Plan Review Details - Permit 06100489
Plan Review Stops For Permit 06100489
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By mjacobs Date 2007-01-19 Time 14:15 Rev Time 0.00
Received By mjacobs Date 2007-01-19 Time 14:04 Sent To PC
Notes
2007-01-19 14:15:01PROVISOR :
 BE AWARE THE OCCUPANCY OF THE NEW AREA NEXT TO UNITS
 201 AND 202 CAN AFFECT THE FIRE RATING OF THE NEW
 DEMISING WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-03 Cont ID  
Sent By mjacobs Date 2007-01-03 Time 07:00 Rev Time 0.00
Received By mjacobs Date 2007-01-03 Time 06:05 Sent To PC
Notes
2007-01-03 06:56:27PROVISOR :
 BE AWARE THE OCCUPANCY OF THE NEW AREA NEXT TO UNITS
 201 AND 202 CAN AFFECT THE FIRE RATING OF THE NEW
 DEMISING WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By amorse Date 2006-10-24 Time 12:04 Rev Time 0.00
Received By amorse Date 2006-10-24 Time 12:04 Sent To  
Notes
2006-10-24 12:22:06 
  
 DENIED
  
 1) A DESIGN PROFESSIONAL THAT IS REGISTERED TO PRACTICE
 UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004
  
 2) PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 3) PROVIDE OCCUPANCY OF NEW AREA BESIDE UNIT 201-202
 THAT HAS BEEN CREATED BY INSTALLATION OF DEMISING WALL
  
 4) ST LUCIE HOME DESIGN DOES NOT MEET THE REQUIREMENTS
 FOR THE EXEMPTIONS FROM LICENSURE AS AN ARCHITECT UNDER
 FLORIDA STATUTE 481.229 AS THIS BUILDING IS INTENDED
 FOR PUBLIC USE BY BEING ACCESSIBLE TO THE GENERAL
 PUBLIC.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By dpalmer Date 2007-01-19 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2007-01-19 Time 07:28 Sent To B
Notes
2007-01-19 07:44:03NO NEW ELECTRICAL IS BEING INSTALLED, ALL ELECTRICAL
 FROM EACH PROPOSED TENANT SHALL NOT CROSS INTO OTHER
 SPACES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 12:10 Sent To  
Notes
2006-12-17 12:29:47*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
  
 ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS
 FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE
 SEE THE COMMENTS BELOW ARE BASED ON THE PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS
 PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING
 SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S)
 PLEASE SEE SCOPE OF WORK PREVIOUSLY SUBMITTED INDICATED
 WALL BEING CLOSED IN TO CREATE SEPARATE SPACES, HOWEVER
 THESE PLANS SUBMITTED NOW INDICATE ANEW TENANT
 SEPARATION WALL AT A DIFFERENT LOCATION?
 PLEASE PROVIDE CIRCUITING ON HOW THE OTHER EXISTING
 SPACE IS BEING FED.
 PERMIT DESCRIPTION INDICATES INSTALLATION OF NEW WALL
 BETWEEN TWO SPACES.
 PLEASE SEE FBC CHAPTER 13 IF NEW TENANT SPACE IS BEING
 CREATED.
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.2.1.ABC.1
 408.4, 310.16,
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 .
 PLEASE KNOW THERE IS MISSING INFORMATION WHICH CAN NOT
 DETERMINE CODE COMPLIANCE AT THIS TIME.
  
 2) NOTE: PLEASE SEE PANEL WHICH IS BEING SHOWN IN WHAT
 APPEARS TO BE A STORAGE CLOSET.
 PLEASE SEE 110.26,408.7, 240.24, AS THIS IS NOT
 PERMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 12:43 Sent To  
Notes
2006-10-24 12:53:12*****UNSAT ********
  
 1) NOTE: PLEASE SEE PLANS ARE REQUIRED TO BE DONE ABY A
 LICENSED PROFESSIONAL UNDER FS 481 OR 471. PLEASE SEE
 HOME DESIGN COMPANY MAY NOT DESIGN SCOPE OF WORK PER
 481.229(1)(C).
  
 PLEASE SEE PLANS ALSO CONTAIN A PHOTO-COPY OF WHAT
 APPEARS TO BE A SIGNATURE FROM AN ENGINEER AND ALSO
 CONTAINS A TITLE BLOCK FOR THE SAME SAID DESIGNER,
 HOWEVER PLANS ARE SIGNED, DATED OR SEALED BY THE SAID
 DESIGNER AS REQUIRED UDNER FS 471.025, FAC
 61G15-23.002
  
 2) NOTE:PLEASE SEE NOW THAT THE SPACE IS BEING SLIT
 UP INTO TWO SEPARATE SPACES, PLEASE INDICATE THE
 CIRCUITINGS FOR THE NEW ELECTRICAL AS SHOWN AND HOW
 THESE WILL BE SEPARATED.
 ONE SPACE PANEL MAY NOT FEED ANOTHER.
 210.25.408.4, 310.16 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By mawillia Date 2007-01-19 Time 13:56 Rev Time 0.00
Received By mawillia Date 2007-01-19 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 10:26 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 10:25 Sent To  
Notes
2006-12-26 10:28:23*****APPROVED******
  
  
 FIRE TO STAMP AND SIGN WHEN ALL PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mcarsill Date 2006-10-26 Time 15:11 Rev Time 0.00
Received By mcarsill Date 2006-10-26 Time 15:11 Sent To  
Notes
2006-10-26 15:13:211. THE PLANS APPEAR TO BE OKAY BUT A PROBLEM EXISTS
 WITH THE COPYING OF THE PLANS AND INK NOTATIONS MADE TO
 THE PLANS. PLEASE FOLLOW GUIDLINES FROM THE
 CONSTRUCTION SERVICES DEPARTMENT.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 09:58 Sent To E
Notes
2007-01-18 09:59:29TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 09:58 Sent To  
Notes
2006-12-14 16:57:17TO "BOB"#12
2006-12-01 09:58:58WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-26 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 09:34 Sent To  
Notes
2006-10-24 09:15:17TO "BOB"#6
2006-10-16 09:35:34WAITING FOR "BOB"