Plan Review Details - Permit 06100214
Plan Review Stops For Permit 06100214
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-22 Cont ID  
Sent By lursu Date 2008-02-22 Time 16:30 Rev Time 0.00
Received By lursu Date 2008-02-22 Time 16:29 Sent To  
Notes
2008-02-22 16:34:39THE JOB LOCATION IS AT 3624 GEORGIA AVE , CONVERSATION
 WITH THE PROJECT ARCHITECT , ANDY SHARE.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-21 Cont ID  
Sent By lmartine Date 2008-03-21 Time 16:43 Rev Time 0.00
Received By lmartine Date 2008-03-21 Time 16:43 Sent To  
Notes
2008-03-21 16:44:32REVISION FOR BUILDING TYPEOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-02-22 Cont ID  
Sent By jwitmer Date 2008-02-22 Time 08:17 Rev Time 1.22
Received By jwitmer Date 2008-02-22 Time 08:16 Sent To PC
Notes
2008-02-22 08:38:08BUILDING PLAN REVIEW
 PERMIT: 06100214
 ADD: 3624 GEORGIA AV
 CONT: INDUSTRIAL COMMERCIAL STRUCTURES, INC
 TEL: (561)472-0563
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)THERE SEEMS TO BE A QUESTION AS TO THE ADDRESSOF
 THE TENANT LOCATION, THE PLUMBING INSPECTOR HAS NOTED
 THIS DURING INSPECTION AS WELL AS THE SUBMITTAL HAVING
 A DIFFERENT ADDRESS AS OF THE REVISION? 106.1.2.
 ADDITIONAL INFORMATION REQUIRED. IF A CHANGE OF ADDRESS
 IS TO BE REQUIRED PLEASE CONTACT LACRAMIOARA (LILLY)
 URSA AT 822-1239.
  
 2) A-0.0 MINIMUM BUILDING TYPE IS DECLARED AS A TYPE IV
 (HEAVY TIMBER) WHILE THE NEXT LINE BELOW THE EXTERIOR
 WALLS ARE CMU. PLEASE PROVIDE THE MINIMUM BUILDING TYPE
 SEE TABLE
 503 & TABLE 601.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By jwitmer Date 2008-01-07 Time 13:51 Rev Time 1.11
Received By jwitmer Date 2008-01-07 Time 13:51 Sent To PC
Notes
2008-01-07 13:54:28REVISION# 2 12-31-07 ADD LOW WALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 10:20 Rev Time 1.22
Received By jwitmer Date 2007-03-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By jwitmer Date 2006-11-17 Time 14:28 Rev Time 3.33
Received By jwitmer Date 2006-11-17 Time 14:27 Sent To  
Notes
2006-11-17 15:14:32BUILDING PLAN REVIEW
 PERMIT: 06100214
 ADD: 3654 GEORGIA AVE.
 CONT: INDUSTRIAL COMMERCIAL STRUCTURES
 TEL: (407)9484395
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 )FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE PROVIDE A SITE PLAN PROVIDING THISTENANT
 LOCATION WITHIN THE BUILDING.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 4) SHEET A-0.0 CODE SUMMARY INDICATES
 THE PLANS WERE DESIGNED TO THE 2001
 FBC. ALL REFRENCES TO CODE SECTIONS ALSO
 REFLECT THE DESIGN TO THE 2001FBC.
 OCT. 1, 2005 ALL PERMIT APPLICATIONS SUBMITTED
 ON THIS OR AFTER ARE TO BE DESIGNED TO THE
 2004 FBC, BUILDING & 2004 EXISTING BUILDING CODE.
 PLEASE CORRECT DESIGN TO THE 2004 FBC AND ALL CODE
 REFRENCES ARE TO REFLECT THE 2004 FBC.
  
 5) 2004 EXISTING BUILDING CODE PLEASE PROVIDE TO WHAT
 LEVEL
 OF ALTERATIONS WILL BE COMPLETED UNDER THIS PERMIT?
  
 6A)SHEET A8.1 SPECIFICATIONS INDICATE THIS DESIGN
 UNDER
 THE 2001 FBC, PLEASE CORRECT TO THE 2004 FBCAND THE
 WRONG ADDITION OF ASCESHOULD READ ASCE 7-02.
  
