Plan Review Details - Permit 06100561
Plan Review Stops For Permit 06100561
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-31 Cont ID  
Sent By amorse Date 2007-03-31 Time 08:49 Rev Time 0.00
Received By amorse Date 2007-03-31 Time 08:49 Sent To PC
Notes
2007-03-31 09:31:59 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES PER 108.3 FBC*. USING THE ABOVE GUIDES A FAIR
 VALUATION OF THE PROPOSED WORK IS $241,573.00 AND
 INCREASED PERMIT FEES ARE DUE OF $793.59. THERE WILL BE
 NO FURTHER PLAN REVIEW UNTIL FEES ARE PAID IN FULL.
  
 2) PRODUCT APPROVALS WERE NOT SUBMITTED FOR THE GLASS
 BLOCK OR THE PRECAST LINTELS PLEASE SUBMIT THESE ALONG
 WITH UPDATED NOA/PRODUCT APPROVALS FOR THE GARAGE DOORS
 AS THEY HAVE BEEN UPDATED ON THE STATE SITE (MIAMI-DADE
 NOA# 05-0228.02) AND THE THERMA-TRU FIBERGLASS DOOR
 SUBMITALS ARE NOT IMPACT RATED AS SUCH SHUTTERS OF SOME
 KIND WILL BE REQUIRED.
  
 3) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED. PLEASE NOTE THAT
 I HAVE PRINTED AND ATTACHED THESE TO YOUR CORRECT
 MAIMI-DADE NOA'S.
  
 4) PHOTO COPIED, STAMPED OR REPRODUCED
 SIGNATURES ARE NOT ACCEPTABLE PER
 471.025 F.S. PLEASE HAVE THE TRUSS DRAWINGS AND SOIL
 REPORTS SIGNED BY THE RESPECTIVE ENGINEERS ALSO THE
 ENGINEERS SEAL ON THE SOIL REPORT IS NON COMPLIANT WITH
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AND
 61G15-23.001(1) F.A.C. THIS SEAL HAS BEEN NON COMPLIANT
 SINCE JAN 1, 2006.
  
 5)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By alange Date 2006-11-07 Time 08:16 Rev Time 0.00
Received By alange Date 2006-11-07 Time 08:16 Sent To  
Notes
2006-11-07 08:20:49DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.CODE SECTION SHOWS PALM BEACH COUNTY.CODE SHOULD
 REFLECT WEST PALM BEACH AMMENDMENTS TO THE 2004 FBC.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $241,573.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4."R" VALUES DO NOT MACH PLANS ON THE ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR GLASS BLOCK, LINTELS
 AND STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-06 Cont ID  
Sent By dpalmer Date 2007-02-06 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2007-02-05 Time 16:44 Sent To M
Notes
2007-02-06 10:25:16******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
 PLEASE KNOW THAT AT THIS TIME DUE TO THE COMPLETELY
 REVISED RISER AND CHANGES, A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AS THERE ARE MANY ITEMS NOT
 SUBMITTED ON RISER ETC.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
 *** PREVIOUS REVIEW NOTES ***
  
 1) NOTE: NO, PLEASE SEE THE YEAR OF THE CODES IS NOT
 STATED ON PLANS. PLEASE KNOW THIS IS OF THE UTMOST
 IMPORTANCE AS THE 2005 NFPA-70 HAS BEEN ADOPTED AND
 THERE ARE SUBSTANTIAL DIFFERENCES.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 ** THE LATEST CODE IS NOTE YET ADOPTED BY THE STATE.
  
 2) NOTE: OK, HOWEVER SEE NOT FOR CIRCUITING.
  
