| Plan Review Stops For Permit 06100532 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-10-20 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-10-20 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2006-10-20 15:54:25 | RECIEVED SIGNED AND SEALED ENGINEERING FOR ENHANCED | | | FASTENING OF THE DUROLAST ROOF SYSTEM AS REQUESTED IN | | | PROVISO. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-10-20 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-10-20 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2006-10-20 10:34:39 | BUILDING PROVISO | | | PREINSPECTION OF EXISTING ROOFING WAS COMPLETED BY KEN | | | CONRAD ON 10/20/06. | | | | | | 1) AN ORIGINAL SIGNED AND SEALED COPY OF THE RAS 137 | | | CALCULATIONS FOR ENHANCED FASTENING OF THE DUROLAST | | | ROOF SYSTEM MUST BE RECIEVED BEFORE THE PERMIT CAN BE | | | FINALED. |
|
|
|