 6B) THE BUILDING CATEGORY LISTED AS I, THIS WOULD BE
 FOR
 FARM OUT BUILDINGS SMALL SHEDS.
  
 6C) PREMANUFACTUREDA/C STANDS REQUIRE, (2) COPIES:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PRODUCTS WILL REQUIRE FLORIDA COVERSHEET AND ASSOCIATED
 REPORT.
  
 6D))W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) PLANS DO NOT PROVIDE A SEATING ARANGEMENT FOR
 ACCESSIBILITY.
 PLEASE SHOW COMPLIANCE AND FOR11-5.2 COUNTERS AND
 BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
  
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED
 ON STOOLS OR STANDING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE
 PROVIDED
 IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 8) CHANGE OF OCCUPANCY WILL REQUIRE IMPACT FESS REVIEW:
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 19:20 Sent To  
Notes
2008-03-04 19:20:45REV #8, E6.1

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-30 Cont ID  
Sent By dpalmer Date 2007-12-30 Time 13:48 Rev Time 0.00
Received By dpalmer Date 2007-12-30 Time 13:48 Sent To  
Notes
2007-12-30 13:48:28REV 3.1 AND 6.1

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 09:15 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-27 Cont ID  
Sent By dpalmer Date 2007-07-27 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2007-07-27 Time 14:44 Sent To  
Notes
2007-07-27 14:59:35*** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW,
 PLEASE CORRELATE THE LIGHTING AND METHODS OF CONTROLS
 FOR LIGHTING ON THE ENERGY CALCULATIONS WITH PLANS.
 PLEASE SEE THE PLANS SHOW AUTOMATED CONTROLS FOR ALL
 LIGHTING, HOWEVER THE INPUT DATA REPORT SHOWS *MANUAL
 ON/OFF* FOR TWO OF THE FIXTURES FOR BATHROOMS? THIS IS
 NOT POSSIBLE.
 PLEASE ALSO SEE THE NEW ENERGY CALCULATIONS SUBMITTED
 ARE UNDER THE NEW CODE DATED AS OF DECEMBER 8TH, 2006.
 THIS PROJECT IS UNDER THE PREVIOUS CODE REVISIONS TO
 THE 2004 FBC WHICH REQUIRES THE RELEVANT ENERGY
 CALCULATIONS AT THE TIME OF PERMIT APPLICATION.
 PLEASE SEE THIS WOULD BE VERSION 2.11AS ADOPTED BY THE
 2004 FBC W/2005 REVISIONS.
 PLEASE KNOW THIS WAS CONFIRMED WITH THE STATE AND
 BUILDING OFFICIAL. MAY NOT SUBMIT ENERGY CALCULATIONS
 FROM ONE CODE AND PLANS FROM ANOTHER CODE EVEN IF THE
 NEW ENERGY CODE IS MORE RESTRICTIVE.
 13-415.1.A
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES
 SPECIFICALLY NOTED FOR ELECTRICAL PLANS TO BE SIGNED BY
 THE ENGINEER OF RECORD AS ON FILE. PLEASE SEE ONLY THE
 NEW REVISED SHEET E2.1 CONTAINS THE SIGNATURE AS
 RECOGNIZED AND AS ON-FILE WITH THE CITY OF WEST PALM
 BEACH.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 11:14 Sent To  
Notes
2007-06-20 12:01:37*** UNSAT 3RDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF
 FIXTURES, THE WATTAGE FOR FIXTURES. PLEASE SEE THE
 PLANS DO NOT INDICATE ANY FIXTURE LEGEND FOR THE
 FIXTURES AND WATTAGE FOR EACH. PLEASE SEE FIXTURES ON
 ENERGY CALCULATIONS INDICATE COMPACT FLUORESCENT WHICH
 IS NOT CLEAR WHEN THE MAJORITY OF THE FIXTURES ON PLANS
 ARE 2X4 LAY-IN FIXTURES.
 PLEASE PROVIDE INFORMATION FOR THESE FIXTURE TYPES AND
 BE SURE TO COORDINATE WITH CALCULATIONS.
 PLEASE BE SURE THE OWNER AGENT IS ISGNED ON SHEETS FOR
 VERIFICATION.13-103.1, 13-415.1.AB.1.1
  