 3) NOTE: NO, PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN
 COMPLETELY REVISED REMOVING MAIN WITH ANY OVER CURRENT
 PROTECTION DEVICES FOR SUB PANELS OR OTHER EQUIPMENT
 WHICH IS FED. PLEASE SEE THE RISER NOW SEEMS TO ONLY
 SHOW A METER TO SOME SORT OF GUTTER WITH NO MAINS ON
 THE RISER, OR ANY EQUIPMENT? PLEASE SEE 240.21 IF THE
 ATTEMPT IS TRYING TO USE SOME SORT OF TAP CONDUCTOR
 RULE. PLEASE SEE THAT ALL MAINS ARE REQUIRED TO BE
 GROUPED, ALL TAPS SHALL TERMINATE IN OVER CURRENT
 PROTECTION ETC.
 PLEASE SEE PANELS ARE SHOWN AS MLO (MAIN LUG ONLY)
 WITHOUT ANY MAINS.
 PLEASE SEE 230.70, 230.71, 230.72, 230.76, 230.79 ETC
 FOR REQUIRED MAINS ETC.
 PLEASE SEE THERE IS EQUIPMENT GROUNDING CONDUCTORS
 BEING SHOWN FROM THIS GUTTER OF SORTS TO THE MLO PANELS
 AND EQUIPMENT, WHICH IS OK AS LONG AS THERE ARE MAINS
 AHEAD OF THIS.
 PLEASE SEE THE PREVIOUS RISER WAS COMPLETELY
 DIFFERENT.
 PLEASE SHOW THE LOCATION OF SERVICE ON PLANS AND
 IDENTIFY ALL PANELS/MAINS AND THEIR LOCATIONS ON
 PLANS.110.26, 240.24 ETC.
 PLEASE SEE THE FEEDERS ON THE RISER DO NOT CORRELATE
 WITH THE FEEDERS ON THE PANEL SUBMITTED.
 FBC 106.1.2, 106.3.5.4
 NEC 2002 PLEASE ALSO SEE OTHER COMMENTS WHICH WILL
 AFFECT THE RISER AND PANELS AS SHOWN.
  
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE CORRELATE RISER AND PLANS, AS PLANS CALL FOR
 WHAT APPEARS TO BE A NEW METER/MAIN COMBO, YET RISER
 SHOWS NO MAIN? PLEASE INDICATE THE SIZE OF THE NEW
 MCB.
 230.70, 240.4, 310.15B6, 310.16, 230.71, ETC
  
 4) NOTE: OK, NOTE REMOVED.
  
 5) NOTE: NO, PLEASE SEE AS THE NOTE #3 STATES THAT
 THERE ARE NOT MAINS ETC, THE RATING CAN NOT BE
 VERIFIED.
 PLEASE SEE THE AVAILABLE FAULT CURRENT IS BEING STATED
 AND SHOWN FROM FPL AND THE MLO PANELS ARE SHOWING A 22K
 RATING FOR ALL BRANCH BREAKERS. SINCE THE MAINS ARE NOT
 SHOWN AT THIS TIME, THIS COMMENT HAS NOT BEEN
 ADDRESSED.
 ** PLEASE ALSO VERIFY THE INDICATION OF THE BRANCH
 BREAKERS BEING SHOWN AT 22K RATING AS THIS IS NOT
 COMMON AND WOULD BE EXTREMELY EXPENSIVE. HAVING THE
 BRANCH BREAKERS RATED AT 22K IS PERMITTED.
 PLEASE ADDRESS THE COMMENT FOR NEW MAINS ONCE RISER IS
 REVISED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE EQUIPMENT
 ALONG WITH SELECTIVE COORDINATION WHICH IS TO BE DONE.
 110.9, 240.12
  
 6) NOTE: NO, PLEASE SEE THE RISER WAS REVISED AND NOW
 SHOWS A NEW PANEL AND AN EXISTING PANEL, HOWEVER THE
 COMPETITION OF CIRCUITS ON PLANS AND COORDINATION WITH
 THE NEW PANEL SUBMITTED AHS NOT YET BEEN DONE.
 PLEASE SEE THE PREVIOUS COMMENT WAS TO SUBMIT A PANEL
 SCHEDULE WHICH WAS NOT SUBMITTED, NOW THAT ONE IS
 SUBMITTED, THERE ARE ITEMS WHICH DO NOT CORRELATE WITH
 LOAD CALCULATIONS AND PLANS.
 PLEASE SEE SOME ITEMS ON PLANS WHICH DO NOT CONTAIN THE
 CIRCUITING FOR WHAT THE EQUIPMENT IS. (OVEN, SA'S,
 FRIG, MICROWAVE ETC) ARE NOT CIRCUITED, EVEN THOUGH THE
 OVEN IS SHOWN IN LOAD CALCULATIONS?
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AND NEW FOR
 ITEMS ON PANEL SCHEDULE AND LOAD CALCULATIONS WHICH DO
 NOT MATCH.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT A PANEL SCHEDULE(S) INDICATING ALL
 MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE(S)SHOW ALL OCP DEVICES
 AND CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS.
 PLEASE KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE
 AT THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: OK.
  
