Plan Review Details - Permit 06100205
Plan Review Stops For Permit 06100205
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-31 Cont ID  
Sent By lmartine Date 2007-01-31 Time 15:40 Rev Time 0.00
Received By lmartine Date 2007-01-31 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:20 Rev Time 0.00
Received By alange Date 2006-10-23 Time 08:20 Sent To  
Notes
2006-10-23 08:22:08DENIED
  
 1.SUBMIT TWO ORIGINAL SIGNED AND SEALED DOCUMENTS
 FROM HILLMAN ENGINEERING.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 18:16 Rev Time 0.33
Received By btrobaug Date 2006-10-19 Time 18:02 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-13 Cont ID  
Sent By mperson Date 2006-12-13 Time 10:02 Rev Time 0.33
Received By mperson Date 2006-12-13 Time 10:02 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By mperson Date 2006-10-20 Time 13:45 Rev Time 0.45
Received By mperson Date 2006-10-20 Time 13:44 Sent To B
Notes
2006-10-20 14:14:50UNSAT
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. THE DISTANCES BETWEEN THE GENERATOR AND THE CLOSEST
 STRUCTURES AND PROPERTY LINES MUST BE CLEARLY INDICATED
 ON THE SURVEY.
  
 2. PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATIONS REGAURDING CLEARENCES FOR THE GENERATOR
 IN RELATION TO PERMANENT STRUCTURES.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (NOTE: THIS MEANS ABOVE AND BELOW
 GROUND.)
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. ( NOTE: THIS
 MEANS ABOVE AND BELOW GROUND.)
  
 5. TYPE OF GAS, (LP OR NATURAL)
  
 6. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT
 (2LB REGULATOR) TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 10:05 Sent To G
Notes
2006-12-12 10:05:55TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 16:02 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 16:02 Sent To Z
Notes
2006-12-01 16:03:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By adarroug Date 2006-10-17 Time 16:49 Rev Time 0.00
Received By adarroug Date 2006-10-17 Time 16:49 Sent To E
Notes
2006-10-17 16:49:43TO "GEN-RES "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:22 Rev Time 0.00
Received By alange Date 2006-10-10 Time 17:49 Sent To  
Notes
2006-10-10 17:49:36TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-13 Cont ID  
Sent By tgordon Date 2006-12-13 Time 13:55 Rev Time 0.15
Received By tgordon Date 2006-12-13 Time 13:55 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By tgordon Date 2006-10-20 Time 08:39 Rev Time 0.20
Received By tgordon Date 2006-10-20 Time 08:39 Sent To P
Notes
2006-10-20 08:42:17*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By mmclean Date 2006-12-08 Time 14:32 Rev Time 0.00
Received By mmclean Date 2006-12-08 Time 14:32 Sent To I
Notes
2006-12-08 14:32:40NOTE: THE PROPOSED GENERATOR WILL BE 12FT FROM
 STRUCTURE AND 5FT FROM THE SIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By kdfreema Date 2006-10-11 Time 12:34 Sent To  
Notes
2006-10-11 12:49:35PLEASE SHOW DISTANCES BETWEEN THE GENERATOR AND THE
 CLOSEST STRUCTURES AND PROPERTY LINES ON THE SURVEY.
  
 NOTE THAT MECHANICAL EQUIPMENT MAY NOT EXTEND ANY MORE
 THAN 4 FEET INTO ANY REQUIRED SETBACK. HOWEVER, A
 GENERATOR MUST BE INSTALLED IN COMPLIANCE WITH ALL OF
 THE SEPARATION DISTANCES REQUIRED BY THE MANUFACTURER
 AND UNDER NO CIRCUMSTANCE SHALL A GENERATOR BE
 INSTALLED CLOSER TO THE PROPERTY LINE THAN SAID
 SEPARATION DISTANCE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY
 QUESTIONS YOU MAY HAVE AT 822-1435.