 2) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK WAS NOT ADJUSTED BY THE CONTRACTOR. PLEASE SEE FBC
 108.3 AS ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST
 FOR ARCHITECTURAL AND ENGINEERING ETC.
 THE VALUE AS SUBMITTED IS TOO LOW AND IF AN APPROPRIATE
 VALUE IS NOT INDICATE, ONE WILL BE ASSESSED BY GUIDES
 ADOPTED BY THE FBC.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOT SIGNED
 WITH SIGNATURE ON FILE AND RECOGNIZED BY THIS OFFICE.
 FS 471.025
  
 4) NOTE: PLEASE SEE THAT SETS NEED TO BE SUBMITTED WITH
 ALL SHEETS ATTACHED INTO SETS FOR REVIEW AND STAMPING
 AS PREVIOUSLY STATED IN EACH OF THE PREVIOUS REVIEWS.
 PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE BE SURE THESE
 ARE BOUND IN SOME MANOR.
 SETS WERE PLACED AND ATTACHED TOGETHER BY THIS REVIEWER
 HOWEVER WILL NOT BE DONE IF PLANS ARE SUBMITTED THE
 SAME WAY FOR THE NEXT REVIEW.
 FBC 106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 10:46 Sent To  
Notes
2007-03-04 11:44:50** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THAT SOME NOTES ARE FROM THE PREVIOUS
 REVIEW STILL ARE IN NEED OF ADDRESSING.
 PLEASE SEE THERE ARE MANY NEW NOTES AS SCOPE OF WORK
 FOR ELECTRICAL HAS COMPLETELY CHANGED.
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR CHAPTER 13 STILL
 NEEDS TO BE CLARIFIED. PLEASE SEE CALCULATIONS
 SUBMITTED DO NOT CORRELATE WITH LIGHTING AS SHOWN ON
 PLANS OR CONTROL FOR SUCH LIGHTING.
 PLEASE SEE PREVIOUS ENERGY CALCULATIONS SUBMITTED AS
 ONLY ONE FIXTURE IS BEING SHOWN AND *MANUAL ON/OFF *.
 PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES.
 PLEASE INDICATE MAXIMUM LIGHTING POWER ALLOWANCES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. 13-415.2.
 ETC
  
 2) NOTE: PLEASE SEE NEW SERVICE RISER AND PLEASE
 CORRELATE ALL EQUIPMENT. SOME SHOWN AS 2400AMPS,
 2500AMPS ETC?
 FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE THE MSBA AND RISER AS SHOWN COULD
 HAVE POWER FROM BOTH THE UTILITY AND BACK UP POWER
 SOURCE.
 PLEASE SEE PLANS NOW INDICATE A NEW SWITCH BOARD
 OUTSIDE WHICH DOES NOT PROVIDE THE INADVERTENT
 CONNECTION OF THE EQUIPMENT INSIDE.
 PLEASE KNOW THAT A KIRK KEY INTERLOCK WILL NOT PROVIDE
 A *FAIL SAFE/INADVERTENT* OPERATION. THIS OFFICE HAS
 REVIEWED DOCUMENTATION PROVIDED BY SQ *D* ON OTHER
 PROJECT(S) WHICH DOES NOT SEEM TO MEET CODE FOR THE
 INSTALLATION. PLEASE KNOW IT IS THE UNDERSTANDING OF
 THIS OFFICE THAT SOME EQUIPMENT IS BEING SUBMITTED FOR
 LISTINGS FOR INTENDED USE OF TRANSFER EQUIPMENT HOWEVER
 INFORMATION FOR THIS HAS NOT BEEN SUBMITTED AT THIS
 TIME FOR ALLOWANCE.
 PLEASE KNOW THAT THERE HAVE BEEN PREVIOUS PROJECTS
 WHICH MAY HAVE ALLOWED THESE TYPES OF DEVICES HOWEVER
 THIS WILL NOT BE PERMITTED BY THIS AHJ. PLEASE KNOW
 THIS AHJ ALONG WITH SEVERAL OTHER LOCAL JURISDICTIONS
 HAVE SEEN MULTIPLE KEYS ON-SITE WHICH WILL ALLOW BOTH
 SIDES TO BE CONNECTED. PLEASE KNOW THAT UNTIL PRODUCTS
 ARE LISTED AND PROVIDE THE OPERATION WHICH PROVIDES THE
 INADVERTENT CONNECTION FROM THE UTILITY AND THE BACK UP
 POWER SOURCE THIS IS A LIFE SAFETY AND PROPERTY HAZARD
 AND WILL NOT BE ACCEPTED BY THIS AHJ.
 THIS OFFICE HAS NOT MENTIONED THAT A *LISTED TRANSFER
 SWITCH* IS REQUIRED HOWEVER WE ARE REQUIRING THE DEVICE
 IS LISTED FOR USE AND THAT IT PROVIDES COMPLETE FAIL
 SAFE OPERATION.
 DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
 PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS.
  
 4) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD
 BE REQUIRED TO TERMINATE IN OCP PER 240.21. 408.16.
 PLEASE SEE THAT DISCONNECTS OF SOME KIND ARE BEING
 SHOWN HOWEVER PLEASE PROVIDE/SHOW THE OVER CURRENT AT
 EACH OF THESE.
  
 5) NOTE:PLEASE SEE THIS COMMENT FROM THE PREVIOUS
 REVIEW HAS NOT BEEN ADJUSTED. PLEASE KNOW THAT BASED ON
 THE ELECTRICAL SCOPE OF WORK ALONG, THE VALUE HAS
 SUBSTANTIALLY INCREASED AND NO ADJUSTMENTS TO THE
 PERMIT APPLICATION HAVE BEEN MADE. A VALUE WILL BE
 REVIEWED AND ADJUSTED BY THIS OFFICE AS NEEDED ON THE
 NEXT RE-SUBMITTAL.
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS, EVEN IF ANY EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED,
 ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE
 AS ADOPTED INTO THE FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 6) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE DIRECT
 ACCESS TO THE MAIN ELECTRICAL SWITCHGEAR FOR SHUT DOWN.
 DOORS, OPENINGS, TRAVEL DISTANCE, ETC. THE LOCATION
 NEEDS TO BE DETERMINED BY THIS OFFICE AND THE FIRE
 MARSHAL ONCE SHOWN ON PLANS.
 PLEASE SEE 230.70.
 PLEASE ALSO SEE THAT THE LOCATION FOR STORAGE/EASILY
 IGNITABLE ETC CAN NOT BE VERIFIED AT THIS TIME.
 PROTECTION OF THIS EQUIPMENT IS REQUIRED IN ANY OPEN
 AREAS AS THE OTHER EQUIPMENT ON PLANS OUTSIDE IS
 SHOWN.
 110.26, 408.7, 240.24 ETC.
  
 7) NOTE: PLEASE SEE THE NEW SWITCH GEAR SHOWS NEW OVER
 CURRENT PROTECTION TO ALL EXISTING PANELS; HOWEVER SIZE
 OF THOSE EXISTING PANELS HAS NOT BEEN SHOWN.
 PLEASE ALSO SEE PANELS *KB AND KC* WHICH DO NOT SHOW
 ANY ITEMS ON PANEL SCHEDULES, YET PANELS SHOW LOADS?
 PLEASE CLARIFY ALL PANELS, USE, LOADS ETC.
 215.5, 240, 220, 310.16 ETC
  
 FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR INFORMATION
 NEEDED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 17:46 Sent To  
Notes
2006-10-28 18:15:35**** UNSAT ******
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES ARE
 STATED ON PLANS. 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, 2004 NFPA-96 ETC.
  
 2) NOTE: PLEASE SEE SPACE APPEARS TO BE PART OF A
 LARGER BUILDINGAND THE NEW SERVICE BEING REQUESTED IS
 NOT GRANTED AT THIS TIME. THIS BUILDING ALREADY
 CONTAINS NUMEROUS MAINS AND SERVICE EQUIPMENT. A
 SERVICE CHANGE/OVERHAUL WILL BE REQUIRED. AS SHOWN AND
 GIVEN THE SERVICE ON THE BUILDING THIS DOES NOT MEET
 230.2.
  
