |
| | |
| | 6D)TO BE DETERMINED @ TENANT BUILD OUT. |
| | |
| | 6E) COMPLIED. |
| | |
| | 6F) COMPLIED. |
| | |
| | 7)2ND REQUEST, THE STRUCTURAL SHEETS DO |
| | NOT PROVIDE THE WIND DESIGN PERAMETERS |
| | THATWILLIAM COOK P.E. DESIGNED TOO. |
| | 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | PLEASE PROVIDE THE POSITIVE/ NEGATIVE PRESSURESFOR |
| | BOTH ZONE 4 & ZONE 5, INDICATE THESE ZONES ON THE |
| | PLANS. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) STOREFRONT PLANS AND CALCULATIONS ARE FOR ZONE 4, |
| | ALSO SHOW CALCULATIONS AND LOCATION FOR END ZONES (ZONE |
| | 5). |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) 2ND REQUEST, THE DESIGNER OF RECORD REVIEWED THIS |
| | PRODUCT FOR ZONE 4, WITH THE |
| | NEW CALCULATIONS FOR ZONE# 5, THE PRESSURES SHALL BE |
| | GREATER AND REQUIRE ADDITIONAL |
| | SUPPORTS. |
| | PLEASE HIGHLIGHT IN THE REPORT WHICH ANCHORING SYSTEM |
| | TO BE USED, MULLIONS AND GLASS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |