Plan Review Details - Permit 06100619
Plan Review Stops For Permit 06100619
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 17:09 Rev Time 1.22
Received By jwitmer Date 2007-01-22 Time 17:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By jwitmer Date 2006-12-13 Time 16:00 Rev Time 1.11
Received By jwitmer Date 2006-12-13 Time 16:00 Sent To PC
Notes
2006-12-13 16:07:28BUILDING PLAN REVIEW
 PERMIT: 06100619
 ADD: 1609 FORUM PL. SUITE# 110
 CONT: PASS INTERNATIONAL
 TEL: (561)702-7201
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE NEW EXIT DOOR "B" IS MISSING THE 18" ON THE
 LATCH SIDE, ALSO SEE LOCATION OF FIRE EXTINGUISHER AND
 PROJECTIONS.
  
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
 11-4.4.4 PROTRUDING OBJECTS.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM
 FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE
 THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND
 FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING
 SPACE [SEE FIGURE 11-8 (E)].
 1003.3.3 HORIZONTAL PROJECTIONS.
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27
 AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR.
 HANDRAILS CAN PROJECT UP TO 4? INCHES (114 MM) FROM THE
 WALL.
  
 2) THE EXISTING DOOR BETWEEN THE RECEPTION ROOM AND
 CORRIDOR IS ALSO MISSING THE 18" LATCH SIDE. UNDER THE
 DISPROPORTIONATE COST THIS DOOR TO BE CORRECTED.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-31 Cont ID  
Sent By alange Date 2006-10-31 Time 16:00 Rev Time 0.00
Received By alange Date 2006-10-31 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-23 Cont ID  
Sent By dpalmer Date 2007-01-23 Time 08:06 Rev Time 0.00
Received By dpalmer Date 2007-01-23 Time 08:02 Sent To  
Notes
2007-01-23 08:07:19NEW SHEETS, PREVIOUS STAMPED SHEETS WERE NOT IN
 RESUBMITTED SETS.
 RESTAMPED OK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2006-12-08 Time 09:06 Sent To I
Notes
2006-12-08 09:07:15PLANS REMOVED FROM INCOMING , PLANS OK, SENT BACK TO
 INCOMING

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 17:53 Sent To  
Notes
2006-10-25 18:39:34** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS CONTAINS A TITLE BLOCK FOR A
 CONSULTING ENGINERR, YET THEY ARE NOT SIGNED AND SEALED
 BY SAID ENGINEER.. PLEASE KNOW SCOPE IS NOT REQUIRED TO
 BE DONE BY AN ENGINEER, HOWEVER IF PLANS CONTAIN THE
 TITLE BLOCK THEN THEY ARE REQUIRED TO BE SIGNED, AND
 SELED.
  
 2) NOTE: PLEASE SEE PLANS TO STATE 2002 NFPA-70 (NEC).
  
 THE 2ND NOTE COULD BE REDLINED.
 ELECTRICAL IS OK FOR MIN SCOPE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 12:01 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 12:01 Sent To B
Notes
2007-01-24 12:02:35*****APPROVED*****
  
  
 SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 13:57 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 15:48 Sent To  
Notes
2006-10-26 15:52:341. FLOOR PLAN DOES NOT DISPLAY ANY EXISTING EXIT SIGNS
 OR EMERGENCY LIGHTING EQUIPMENT. NOTE # 9 ON PAGE A-1
 ADVISES THAT THESE DEVICES WILL BE RELOCATED. PLEASE
 INDICATE THE EXISTING AND NEW LOCATION FOR THESE
 DEVICES.
 2. ARE THERE ANY EXISTING OR NEW FIRE EXTINGUISHERS
 PLANNED FOR THE SPACE.
 3. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
 4. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 16:11 Sent To  
Notes
2007-01-24 15:00:52 
  
  
 1/24/07PASSED.SENT TO DEWEY PALMER'S DESK FOR
 PROCESSING.RB
2007-01-22 16:13:01TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 13:46 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 13:46 Sent To  
Notes
2006-12-12 11:43:33TO "BOB"#15
2006-11-21 13:46:24WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-01 Cont ID  
Sent By alange Date 2006-11-01 Time 09:48 Rev Time 0.00
Received By alange Date 2006-10-18 Time 15:00 Sent To  
Notes
2006-10-25 10:12:29TO "BOB"#10
2006-10-18 15:00:28WAITING FOR "BOB"