 3) NOTE: PLEASE SEE PLANS STATE A "TEST" KITCHEN
 HOWEVER THE SAME REQUIREMENTS FOR ANY COMMERCIAL
 KITCHEN WILL BE REQUIRED AS THESAME TASKS WILL BE AT
 HAND.
 PLEASE SEE 210.8B3 FOR ALL RECEPTS. PLEASE KNOW, EVEN
 ALL THE EXISTING.
  
 4) NOTE: PLEASE SEE AS THIS APPEARS TO BE A CHANGE IN
 USE OR OCCUPANCY, PLEASE SEE CHAPTER 13 FOR
 COMPLIANCE.
 PLEASE SHOW ALL OTHER AREAS PART OF THIS BUILDING.
  
 5) NOTE: PLEASE SEE ANY POSSIBLE FIRE REVIEW NOTES WITH
 RESPECT TO AN EXIT LT WHICH APPEARS TO GUIDE PERSON
 BACK INTO THE LARGER PORTION OF THE BUILDING. THIS IS
 NOT AN ELECTRICAL REVIEW NOTE , HOWEVER ANY CHANGES MAY
 AFFECT THE ELECTRICAL PLANS.
 LS 101 7.8, 7.9
  
 6) NOTE: PLEASE SEE TAPPED CONDUCTORS ON GUTTER WOULD
 BE REQUIRED TO TERMINATE IN OCP PER 240.21.
 408.16HOWEVER PLEASE KNOW, AT THIS TIME, DUE TO THE
 UNKNOWN OF THE EXISTING SERVICE, BUILDING ETC, THIS
 COMMENT HAS NO AFFECT AS THE SERVICE AS SHOWN IS NOT
 PERMITTED.
  
 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOUR AND MATERIALS, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE KNOW IF AN APPROPRIATE VALUE IS NOT ADJUSTED,
 ONE WILL BE ADJUSTED BASED ON MARSHALL'S & SWIFT GUIDE
 AS ADOPTED INTOTHE FBC 108.3 ADMINISTRATIVE SECTION
 AS ADOPTED BY THE CITY OF WESTPALM BEACH.
  
 8) NOTE: PLEASE SEE SOME SHEETS ARE MISSING FROM SETS
 WHICH ARE INDICATED ON COVER TITLE SHEET.
  
 9) NOTE:** IMPORTANT**
 ** DO NOT IGNORE THIS COMMENT.
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICLA PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-22 09:16:29SEE UPDATED "I" NOTES, TO BE PLACED ON COMM BOARD.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By mawillia Date 2008-03-19 Time 19:37 Rev Time 0.00
Received By mawillia Date 2008-03-19 Time 19:24 Sent To  
Notes
2008-03-19 19:37:21*****REVISION #3, DATED 2/22/08, APPROVED*****
  
  
 REVISED PLAN SHEETS A-1.1AND A-1.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By mwennerg Date 2008-01-09 Time 10:42 Rev Time 0.00
Received By mwennerg Date 2008-01-09 Time 10:42 Sent To  
Notes
2008-01-09 10:43:28REVISED SHEETS E3.1, E6.1, M0.1, M2.1, P2.1, P5.1.
 STAMPED. SIGNED AND DATED E3.1 ON THIS DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-29 Cont ID  
Sent By mawillia Date 2007-11-29 Time 11:55 Rev Time 0.00
Received By mawillia Date 2007-11-29 Time 11:51 Sent To M
Notes
2007-11-29 11:54:51*****APPROVED REVISION*****
  
  
 PLAN SHEET 3 OF 3 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-08 Cont ID  
Sent By mawillia Date 2007-03-08 Time 10:46 Rev Time 0.00
Received By mawillia Date 2007-03-08 Time 09:41 Sent To  
Notes
2007-03-08 10:42:54*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED.PLAN SHEET A-1.0 AND E2.1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By mawillia Date 2006-12-13 Time 11:16 Rev Time 0.00
Received By mawillia Date 2006-12-13 Time 11:16 Sent To  
Notes
2006-12-13 12:04:04*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
 AMEND SHEET A 0.0 UNDER BUILDING CODES.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY TEREOF.
  
 4.INTERIOR FINISH IN AN UNSPRINKLERED BUILDING SHALL
 BE CLASS "A" OR CLASS "B" , NO CLASS "C".
  