 8) NOTE:OK, HOWEVER PLEASE SEE A CIRCUIT ON PANEL
 SCHEDULE WHICH MENTIONS *WP BATH*PLEASE SEE MISSING
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: NO, PLEASE SEE THE CIRCUIT IS ON PANEL
 SCHEDULE HOWEVER THE LOAD IS NOT CORRECT AND THE LOAD
 WHICH IS TO BE CORRECTED NEEDS TO BE INCLUDED IN THE
 LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING DINING AREA/BREAKFAST AREA PER
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: OK.
  
 11) NOTE: NO, PLEASE SEE A NOTE WAS ADDED ON THE PLANS
 AND SOME ELECTRICAL OUTLETS ARE SHOWN WITH AFCI
 PROTECTION; HOWEVER PLEASE SEE THAT THE SA'S ARE NOT
 CIRCUITED AND NOTE MENTIONS THESE ARE TO BE CIRCUITED
 TO THE KITCHEN/BATH LIGHTING CIRCUITS. THIS WOULD THEN
 REQUIRE ARC FAULT PROTECTION FOR THESE CIRCUIT(S)
 ALSO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE WE ARE UNDER THE 2002 NEC AND REQUIRES AFCI
 PROTECTIONS FOR ALL "OUTLETS" IN BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: OK, HOWEVER PLEASE KNOW AT THIS TIME DUE TO
 THE REVISIONS AND CHANGES IN RISER WHICH WILL BE
 FORTH-COMING THIS NOTE WILL REMAIN.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR PER
 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: NO/OK, PLEASE SEE NEW GROUNDING DETAIL
 MENTIONS FOOTER STEEL WHERE AVAILABLE. PLEASE KNOW THIS
 IS REQUIRED. 250.50
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE NOTE AND VERIFY THE EXISTING/NEW GROUNDING
 ELECTRODE SYSTEM FOR THE NEW SERVICE. 250.50, CWP (IF
 METAL)
 PLEASE SEE 250.66, 310.15B16 FOR MIN SIZE SHALL BE
 1/0.
  
 14) NOTE: NO, PLEASE SEE THE HEAT FOR THE AHU HAS NOW
 BEEN COMPLETELY REVISED TO WHAT IS BEING SHOWN AS
 12.5KW. PLEASE VERIFY THIS. IF THIS IS INDEED THE CASE,
 PLEASE SEE THE SAME CODE SECTION AS PREVIOUSLY GIVEN
 FOR THE MINIMUM OVER CIURRENT PROTECTION TO BE SIZED AT
 125% PER 424.3B.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE VERIFY THE SIZE OF THE HEAT STRIPS AS SHOWN.
 5KW SEEMS LOW FOR THIS SIZE ADDITION. PLEASE KNOW THAT
 THIS IS ONLY A NOTE GIVEN. IF THIS CHANGES AND AS PANEL
 SCHEDULES ARE REQUIRED, PLEASE SEE 424.3B FOR MIN OCP.
  
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
 18) NOTE: OK, FOR THIS COMMENT, HOWEVER SEE #6 ABOVE.
  
 19) NOTE: NO, AS PREVIOUSLY NOTED AND THE NOTE # 3
 ABOVE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE INDICATE THE NEW SERVICE LOCATION ON PLANS.
 PLEASE SEE 240.24, 230.70 ETC.
  
 20) NOTE: OK.
  
 21) NOTE: NO, PLEASE SEE THAT THE ENTIRE PACKAGE OF
 TRUSS PLANS AND LAYOUTS ARE THE SAME AS PREVIOUSLY
 SUBMITTED. PLEASE KNOW THAT THIS IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY THE OTHER TRADE(S).
 ** PLEASE KNOW THAT ONE SET WILL BE RETAINED ALONG WITH
 OTHER RETAINED PLANS. PLEASE CONTACT THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS IF THERE ARE ANY QUESTIONS ON
 THIS MATTER.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE BUILDING REVIEW NOTES, AS THE TRUSS
 ENGINEERING PLANS CONTAIN A RAISED SEAL OVER A "RUBBER
 STAMPED" SIGNATURE WHICH IS NOT PERMITTED UNDER FAC
 61G15-23.002, FS 471.025
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
 24) NOTE:NO, SAME COMMENT, PLEASE SEE THE SECTION
 GIVEN PREVIOUSLY AS THE AMOUNT OF THE RECESSED LIGHTING
 SHALL BE FIGURED INTO THE CALCULATIONS IN ADDITION TO
 THE LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON MAX WATTAGE FOR
 FIXTURE(S). THIS MAY NOTBE FIGURED IN W/ 3W/PER SQ
 FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND.
  
