| Plan Review Stops For Permit 06100199 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-03-26 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-03-26 |
Time |
09:49 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-03-02 |
Time |
15:24 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2007-03-02 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2007-03-02 16:24:12 | BUILDING REVIEW FOURTH CHECKLIST: | | | 1- INFORMATION REQUESTED ON THIRD CHECKLIST REGARDING | | | THE FLAT ROOF WAS NOT PROVIDED: | | | NEED TO PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING | | | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON PAGE 32 OF NOA 03-0501.02 SUBMITTED. | | | SELECTED ROOF ASSEMBLY ON PAGE 28 IS LIMITED BY GENERAL | | | LIMITATION #7 AND THE MAXIMUM DESIGN PRESSURES ARE | | | -45PSF.NEED TO PROVIDE THE RAS 117 CALCULATIONS | | | BECAUSE ACCORDING TO TABLE R301.2(2) OF 2004 FLORIDA | | | RESIDENTIAL CODE THE ROOF ASSEMBLY MUST MEET HIGHER | | | DESIGN PRESSURES AT PERIMETER AND CORNER AREAS. | | | | | | ***NOTE; | | | THERE WAS ACONTRACTOR'SAFFIDAVIT FORM SUBMITTED. | | | THIS AFFIDAVIT HAS NOTHING TO DO WITH RAS 117 | | | CALCULATIONS AND APPLIES TO PALM BEACH COUNTY BUILDING | | | DEPARTMENT ONLY,NOT CITY OF WEST PALM BEACH. IN | | | ADDITIONIT'S INCOMPLETE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-01-22 |
Time |
18:51 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2007-01-22 |
Time |
18:35 |
Sent To |
|
|
| Notes |
| 2007-01-22 18:57:43 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- FLAT ROOF NOA 03-0501.02 SUBMITTED: | | | A) THERE ARE TWO DIFFERENT APPROVED ASSEMBLIES THAT | | | WERE HIGHLIGHTED. ONE IS ON PAGE 26 AND THE OTHER ONE | | | IS ON PAGE28. THESE ARE 2 COMPLETELY DIFFERENT | | | APPLICATIONS. NEED TO SELECT THE SPECIFIC ASSEMBLY THAT | | | IS GOING TO BE INSTALLED. | | | | | | B) PROVIDE THE RAS 117 CALCULATIONS FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY | | | GENERAL LIMITATION #7. SEE PAGE 32 ON NOA SUBMITTED. | | | | | | 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF | | | RECORDING IF WORK IS NOT STARTED. SEE FLORIDA STATUTES | | | 713.13 FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF | | | COMMENCEMENT. | | | | | | 3- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE | | | BOTTOM OF FORMS. | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. LETTER SUBMITTED BY ENGINEER | | | SAYING THAT HE REVIEWED PRODUCT APPROVALS WITH | | | CONTRACTOR IS TOO GENERAL. NEED TO IDENTIFY EACH | | | PRODUCT APPROVAL WITH SPECIFIC INFORMATION LIKE | | | MANUFACTURER, NOA NUMBER, ETC. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-15 |
Time |
14:39 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2006-12-14 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2006-12-15 16:12:24 | BUILDING REVIEW 2ND CHECKLIST: | | | 1- ORIGINAL APPLICATION WAS SUBMITTED BY OWNER/BUILDER. | | | NOW THERE IS A CONTRACTOR ON BOARD. PROVIDE CHANGE OF | | | CONTRACTOR FORM ALONG WITH RELATED FEES. SEE ATTACHED | | | COPY OF CHANGE OF CONTRACTOR FORM AND COMPLETE ALL | | | REQUIRED INFORMATION. | | | | | | 2- FLAT ROOF PRODUCT APPROVAL: | | | A)SPECIFY PROPOSED FASTENING OPTION FOR SELECTED | | | APPROVED ASSEMBLY ON PAGE 17 OF NOA 02-0212.07 AS | | | REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE | | | ATTACHED COPY. | | | | | | B) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY | | | GENERAL LIMITATION #7. SEE LAST PAGE OF NOA 02-0212.07. | | | CALCULATIONS MUST BE DONE ONLY BY ANY ONE OF THE | | | PROFESSIONALS LISTED IN LIMITATION #7. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTES. | | | | | | 4- ENERGY CALCULATIONS SUBMITTED FORM 600B-04 CAN NOT | | | BE USED FOR SINGLE ASSEMBLY ROOF/CEILING CONSTRUCTION. | | | SEE GENERAL DIRECTIONS NOTE #1 ON FRONT PAGE OF ENERGY | | | CALCULATIONS. PROPOSED ADDITION ISSINGLE ASSEMBLY | | | CONSTRUCTION.PROVIDE PROPER ENERGY CALCULATIONS | | | FORM. | | | | | | 5- PROVIDE PRODUCT APPROVAL FOR SIMPSON CONNECTORS | | | SPECIFIED ON PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT | | | APPROVAL COVER PAGE AND SPECIFIC SHEET WHERE CONNECTOR | | | IS SHOWN WITH FASTENING AND UPLIFT SPECIFICATIONS. GO | | | TO DCA WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL | | | PRODUCT APPROVAL INFORMATION. | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 7- TYPICAL WALL SECTION WAS NOT REVISED AS REQUESTED ON | | | PREVIOUS CHECKLIST. SEE CURRENT SIMPSON CATALOGUE FOR | | | CORRECT UPLIFT LOADS AND NUMBER OF FASTENERS. | | | OTHERWISE, ENGINEER TO PROVIDE COMPLETE ENGINEERING | | | ANALYSIS IF NUMBERS ARE DIFFERENT THAN THOSE TESTED AND | | | PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (5610805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-10-20 |
Time |