 5.THERE APPEARS TO BE A DISCREPANCY IN THE SWING OF
 THE DOUBLE EXIT DOORS.FOR EXAMPLE, SHEET KE-1.0 HAS
 THE DOORS SWINGING INTO THE EGRESS PATH, WHEREAS SHEET
 P2.1 HAS THE DOORSPROPERLY SWINGING OUT TOWARDS THE
 DIRECTION OF EGRESS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-03-07 Cont ID  
Sent By kstevens Date 2007-03-07 Time 14:43 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 16:23 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 16:23 Sent To  
Notes
2008-02-26 16:25:39TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 11:50 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 11:50 Sent To B
Notes
2008-02-14 11:50:52TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-01-02 Cont ID  
Sent By spalmer Date 2008-01-02 Time 12:26 Rev Time 0.00
Received By spalmer Date 2008-01-02 Time 12:25 Sent To B
Notes
2008-01-02 12:26:24TO JIM WITMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 11:58 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 11:58 Sent To  
Notes
2007-12-28 11:58:24TO COMM BOARD # 42

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 16:30 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 16:30 Sent To M
Notes
2007-11-19 16:30:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 10:51 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 10:51 Sent To E
Notes
2007-08-16 10:51:30TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 16:36 Sent To  
Notes
2007-07-27 12:04:59TO "COMM" BD#60
2007-07-18 16:37:19WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 09:50 Sent To  
Notes
2007-06-26 09:50:236/26/07--TAKEN FROM "COMM" BD AND ROUTED TO "P"
2007-06-14 13:43:12TO "COMM" BD#4
2007-05-25 09:51:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 11:26 Sent To  
Notes
2007-03-01 11:27:02TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-13 Cont ID  
Sent By mawillia Date 2006-12-13 Time 11:16 Rev Time 0.00
Received By mawillia Date 2006-10-12 Time 10:20 Sent To  
Notes
2006-10-24 15:47:56TO "COMM" BD#26
2006-10-22 09:15:41REMOVED FROM BOB BOARD, AND PLACED ON TABLE WAITING FOR
 COMM BOARD. PER RB AND DVP>
2006-10-20 13:09:21TO "BOB"#6
2006-10-12 10:21:10WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-31 Cont ID  
Sent By tgordon Date 2007-12-31 Time 14:35 Rev Time 0.45
Received By tgordon Date 2007-12-31 Time 14:35 Sent To  
Notes
2007-12-31 14:37:21REVISION TO MECH. PLANS PAGES M0.1 AND M2.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 14:07 Rev Time 0.30
Received By tgordon Date 2007-11-29 Time 14:07 Sent To  
Notes
2007-11-29 14:08:15REVISION TO KITCHEN HOOD PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-02 Cont ID  
Sent By tgordon Date 2007-03-02 Time 09:13 Rev Time 2.00
Received By tgordon Date 2007-03-02 Time 09:13 Sent To  
Notes
2007-03-02 09:19:39*** NOTICE ***
 1) ADDITIONAL PERMITS REQUIRED FOR HOOD AND FIRE
 SUPPRESSION (SUBMIT FIRE SUPPRESSION PLANS WITH
 APPLICATION).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By tgordon Date 2006-10-26 Time 11:58 Rev Time 1.30
Received By tgordon Date 2006-10-26 Time 11:58 Sent To  
Notes
2006-10-26 12:08:58*** DENIED ***
 1) SEE PAGE A-8.1 SPECIF. #10 REFERS TO THE 2001 FBC,
 PLEASE CORRECT AS THE CURRENT CODE IN USE IS 2004 FBC.
  
 2) PAGE KE-3.0 (CAPTIVE AIR HOOD DRAWING) IS MISSING
 FROM PLAN SET. PLEASE PROVIDE PLANS FOR KITCHEN HOOD.
  
 3) PLEASE SHOW ON PLANS HOW KITCHEN HOOD EXHAUST FAN &
 SUPPLY FAN ARE TO BE SECURED TO ROOF TO WITH STAND 140
 MPH WIND, PER 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
2006-10-20 15:31:05 

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-03-24 Cont ID  
Sent By mperson Date 2008-03-24 Time 11:04 Rev Time 0.00
Received By mperson Date 2008-03-24 Time 11:04 Sent To PC
Notes
2008-03-24 11:06:40REVISION:ADDED NEW SHEET NUMBERS A-1.1, AND A-1.2.

