Plan Review Details - Permit 06100520
Plan Review Stops For Permit 06100520
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 10:09 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 10:09 Sent To PC
Notes
2006-10-16 10:10:25ATTACH PERMIT TO EXT #0004 CREATED FOR UNIT 401
2006-10-13 14:57:14NEED AN EXTENSION FOR # 401 FOR THIS ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-11-01 Cont ID  
Sent By alange Date 2006-11-01 Time 08:02 Rev Time 0.00
Received By alange Date 2006-11-01 Time 08:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 12:30 Sent To  
Notes
2006-10-24 12:41:01REDLINED PLANS.
  
 PLEASE SEE AS THIS IS A NEW TEANT BLD OUT, THE EXISTING
 SERVER/PHONE ROOM AND BREAK ROOM LIGHTING DEVICES FOR
 CONTROL OF LTS WILL BE REQUIRED TO BE CHANGED OUT.
 PLEASE SEE THIS WAS REDLINED ON PLANS AND THERE IS NO
 NEED FOR PLANS TO BE REVISED.
 13-415.1.ABC.1.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 16:03 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 15:55 Sent To  
Notes
2006-10-26 16:03:261. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
 3. THE EXISTING FIRE DAMPERS DECLARED ON THE PLANS
 SHALL BE INSPECTED TO ENSURE THAT NO ABNOMALITIES
 EXIST.
 4. INTERIOR FINISH CLASSIFICATIONS SHALL COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS. SEE PLAN NOTE ON
 SHEET T.
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR
 MODIFICATIONS FOR THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-01 Cont ID  
Sent By alange Date 2006-11-01 Time 08:02 Rev Time 0.00
Received By alange Date 2006-10-14 Time 17:56 Sent To  
Notes
2006-10-23 13:39:14TO "BOB"#14
2006-10-14 17:57:11WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-25 Cont ID  
Sent By tgordon Date 2006-10-25 Time 08:42 Rev Time 0.30
Received By tgordon Date 2006-10-25 Time 08:42 Sent To  
Notes
2006-10-25 08:49:46*** PROVISO ***
 1) IF NO FIRE DAMPERS ARE LOCATED IN THE TWO HEAT DUCTS
 WERE PENETRATING THE FIRE WALLS, THEN FIRE DAMPERS NEED
 TO BE INSTALLED, PER 2004 FBC/M 607.5.3, OR COMPLY WITH
 2004 FBC/M
 607.5.3 EXCEPTIONS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  