Plan Review Details - Permit 06100451
Plan Review Stops For Permit 06100451
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By mjacobs Date 2006-11-01 Time 18:32 Rev Time 0.00
Received By mjacobs Date 2006-11-01 Time 17:45 Sent To PC
Notes
2006-11-01 18:32:40 
  
 1)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)MORE DETAILS IS REQUIRED FOR THE CONSTRUCTION TO
 THE NEW FENCE.ARETHE COLUMNSCONCRETE BLOCKS
 /POURED CONCRETE OR STONE?WHAT TYPE OF MATERIAL WILL
 BE BETWEEN THE COLUMNS? IS IT CONCRETE BLOCKS/ALUMINUM
 OR WOOD? WHERE IS THE FOUNDATION DETAIL FOR THE
 COLUMNS.SHOW THE LAYOUT OF THE STEEL FOR THE COLUMNS
 AND IF CONCRETE BLOCKS WILL BE SHOW THE LOYOUT OF THE
 STEEL ALSO.INDICATETHERE WILL BE ANY FILL CELLS IN
 BETWEEN THE COLUMNS.
  
 3)2121.8.1
 MASONRY FENCES SO LOCATED ON A PROPERTY THAT SUCH FENCE
 , AT THE PROPOSED HEIGHT OR BY A FUTURE ADDITION TO
 HEIGHT, COULD BE USED AS A WALL OF A BUILDING SHALL BE
 CONSTRUCTED WITH FOUNDATIONS AND TIE COLUMNS AS
 PROVIDED FOR AN EXTERIOR WALL. SUCH FENCE SHALL BE
 CAPPED WITH A COPING BEAM NOT LESS THAN 64 SQUARE
 INCHES (.4 M 2 ) IN CROSS-SECTION REINFORCED WITH A
 MINIMUM OF TWO #4 RODS, WHEN NOT EXCEEDING A HEIGHT OF
 5 FEET (1.5 M), OR SHALL BE CAPPED BY A TIE BEAM AS
 PROVIDED FOR EXTERIOR WALLS IF EXCEEDING A HEIGHT OF 5
 FEET (1.5 M).
  
 4)2121.8.2.1
 FENCES NOT EXCEEDING 5 FEET (1.5 M) IN HEIGHT SHALL BE
 8 INCHES (203 MM) THICK AND SHALL NOT BE REQUIRED TO
 HAVE TIE COLUMNS, BUT SHALL BE REQUIRED TO HAVE A
 COPING AS PROVIDED HEREIN; OR SUCH FENCES MAY BE 4
 INCHES (102 MM) THICK WITH TIE COLUMNS AND COPING NOT
 LESS THAN 8 INCHES (203 MM) THICK.
  
 5) 1609.1.3STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHOREDTO RESIST WIND-INDUCED
 OVERTURNING,UPLIFT AND SLIDING AND TO PROVIDE CONTINOUS
 LOAD PATHS FOR THESE FORCES TO THE FOUNDATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-10-12 Cont ID  
Sent By ssherman Date 2006-10-12 Time 14:06 Rev Time 0.00
Received By ssherman Date 2006-10-12 Time 14:06 Sent To  
Notes
2006-10-12 14:06:33HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By adarroug Date 2006-10-17 Time 16:53 Rev Time 0.00
Received By adarroug Date 2006-10-17 Time 16:53 Sent To B
Notes
2006-10-17 16:54:09TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-11-01 Time   Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:10 Sent To  
Notes
2006-10-14 16:10:59TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By kdfreema Date 2006-10-16 Time 09:54 Rev Time 0.00
Received By kdfreema Date 2006-10-16 Time 09:53 Sent To  
Notes
***NONE***