 25) NOTE: NO, PLEASE SEE THIS COMMENT REMAINS THE SAME
 AS THE LOAD ON THE PANEL SCHEDULE WHICH IS NOW
 SUBMITTED STILL EXCEEDS THAT FOR A SMALL APPLIANCE
 CIRCUIT.
 PLEASE SEE THE LOAD CALCULATIONS STILL INDICATE A LOAD
 OF 2500 VA???
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE SMALL APPL CIRCUITS ARE SHOWN AT 2500VA
 WHICH FAR EXCEEDS THE RATING OF A 20A CIRCUIT AND #12
 AWG.
 240.4,310.16, 220, ETC
  
 ***** NEW NOTES ***
  
 26) NOTE: PLEASE SEE THERE ARE SEVERAL ITEMS ON LOAD
 CALCULATIONS WHICH DO NOT CORRELATE WITH THE LOADS ON
 THE PANEL SCHEDULE SUBMITTED.
 PLEASE CORRELATE ALL.
 PLEASE ALSO SEE 408.4 AS THE PANEL SCHEDULE WHICH IS
 NOW SUBMITTED SHALL CONTAIN MORE DETAIL FOR THE
 CIRCUITS BEING SHOWN. PLEASE SEE THE FOLLOWING
 COMMENTARY WHICH IS BEING EXTRACTED DIRECTLY FROM THE
 CODE.
 PANEL SCHEDULES ARE *TO REQUIRE THAT THE IDENTIFICATION
 FOR EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR
 SWITCHBOARD BE LEGIBLE AND CLEARLY STATE THE SPECIFIC
 PURPOSE FOR WHICH THE CIRCUIT IS USED. CIRCUITS USED
 FOR THE SAME PURPOSE MUST BE IDENTIFIED AS TO THEIR
 LOCATION. FOR EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS
 CAN SUPPLY OUTLETS IN THE KITCHEN, DINING ROOM, AND
 KITCHEN COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS "KITCHEN WALL
 RECEPTACLES,'' DINING ROOM FLOOR RECEPTACLE,'' OR
 "KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' CIRCUIT
 DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH ONLY
 "LIGHTS'' OR "OUTLETS'' DO NOT PROVIDE THE SUFFICIENT
 DETAIL REQUIRED BY THIS SECTION.*
  
 27) NOTE: PLEASE SEE OTHER SHEETS INDICATE A
 RECIRCULATION PUMP FOR HOT WATER HOWEVER THE ELECTRICAL
 PLANS DO NOT SEEM TO INDICATE OR SHOW THIS.
 PLEASE COMPLETE AND CORRELATE WITH OTHER SHEETS FOR
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
 310.16, 240.4, ETC (NEC)
  
 28) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, THERE MAY BE FUTURE COMMENTS ON NEXT
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By dpalmer Date 2006-10-31 Time 20:43 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 20:03 Sent To M
Notes
2006-10-31 20:43:13***** UNSAT ****
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 ** THE LATEST CODE IS NOTE YET ADOPTED BY THE STATE.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR
 SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE
 WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE
 IS A FIRE ALARM SYSTEM, THEN THEY WOULD BE SD. PLEASE
 ALSO SEE LOCATIONS SHALL BE INSTALLED PER 11.5.1.1, AND
 11.8.3.
 PLEASE SEE AREAS WHICH CONTAIN A TRAY/VAULTED CEILING ,
 THE SA SHALL BE INSTALLED WITHIN 12" OF THE HIGHEST
 POINT OF A FLAT CEILING AND WITHIN 3' OF THE PEAK ON A
 SLOPED/VAULTED CEILING.
 PLEASE INCLUDE COMPLETE LAYOUT FOR THE EXISTING
 DWELLING FOR SMOKE ALARM?S EITHER EXISTING MEETING THE
 CURRENT CODE OR NEW TO BE INSTALLED. PLEASE SEE FBC
 2004 R313 WHICH REQUIRES ALL TO BROUGHT UP TO CODE.
 PLEASE ADJUST PLANS.
  