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 06:33 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 06:33 Sent To  
Notes
2008-02-22 06:42:07REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SHT A-1.1 DETAIL 5, THE LAV SHALL BE A MINIMUM 1'3"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR
 SPACE REQUIRED BY SECTION 11-4.19.3.
  
 2. SHT A-1.2 DETAILS 19 & 20, SHOW COMPLIANCE WITH THE
 FOLLOWING:
  
 ___FOR W/C:
 1. 11-4.16.3 HEIGHT
  
 ___ FOR LAV:
 1. 11-4.19.3 HEIGHT
  
  
 3. SHT A-1.2 DETAILS 19 & 20 PER SECTION 1210.2 WALLS
 WITHIN 2 FEET OF WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. EPOXY PAINT DOES NOT COMPLY
 WITH THE REQUIREMENT FOR A HARD SURFACE. PLEASE SHOW
 COMPLIANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-23 Cont ID  
Sent By kstevens Date 2008-01-23 Time 16:35 Rev Time 0.00
Received By kstevens Date 2008-01-23 Time 16:35 Sent To  
Notes
2008-01-23 16:36:12REVISION OK - SHTS P2.1 & P5.1

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-11 Cont ID  
Sent By kstevens Date 2007-08-11 Time 09:43 Rev Time 0.00
Received By kstevens Date 2007-08-11 Time 09:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-07 Cont ID  
Sent By kstevens Date 2007-07-07 Time 17:31 Rev Time 0.00
Received By kstevens Date 2007-07-07 Time 17:31 Sent To  
Notes
2007-07-07 17:43:35DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHEETS P0.1 & P5.1. A PROFESSIONAL ENGINEER SHALL
 SIGN HIS NAMEWITH A LEGAL SIGNATURE ON FILE IN THIS
 OFFICE. INITIALS ARE NOT ACCEPTABLE. FAC
 61G15-23.002(1)(2) & FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By kstevens Date 2007-03-07 Time 14:15 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 14:15 Sent To  
Notes
2007-03-07 14:29:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
  
 1. OK
  
 2. ALL ARCHITECTURAL SHEETS. THE EMBOSSED SEAL SHALL
 IMPART ALL REQUIRED INFORMATION ON EACH SHEET. PLEASE
 IMPRESS ALL INFORMATION REQUIRED BY FAC 61G1-16.002(1)
 & FS 481.2055.
 ****RESPONSE NOTED, BUT ALL THE INFORMATION REQUIRED IS
 NOT IMPRESSED ON EACH SHEET. THE SEAL APPEARS TO BE
 WORN OUT, AND MAYBE A NEW SEAL IS NEEDED.
  
 3. OK
 4. OK
 5. OK
  
 6. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LMASSON, ENVIRONMENTAL COMPLIANCE MANAGER, (561)
 822-2271, FAX (561) 822-2279, E-MAIL [email protected].
 UTILITY ORD. 3434.
 ****RESPONSE NOTED, BUT NO REPLY FROM ENVIRONMENTAL
 COMPLIANCE AT THIS TIME. I WILL TRY TO GET THE FINAL
 DETERMINATION.
  
 7. OK (DEPT. OF AGRICULTURE)
 8. OK
 9. OK (DELETED)
 10. OK
 11. OK
  
 12. SHTS P2.1 AND P5.1 THE UNDERCOUNTER GREASE TRAP IS
 NOT APPROVED. A MINIMUM 750 GALLON GREASE INTERCEPTOR
 IS REQUIRED PER SECTION 90-124(7)(F) OF THE MUNICIPAL
 CODE AND THE UTILITY DEPT STANDARD GREASE INTERCEPTOR
 DETAIL.
 ****RESPONSE NOTED. WAITING FOR RESPONSE FROM
 ENVIRONMENTAL COMPLIANCE.
  
 13. OK
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 H. N/A
 I. N/A
 J. OK
  
 **********NEW COMMENT**********
  
 1B. SHT P5.1 WATER ISOMETRIC, THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By kstevens Date 2006-12-06 Time 16:51 Rev Time 0.00
Received By kstevens Date 2006-12-06 Time 16:51 Sent To  
Notes
2006-12-06 17:42:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS NUMBER IS
 REQUIRED IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.219. PLEASE PROVIDE REQUIRED INFORMATION ON EACH
 SEET.
  
