Plan Review Details - Permit 06100612
Plan Review Stops For Permit 06100612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-01 Cont ID  
Sent By rmcdouga Date 2006-12-01 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2006-12-01 Time 11:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By rmcdouga Date 2006-10-24 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2006-10-24 Time 15:08 Sent To  
Notes
2006-10-24 16:15:26DENIED BY BUILDING
  
 1) THE FLORIDA ADMINISTRATIVE CODE 61G-16.004 REQUIRES
 THE LICENSE NUMBER OF THE ARCHITECTURAL FIRM TO BE
 SPECIFIED IN THE TITLE BLOCK. PLEASE COMPLY.
  
 2) THE FLORIDA ADMINISTRATIVE CODE 61G-23.002 REQUIRES
 THE CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS TO APPEAR ON EACH SHEET OF THE
 PLANS. PLEASE COMPLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-29 Cont ID  
Sent By dpalmer Date 2006-11-29 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2006-11-29 Time 20:36 Sent To  
Notes
2006-11-29 20:41:07ELEC INTERIOR DEMO PERMIT REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 12:17 Sent To  
Notes
2006-10-24 12:26:34****** UNSAT **********
  
 1) NOTE: PLEASE SEE NOTES WHICH WAS GIVEN ON ORIGINAL
 REVIEW UNDER THE BUILD OUT PERMIT WHICH STATES FLORIDA
 ADMINISTRATIVE CODE61G1-16.004, 61G15-23.002 AND
 FLORIDA STATUTES, 471.023, 481.219 FOR MISSING REQUIRED
 LICENSING UNDER THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE TITLE BLOCKS HAVE
 NOT BEEN CORRECTED AT THIS TIME WITH MISSING
 CERTIFICATE OF AUTHORIZATION NUMBERS FORTHEENGINEER
 FIRM AS SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. ONCE
 AGAIN, IF THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER.
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 DPALMERWPB.ORG

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-06 Cont ID  
Sent By mawillia Date 2006-12-06 Time 11:16 Rev Time 0.00
Received By mawillia Date 2006-12-06 Time 11:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 15:30 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 15:21 Sent To  
Notes
2006-10-26 15:30:451. CONSTRUCTION, ALTERATION, AND DEMOLITION TO COMPLY
 WITH NFPA 241.
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 3. EXITS ARE TO BE MAINTAINED DURING DEMOLITION
 ACTIVITIES.
 4. GASOLINE POWERED EQUIPMENT FOR DEMOLITION ACTIVITIES
 SHALL NOT BE USED TO PREVENT THE POSSIBILITY OF CARBON
 MONOXIDE POISONING.
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEM REMODEL.
 6. APPROVED FIRE WATCH ACTIVITIES IF REQUIRED MUST BE
 APPROVED BY THE FIRE MARSHAL OR ASSISTANT FIRE MARSHAL
 WHENEVER A REQUIRED FIRE PROTECTION SYSTEM IS SHUT DOWN
 MORE THAN FOUR HOURS IN ANY TWENTY FOUR HOUR PERIOD.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 15:55 Sent To  
Notes
2006-11-29 20:36:18TO BOB BOARD SPACE #13.
2006-11-16 15:56:09WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-03 Cont ID  
Sent By jleech Date 2006-11-03 Time 14:23 Rev Time 0.00
Received By jleech Date 2006-10-18 Time 12:37 Sent To  
Notes
2006-10-24 12:37:04TO "BOB"#8--INTERIOR DEMO

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-25 Cont ID  
Sent By tgordon Date 2006-10-25 Time 09:35 Rev Time 0.15
Received By tgordon Date 2006-10-25 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By jleech Date 2006-12-05 Time 15:23 Rev Time 0.00
Received By jleech Date 2006-12-05 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By jleech Date 2006-11-03 Time 14:10 Rev Time 0.00
Received By jleech Date 2006-11-03 Time 14:10 Sent To  
Notes
2006-11-03 14:19:50SEE BUILDING PLAN REVIEW NOTES 1 AND 2.
 PLEASE ADD NOTE TO DEMO PLAN; NO DEAD ENDS PERMITED IN
 THE PLUMBING SYSTEM FBC-2004 PLUMBING SECTION 704.5.A
 PLUMBING PERMIT IS REQUIRED BY ALICENSED PLUMBING
 CONTRACTOR. INSPECTION REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805=6695