 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS
 CALL FOR WHAT APPEARS TO BE A NEW METER/MAIN COMBO, YET
 RISER SHOWS NO MAIN? PLEASE INDICATE THE SIZE OF THE
 NEW MCB.
 230.70, 240.4,310.15B6,310.16,230.71, ETC
  
 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF LOAD
 CALCULATIONS INDICATE EXISTING 200A SERVICE TO REMAIN,
 HOWEVER RISER SHOWS A NEW 400A SERVICE??
 PLEASE CORRELATE.
 FBC ADMIN SECT 106.1.2, 106.3.5.4(8)
  
  
 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO
 BE DONE.
 110.9, 240.12
  
 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE(S) INDICATING
 ALL MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE(S)SHOW ALL OCP DEVICES
 AND CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS.
 PLEASE KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE
 AT THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: PLEASE SEE MISSING GARAGE GFI PER 210.52G,
 210.8A
  
 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA
 PER 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE 110.26 FOR ANY NEW DISCONNECTING
 MEANS FOR MIN CLEARANCES.
 PLEASE SEE UPSTAIRS CLOSET WHICH SHOWS A DISC , YET NO
 EQUIPMENT IS SHOWN.
 440.11,110.26
  
 11) NOTE:. PLEASE SEE WE ARE UNDER THE 2002 NEC AND
 REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN
 BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING/NEW
 GROUNDING ELECTRODE SYSTEM FOR THE NEW SERVICE. 250.50,
 CWP (IF METAL)
 PLEASE SEE 250.66, 310.15B16 FOR MIN SIZE SHALL BE
 1/0.
  
 14) NOTE: PLEASE VERIFY THE SIZE OF THE HEAT STRIPS AS
 SHOWN. 5KW SEEMS LOW FOR THIS SIZE ADDITION. PLEASE
 KNOW THAT THIS IS ONLY A NOTE GIVEN. IF THIS CHANGES
 AND AS PANEL SCHEDULES ARE REQUIRED, PLEASE SEE 424.3B
 FOR MIN OCP.
  
  
 15) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI
 PROTECTED.
  
 16) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHICH
 APPEAR TO CONTAIN NEW WALLS SPACE, YET DO NOT MEET
 210.52 FOR RECEPT SPACING.
 PLEASE ALSO KNOW, RAIL AREAS ARE ALSO CONSIDERED WALL
 SPACE. PLEASE SEE 2FT OR MORE, WITHIN 6FT OF A DOOR
 ETC.
  
 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 106.1.2
  
 17) NOTE: PLEASE SEE EXISTING DWELLING LA
  
 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE
 SHOWN BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 19) NOTE: PLEASE INDICATE THE NEW SERVICE LOCATION ON
 PLANS.
 PLEASE SEE 240.24, 230.70 ETC.
  
 20) NOTE: PLEASE BE SURE TO SEE 410.8 FOR POSSIBLE
 CONFLICT WITH THE CODE FOR RECESSED LIGHTS IN CLOSET.
  
 21) NOTE: PLEASE SEE BUILDING REVIEW NOTES, AS THE
 TRUSS ENGINEERING PLANS CONTAIN A RAISED SEAL OVER A
 "RUBBER STAMPED" SIGNATURE WHICH IS NOT PERMITTED UNDER
 FAC 61G15-23.002, FS 471.025
  
 22) NOTE: PLEASE SEE COVER SHEET MENTIONS "PALM BEACH
 COUNTY", HOWEVER SCOPE OF WORK IS LOCATED IN THE CITY
 OF WEST PALM BEACH.
  
 23) NOTE: PLEASE SEE VALUATIONS ARE BASED ON MINIMUM
 TABLES BASED IN THE FBC AND ADMINISTRATIVE SECTION.
 108.3
 PLEASE SEE POSSIBLE ADJUSTMENT MAY BE MADE.
  
 24) NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 25) NOTE: PLEASE SEE SMALL APPL CIRCUITS ARE SHOWN AT
 2500VA WHICH FAR EXCEEDS THE RATING OF A 20A CIRCUIT
 AND #12 AWG.
 240.4,310.16, 220, ETC
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, THERE MAY BE FUTURE COMMENTS ON NEXT
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-31 20:03:18IN ELEC ON 10/31

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 14:13 Sent To E
Notes
2007-02-05 14:14:32TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 16:18 Sent To Z
Notes
2007-01-31 16:20:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By adarroug Date 2006-10-31 Time 11:03 Rev Time 0.00
Received By adarroug Date 2006-10-31 Time 11:03 Sent To E
Notes
2006-10-31 11:03:51TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-07 Cont ID  
Sent By alange Date 2006-11-07 Time 08:20 Rev Time 0.00
Received By alange Date 2006-10-16 Time 15:28 Sent To  
Notes
2006-10-16 15:28:43TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-06 Cont ID  
Sent By tgordon Date 2007-02-06 Time 15:38 Rev Time 0.25
Received By tgordon Date 2007-02-06 Time 15:38 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 09:28 Rev Time 0.35
Received By tgordon Date 2006-11-01 Time 09:28 Sent To P
Notes
2006-11-01 09:47:33*** DENIED ***
 1) PLEASE SIZE THE SUPPLY AIR DUCT TO THE FIRST FLOOR
 NEAR STAIR CASE, AND SECONDD FLOOR 1 IN THE LOFT AND 2
 IN THE MASTER BEDROOM.
  