 2. ALL ARCHITECTURAL SHEETS. THE EMBOSSED SEAL SHALL
 IMPART ALL REQUIRED INFORMATION ON EACH SHEET. PLEASE
 IMPRESS ALL INFORMATION REQUIRED BY FAC 61G1-16.002(1)
 & FS 481.2055.
  
 3. SHT A-0.0 CODES IN EFFECT ARE FBC-2004. PLEASE
 DESIGN TO THIS CODE AND CHANGE CODE REFERENCES TO
 REFLECT THIS REQUIREMENT.
  
 4. PLEASE INDICATE THE SPACE NUMBER ON THE APPLICATION
 AND ON THE PLANS. THE PLANS INDICATE THAT THIS IS A
 SPACE WITHIN THE BUILDING. SECTION 106.1.2.
  
 5. SHT A-0.1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A
 SERVICE SINK ARE REQUIRED. PLEASE INDICATE THE LOCATION
 OF EACH.
  
 6. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LMASSON, ENVIRONMENTAL COMPLIANCE MANAGER, (561)
 822-2271, FAX (561) 822-2279, E-MAIL [email protected].
 UTILITY ORD. 3434.
  
 7. MORE INFORMATION IS REQUIRED. WILL THERE BE SALES OF
 FOOD AND WILL THIS BE CONSIDERED A RESTURANT? IF SO THE
 PLANS WILL HAVE TO BE ROUTED TO DBPR HOTEL & RESTURANT
 DIVISION FOR REVIEW, AND A MINIMUM OF TWO SETS OF
 STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" WILL BE
 REQUIRED TO BE SUBMITTED TO WEST PALM BEACH FOR REVIEW
 PRIOR TO ISSUING A PERMIT. SECTION 102.2.1.
  
 8. SHT KE-2.1 DETAIL 15 INDICATES PLUMBING EQUIPMENT
 SCHEDULE. DETAIL 5 DOES NOT REFLECT THE ITEM NUMBERS.
 PLEASE CORRELATE SCHEDULE AND ITEM NUMBERS ON THE FLOOR
 PLAN. SECTION 106.1.1.
  
 9. SHT KE-2.1 DETAIL 15, ITEM 34 INDICATES A WATER
 FILTER. THE FILTER SHALL COMPLY WITH NSF-42. PLEASE
 SUBMIT MANUF. SPECIFICATIONS FOR THE FILTER SHOWING
 COMPLIANCE WITH THE NSF STANDARD. SECTION 611.1.
  
 10. SHT P.1 WATER SERVICE. AN RPZV BACKFLOW IS REQUIRED
 ON THE WATER SERVICE TO THE SPACE. SECTION 608.13.2.
 PLEASE INDICATE ON THE RISER DIAGRAM AND ON THE FLOOR
 PLAN.
  
 11. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED. SECTION
 607.3.2.
  
 12. SHTS P2.1 AND P5.1 THE UNDERCOUNTER GREASE TRAP IS
 NOT APPROVED. A MINIMUM 750 GALLON GREASE INTERCEPTOR
 IS REQUIRED PER SECTION 90-124(7)(F) OF THE MUNICIPAL
 CODE AND THE UTILITY DEPT STANDARD GREASE INTERCEPTOR
 DETAIL.
  
 13. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NO CORRESPONDING LENGTHS SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - THIS WILL BE VERIFIED
 WHEN ALL LENGTHS OF PIPE ARE SHOWN ON THE RISER
 DIAGRAM.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. - INDICATE IF WATER HEATER ROOM
 IS A CONFINED SPACE OR NOT. SHOW CUBIC FEET OF HEATER
 ROOM.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. SHOW THE MODEL NUMBER
 AND BTU LOAD FOR EACH PIECE OF EQUIPMENT TO REFLECT THE
 GAS RISER DIAGRAM.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-08 Cont ID  
Sent By choops Date 2008-01-08 Time 10:38 Rev Time 0.00
Received By choops Date 2008-01-08 Time 10:38 Sent To  
Notes
2008-01-08 10:38:55*ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.