18:54 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2006-10-20 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2006-10-20 18:57:02 | BUILDING REVIEW CHECKLIST: | | | | | | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO | | | CHECK IF IMPACT FEES WILL NEED TO BE PAID.BRING BACK | | | STAMPED DRAWINGS AND COPY OF PAID RECEIPT. | | | | | | 3- PROVIDE ENERGY CALCULATIONSUSING 2004 FORM. | | | OWNER'AGENT TO SIGN AND DATE FORM AS WELL. | | | | | | 4- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS | | | REQUIRED BY DCA RULE 9B-72 FOR: | | | A) FLAT ROOF.SBCCI REPORT SUBMITTED IS ONLY GOOD | | | FOR UP TO -45PSF UPLIFT PRESSURES. SEE LIMITATIONS OF | | | PRODUCT ON LAST PAGE OF THE REPORT. NEED PRODUCT THAT | | | CAN RESIST AT LEAST -89PSF FOR CORNER AREAS. SEE TABLE | | | 1609.6B FBC 2004.SUBMIT FLORIDA OR LOCAL PRODUCT | | | APPROVAL AND CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE | | | INSTALLED. READGENERAL LIMITATIONS OF THE PRODUCT AND | | | PROVIDE REQUIRED INFORMATION. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | | PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND SPECIFIC PAGE SHOWING THE CONNECTORS. | | | | | | C) SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT | | | APPROVAL COVER PAGE WAS SUBMITTED. NEED TO PROVIDE THE | | | DRAWINGS ALSO. | | | NOTE: IF SINGLE HUNG WINDOWS HAVE NOT MISSILE IMPACT | | | GLAZING,THEN NEED TO PROVIDE COMPLETE INFORMATION FOR | | | STORM SHUTTERS. | | | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING | | | ALL PRODUCT APPROVALS AS REEQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 6- BUILDING PERMIT VALUATION WAS UPDATED TO $35970. | | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004.. OWES $124.13. | | | | | | 7- REVISE TYPICAL WALL SECTION DETAIL.NUMBER OF NAILS | | | AND UPLIFT LOAD FOR CONNECTOR SIMPSON HETAL 20 NEED TO | | | BE UPDATED. SEE CURRENT SIMPSON CATALOGUE AND REVISE AS | | | REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-19 |
Time |
14:21 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-10-19 |
Time |
14:10 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
11:11 |
Sent To |
B |
|
| Notes |
| 2007-03-23 11:11:19 | TO "JGOMEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-14 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-14 |
Time |
11:05 |
Sent To |
M |
|
| Notes |
| 2007-02-14 11:06:17 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-03 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-03 |
Time |
11:59 |
Sent To |
M |
|
| Notes |
| 2007-01-03 11:59:30 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-12 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-12 |
Time |
08:22 |
Sent To |
M |
|
| Notes |
| 2006-12-12 08:23:34 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-12-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-04 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-04 |
Time |
14:20 |
Sent To |
Z |
|
| Notes |
| 2006-12-04 14:23:36 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-12 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-12 |
Time |
14:53 |
Sent To |
E |
|
| Notes |
| 2006-10-12 14:53:49 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-10-20 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2006-10-10 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2006-10-10 17:42:57 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2007-02-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-20 |
Time |
09:07 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2007-02-20 |
Time |
09:07 |
Sent To |
B |
|
| Notes |
| 2007-02-20 09:08:15 | NO MECHANICAL WORK TO BE DONE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2007-01-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-04 |
Time |
08:03 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-01-04 |
Time |
08:03 |
Sent To |
B |
|
| Notes |
| 2007-01-04 08:04:54 | MACHANICAL PERMIT #06100203 HAS BEEN VOIDED, NO | | | MECHANICAL WORK TO BE DONE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-13 |
Time |
14:28 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-12-13 |
Time |
14:28 |
Sent To |
B |
|
| Notes |
| 2006-12-13 14:37:29 | *** DENIED *** | | | 1) IF NO A/C WORK IS TO BE DONE THAN YOU NEED TO SUBMIT | | | A NOTARIZED LETTER FROM GERARD HERLIHY REQUESTING | | | MECHANICAL PERMIT #06100203 BE VOIDED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-19 |
Time |
15:43 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-10-19 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2006-10-19 15:50:23 | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS FORM 600C-2004 | | | (SHORT FORM), PER 2004 FBC 13-101.4.1.1 . | | | | | | 2) PLEASE HAVE NEW ENERGY CALCULATIONS SIGNED BY | | | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2 . | | | | | | 3) PLEASE SHOW ON PLANS THE A/C SUPPLY AIR DUCT SIZE, | | | GRILL SIZE, AND THE CFM'S., PER 2004 FBC/ WPB AMEND. | | | 106.3.5.4(10) . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-12-09 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-12-09 |
Time |
12:41 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2006-10-12 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2006-10-12 |
Time |
11:28 |
Sent To |
I |
|
| Notes |
| 2006-10-12 11:30:32 | 10/12/2006 ***FAILED*** | | | | | | 1) ACC (ARCHITECTURAL CONTROL COMMITTEE) APPROVAL | | | LETTER SHALL BE PROVIDED. | | | 2) SETBACKS FROM THE PROPOSED WORK TO THE PROPERTY LINE | | | SHALL BE PROVIDED ON THE SURVEY AND SITE PLAN. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA, PLANNER, | | | 822-1435. |
|
|