 2) PLEASE SIZE THE MAIN SUPPLY AIR DUCT FROM THE AHU TO
 THE MIXING BOX OVER THE MASTER BATH.
  
 3) PLEASE SIZE THE SUPPLY AIR DUCT FROM THE AHU TO THE
 FIRST FLOOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-08 Cont ID  
Sent By mperson Date 2007-02-08 Time 08:10 Rev Time 0.45
Received By mperson Date 2007-02-08 Time 08:10 Sent To B
Notes
2007-02-08 08:17:48 
 ****************PROVISO****************
 A} GENERAL PLUMBING NOTE #17: SLOPE OF HORIZONTAL
 DRAINAGE PIPE PER FBC-2004 PLUMBING, TABLE 704.1.
 B} WATER HEATER THERMAL EXPANSION CONTROL PER FBC-2004
 PLUMBING, SECTION 607.3.
 C}WATER HEATER DETAIL RELIEF VALVE INSTALLATION CODE
 REFERENCE WRONG, CORRECT CODE REFERENCE IS 504.4.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By mperson Date 2006-11-02 Time 14:31 Rev Time 0.45
Received By mperson Date 2006-11-02 Time 14:31 Sent To B
Notes
2006-11-02 15:35:37UNSAT
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE DOUBLE-BOWL ISLAND KITCHEN SINK INDICATED ON
 SHEET P-1 SANITARY RISER DIAGRAM IS NOT CODE COMPLIANT
 PER FBC-2004 PLUMBING, SECTION 913.2 VENT CONNECTIONS:
 PLEASE NOTE THE DETAIL IN RED INK ON SHEET P-1 ADDING
 AN AIR ADMITTANCE VALVE PER FBC-2004 PLUMBING, SEC. 917
 TO MEET CODE COMPLIANCE.
  
 2. THE WASHING MACHINE PIPING INDICATED ON SHEET P-1
 SANITARY RISER DIAGRAM IS NOT CODE COMPLIANT PER
 FBC-2004 PLUMBING, SECTIONS 406.3 , 802.4, 708.9: (A)
 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANPIPE ON RESUBMITTAL.
 (C) 708.9 ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS.
 PLEASE INSTALL CLEANOUT FOR WASING MACHINE AT FOUR FEET
 ABOVE FINNISH FLOOR, 4' A.F.F. PLEASE INDICATE THIS ON
 THE RESUBMITTAL.
  
 3. PLEASE NOTE THAT THE LAUNDRYROOM PLUMBING TO THE
 WASHING MACHINE,SINK AND THE PLUMBING TO THE NEW
 KITCHEN AND SECOND FLOOR MASTER BATH MUST BE PIPED TO
 THE FOLLOWING TO MEET CODE COMPLIANCE AND BE INDICATED
 ON THE SANITARY PLUMBING RISER DIAGRAM AND FIRST FLOOR
 PLUMBING PLAN ON SHEET P-1.
 PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-02-03 Cont ID  
Sent By mmclean Date 2007-02-03 Time 13:54 Rev Time 0.00
Received By mmclean Date 2007-02-03 Time 13:54 Sent To I
Notes
2007-02-03 13:55:06NOTE: PROVISO: 1) PAVERS SHALL BE INSTALLED ON A
 PERVIOUS BASE (I.E. SAND) AND NOT SET IN CONCRETE.
 PAVERS SHALL NOT BE SEALED WITH ANY WATERPROOFING
 MATERIAL SO AS TO MAINTAIN PERVIOUS QUALITY.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By mmclean Date 2006-10-28 Time 08:41 Rev Time 0.00
Received By mmclean Date 2006-10-28 Time 08:41 Sent To I
Notes
2006-10-28 08:43:54DENIED,
 1. PLEASE PROVIDE THE DIMENSION OF EXISTING
 DRIVEWAY/WALKWAY AND PROPOSED DRIVEWAY (LENGTH &
 WIDTH).
  
 NTOE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 2. PLEASE INDICATE IF THE EXISTING & PROPOSED DRIVEWAY
 PAVERS WILL BE JUST SAND BASE (NOT SEALED).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720