Plan Review Details - Permit 06100509
Plan Review Stops For Permit 06100509
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-31 Cont ID  
Sent By lmartine Date 2007-08-31 Time 12:30 Rev Time 0.00
Received By lmartine Date 2007-08-31 Time 12:30 Sent To  
Notes
2007-08-31 12:30:55DECK REVISION APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By rnuquist Date 2006-12-20 Time 05:53 Rev Time 0.00
Received By rnuquist Date 2006-12-20 Time 05:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-11-05 Cont ID  
Sent By rnuquist Date 2006-11-05 Time 18:12 Rev Time 0.00
Received By rnuquist Date 2006-11-05 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-31 Cont ID  
Sent By btrobaug Date 2007-07-31 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2007-07-31 Time 08:36 Sent To B
Notes
2007-07-31 08:59:44 
 TO LUIS INPILE./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By btrobaug Date 2006-12-08 Time 07:46 Rev Time 0.33
Received By btrobaug Date 2006-12-08 Time 07:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-26 Cont ID  
Sent By btrobaug Date 2006-10-26 Time 07:45 Rev Time 0.33
Received By btrobaug Date 2006-10-26 Time 07:36 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 15:34 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 15:34 Sent To Z
Notes
2007-07-27 15:35:04TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 09:17 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 09:17 Sent To E
Notes
2006-12-06 09:17:41TO "BTROBAUG" DESK/RESUB/NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:33 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:33 Sent To Z
Notes
2006-11-29 17:32:58SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-25 Cont ID  
Sent By mmiller Date 2006-10-25 Time 18:03 Rev Time 0.00
Received By mmiller Date 2006-10-25 Time 18:03 Sent To E
Notes
2006-10-25 18:04:14SENT TO E BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2006-11-05 Cont ID  
Sent By rnuquist Date 2006-11-05 Time 18:12 Rev Time 0.00
Received By rnuquist Date 2006-10-14 Time 17:29 Sent To  
Notes
2006-10-14 17:29:42TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By mperson Date 2006-12-08 Time 09:38 Rev Time 0.33
Received By mperson Date 2006-12-08 Time 09:38 Sent To B
Notes
2006-12-08 09:42:24 
 *************PROVISO***************
 A) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 B) FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By mperson Date 2006-10-27 Time 11:00 Rev Time 0.33
Received By mperson Date 2006-10-27 Time 11:00 Sent To B
Notes
2006-10-27 11:30:01UNSAT
 REFERENCE: FBC-2004 SEC. 424.2 OR RFBC-2004 SEC. R4101
 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAIALS, OR SUBMITTALS TO
 REFLECT THE FOLLOWING INFOMATION REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS. (ADD TO NOTES)
  
 2) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPER- ATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.(DETAIL
 REQUIRED OR ADD MAKE AND MODEL NUMBER TO PRINTS)
  
 3) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 4) FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (ADD TO NOTES)
  
 5) FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING.(ADD TO
 NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-30 Cont ID  
Sent By adavila Date 2007-07-30 Time 09:10 Rev Time 0.00
Received By adavila Date 2007-07-27 Time 08:17 Sent To E
Notes
2007-07-30 09:10:24PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-03 Cont ID  
Sent By mmclean Date 2006-12-03 Time 23:25 Rev Time 0.00
Received By mmclean Date 2006-12-03 Time 23:25 Sent To I
Notes
2006-12-03 23:27:09NOTE: THE PROPOSED POOL EQUIPMENT SHALL NOT BE CLOSER
 THAN 9.4FTFROM REAR PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-25 Cont ID CPC023568
Sent By adavila Date 2006-10-25 Time 15:23 Rev Time 0.00
Received By adavila Date 2006-10-16 Time 10:19 Sent To I
Notes
2006-10-25 15:24:5610/25/2006 - PLANNING AND ZONNING ***FAILED***
  
 1) PROVIDE SETBACK FROM PROPERTY LINE TO POOL
 EQUIPMENT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA, PLANNER,
 AT 822-1435.