| 2006-10-27 20:43:52 | *** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEEVALUE FOR COMPLETE SCOPE OF WORK |
| | SHALL BE ADJUSTED OR ONE WILL BE ADJUSTED USING THE |
| | MARSHALL'S & SWIFT GUIDE AS ADOPTED INTO CHAPTER 1, OF |
| | THE 2004 FBC . |
| | PLEASE SEE 108.3, WHICH REQUIRES VALUE TO INCLUDE ALL |
| | LABOUR AND MATERIALS, EVEN IF ANY MATERIALS OR |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | |
| | 2) NOTE; PLEASE SEE PLANS SUBMITTED SHALL BE DONE BY AN |
| | ENGINEER, SIGNED, DATED AND SEALED WITH APPROPRIATE |
| | TITLE BLOCKS AS REQUIRED PER FBC ADMIN SECT105.3.1.2. |
| | PLEASE ALSO SEE FAC 61G15-23.002, FS 471.025 AND |
| | 471.023 IF APLICABLE. |
| | |
| | 3) NOTE: PLEASE INDICATE ALL AREAS AND MINIMUM CANDELA |
| | LEVELSAND ALL MINIMUM AUDIBLE LEVELS PER FBC 11-4.28, |
| | 11-4.28.2, 11-4.28.3(4). |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |