Plan Review Details - Permit 06100473
Plan Review Stops For Permit 06100473
Review Stop AD ADDRESSING
Rev No 3 Status N Date 2007-01-09 Cont ID  
Sent By lursu Date 2007-01-09 Time 16:14 Rev Time 0.00
Received By lursu Date 2007-01-09 Time 16:14 Sent To  
Notes
2007-01-09 16:14:57THE JOB LOCATION IS AT UNIT 100. PERMIT MUST BE
 ASSIGNED TO THIS ADDRESS 770 NORTHPOINTE PKWY # 100.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By lursu Date 2006-10-30 Time 08:06 Rev Time 0.00
Received By lursu Date 2006-10-30 Time 08:06 Sent To  
Notes
2006-10-30 08:07:19THE ADDRESS ON THE APPLICATION DOES NOT CORRELATE WITH
 THE ADDRESS ON THE SITE PLANS; ON THE APPLICATION IS
 UNIT 200 AND SITE PLANS SHOW UNIT 100.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-11-20 Cont ID  
Sent By lursu Date 2006-10-16 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2006-10-16 Time 10:34 Sent To PC
Notes
2006-10-16 10:34:50EXT #0002 WAS CREATED FOR UNIT 200.ATTACH PERMIT
2006-10-13 09:12:41NEED AN EXTENSION # 200 FOR THIS ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 07:26 Rev Time 0.77
Received By jwitmer Date 2007-01-11 Time 07:26 Sent To  
Notes
2007-01-11 07:27:11NEEDS NOTICE OF COMMENCEMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By jwitmer Date 2006-11-20 Time 14:19 Rev Time 1.11
Received By jwitmer Date 2006-11-20 Time 13:51 Sent To  
Notes
2006-11-20 14:33:10BUILDING PLAN REVIEW
 PERMIT: 06100473
 ADD: 770 NORTHPOINT PARKWAY #200
 CONT: BRICAR ENTERPRISES
 TEL: (561)954)675-1976
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) DISCREPANCY, THE PLANS INDICATE WORK TO BE COMPLETED
 UNDER THIS PERMIT AS SUITE
 # 100WHERE AS THE PERMIT APPLICATION INDICATES SUITE#
 200.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G)THE 2004 EXISTING BUILDING CODE, WHAT LEVEL OF
 ALTERATION
 IS BEING COMPLETED UNDER THIS PERMIT?
  
 5) THE FIRE ALARM PERMIT WILL REQUIRE SEPERATE PLANS
 FOR THIS PERMIT. UNDER 106.3.5*
 THE MINIMUM PLAN CRITERIA FOR BUILDING REVIEW 106.3.5
 (6)*LIFE SAFETY
 AND 106.3.5(7) * EGRESS REQUIREMENTS THESE DOCUMENTS
 MUST BE MAINTAINED
 IN THE BUILDING PERMIT. TWO SEPERATE SETS OF FIRE ALARM
 PLANS
 WILL BE REQUIRED FOR THE FIRE ALARM PERMIT.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By dpalmer Date 2007-01-09 Time 08:56 Rev Time 0.00
Received By dpalmer Date 2007-01-09 Time 08:02 Sent To  
Notes
2007-01-09 08:59:09***REDLINED TITLE BLOCKS ON ELECTRICLA SHEETS.,
 RESPONSE LETTER MENTIONS THE SUITE # OF 100 IS THE
 CORRECT #, HOWEVER PLANS INDICATE SUITE # 101. CHANGED
 TO SUITE #100 ON TITLE BLOCKS ON ELECTRICAL SHEETS AS
 THIS IS WHAT RESPONSE MENTIONS, RESUB SHEET CONTAINS
 AND PERMIT APPLICATION HAS.
2007-01-09 08:02:25IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 20:09 Sent To  
Notes
2006-10-27 20:28:58*** UNSAT ***
  
  
 *** PLEASE SEE PLANS CALL FOR SUITE #100 , YET PERMIT
 APPLICATION HAS SUITE #200. PLEASE CORRELATE AND
 CONTACT THE ADDRESSING REVIEWER AS THESE DO NOT
 CORRELATE AND THIS REVIEWER HAS GRANTED AN EXTENSIONOF
 #200. IF INDEED SUITE #200, PLEASE ADJUST ALL TITLE
 BLOCKS AS REQUIRED PER FAC 61G16, 61G15
  
 1) NOTE: PLEASE BE SURE PLANS LIST THE CURRENT RELEVANT
 CODES ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101.
 PLEASE ALSO LIST THE 2004 FBC.
  
 2) NOTE: PLEASE CLARIFY THE LOADS AS SHOWN AND ANY
 CONTINUOUS LOADS ARE ALREADY FIGURED AT 125% OR ADJUST
 AND SHOW AS NEEDED.
 215.3,230.42 ETC.
  
 3) NOTE: PLEASE SEE NEC 605.
 PLEASE STATE THE FOLLOWING ON PLANS.
 (C) RECEPTACLE OUTLETS, MAXIMUM. INDIVIDUAL PARTITIONS
 OR GROUPS OF INTERCONNECTED INDIVIDUAL PARTITIONS SHALL
 NOT CONTAIN MORE THAN THIRTEEN 15-AMPERE, 125-VOLT
 RECEPTACLE OUTLETS.
 (D) MULTIWIRE CIRCUITS, NOT PERMITTED. INDIVIDUAL
 PARTITIONS OR GROUPS OF INTERCONNECTED INDIVIDUAL
 PARTITIONS SHALL NOT CONTAIN MULTIWIRE CIRCUITS. PLEASE
 ALSO STATE ALL FURNITURE SHALL BE IN PLACE OR WILL BE
 REQUIRED TO BE DONE UNDER A SEPARATE PERMIT . PERMIT
 MUST BE APPLIED FOR BEFORE FINAL OF UNIT ONLY IF
 FURNITURE IS NOT INSTALLED BEFORE FINAL AND DURING THIS
 CONSTRUCTION.
  
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
 ** PLEASE ALSO KNOW, DU E TO SCOPE OF WORK AT THIS
 TIME, FBC 2004 CHAPTER 13 DOES NOT APPLY BASED ON
 FACTORS AS SHOWN, HOWEVER IF SCOPE DOES INCREASE,
 CHAPTER 13 REQUIREMENTS MAY BE REQUIRED.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By mawillia Date 2007-01-11 Time 11:45 Rev Time 0.00
Received By mawillia Date 2007-01-11 Time 11:44 Sent To  
Notes
2007-01-11 11:51:26*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE REVIEW OF 12/08/07 HAVE
 BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-08 Cont ID  
Sent By mawillia Date 2006-12-08 Time 11:52 Rev Time 0.00
Received By mawillia Date 2006-12-08 Time 11:28 Sent To  
Notes
2006-12-08 12:22:25*****DENIED*****
  
  
  
 1.THE SUITE NUMBER LOCATED IN THE TITLE BLOCK OF THE
 SUBMITTED PLAN IS INCORRECT.SUITE 200 SHOULD BE USED
 NOT 100.
  
 2.NFPA 101 - 2003 EDITION - AND THE FLORIDA FIRE
 PREVENTION CODE -2004 EDITION- SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION ACTIVITIES SHALL COMPLY WITH NFPA 241.
  
 4.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST,
 AND DEBRIS SHALL BE REMOVED FROM THE STRUCTURE DAILY
 AND ITS IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 5.INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS AND
 EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 6.IF THE SCOPE OF THE WORK REQUIRES MODIFICATION OF
 THE SPRINKLER SYSTEM, SEPARATE PLANS AND PERMIT ARE
 REQUIRED.
  
 7.THE SUITE NUMBER IS MISSING IN THE TITLE BLOCK ON
 DRAWING FA 0.1 AND FA 1.0.
  
 8.ALL PLANS SUBMITTED UNDER THE MASTER SHALL HAVE THE
 PROPER SEAL AND SIGN AS PER FLORIDA ADMISTRATIVE
 CODES.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 15:43 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 15:43 Sent To  
Notes
2007-01-08 09:31:24TO "COMM" BD#24
2006-12-17 15:43:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-08 Cont ID  
Sent By lmartine Date 2006-12-08 Time 14:49 Rev Time 0.00
Received By lmartine Date 2006-10-14 Time 16:29 Sent To  
Notes
2006-10-24 16:02:35TO "COMM" BD#41
2006-10-14 16:30:39WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 10:45 Rev Time 0.25
Received By tgordon Date 2006-10-31 Time 10:45 Sent To  
Notes
***NONE***