Plan Review Details - Permit 06100199
Plan Review Stops For Permit 06100199
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-26 Cont ID  
Sent By jgomez Date 2007-03-26 Time 10:15 Rev Time 0.00
Received By jgomez Date 2007-03-26 Time 09:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-03-02 Cont ID  
Sent By jgomez Date 2007-03-02 Time 15:24 Rev Time 1.00
Received By jgomez Date 2007-03-02 Time 15:24 Sent To  
Notes
2007-03-02 16:24:12BUILDING REVIEW FOURTH CHECKLIST:
 1- INFORMATION REQUESTED ON THIRD CHECKLIST REGARDING
 THE FLAT ROOF WAS NOT PROVIDED:
 NEED TO PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON PAGE 32 OF NOA 03-0501.02 SUBMITTED.
 SELECTED ROOF ASSEMBLY ON PAGE 28 IS LIMITED BY GENERAL
 LIMITATION #7 AND THE MAXIMUM DESIGN PRESSURES ARE
 -45PSF.NEED TO PROVIDE THE RAS 117 CALCULATIONS
 BECAUSE ACCORDING TO TABLE R301.2(2) OF 2004 FLORIDA
 RESIDENTIAL CODE THE ROOF ASSEMBLY MUST MEET HIGHER
 DESIGN PRESSURES AT PERIMETER AND CORNER AREAS.
  
 ***NOTE;
 THERE WAS ACONTRACTOR'SAFFIDAVIT FORM SUBMITTED.
 THIS AFFIDAVIT HAS NOTHING TO DO WITH RAS 117
 CALCULATIONS AND APPLIES TO PALM BEACH COUNTY BUILDING
 DEPARTMENT ONLY,NOT CITY OF WEST PALM BEACH. IN
 ADDITIONIT'S INCOMPLETE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-22 Cont ID  
Sent By jgomez Date 2007-01-22 Time 18:51 Rev Time 1.00
Received By jgomez Date 2007-01-22 Time 18:35 Sent To  
Notes
2007-01-22 18:57:43BUILDING REVIEW THIRD CHECKLIST:
 1- FLAT ROOF NOA 03-0501.02 SUBMITTED:
 A) THERE ARE TWO DIFFERENT APPROVED ASSEMBLIES THAT
 WERE HIGHLIGHTED. ONE IS ON PAGE 26 AND THE OTHER ONE
 IS ON PAGE28. THESE ARE 2 COMPLETELY DIFFERENT
 APPLICATIONS. NEED TO SELECT THE SPECIFIC ASSEMBLY THAT
 IS GOING TO BE INSTALLED.
  
 B) PROVIDE THE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7. SEE PAGE 32 ON NOA SUBMITTED.
  
 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED. SEE FLORIDA STATUTES
 713.13 FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 3- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORMS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. LETTER SUBMITTED BY ENGINEER
 SAYING THAT HE REVIEWED PRODUCT APPROVALS WITH
 CONTRACTOR IS TOO GENERAL. NEED TO IDENTIFY EACH
 PRODUCT APPROVAL WITH SPECIFIC INFORMATION LIKE
 MANUFACTURER, NOA NUMBER, ETC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-15 Cont ID  
Sent By jgomez Date 2006-12-15 Time 14:39 Rev Time 2.00
Received By jgomez Date 2006-12-14 Time 07:42 Sent To  
Notes
2006-12-15 16:12:24BUILDING REVIEW 2ND CHECKLIST:
 1- ORIGINAL APPLICATION WAS SUBMITTED BY OWNER/BUILDER.
 NOW THERE IS A CONTRACTOR ON BOARD. PROVIDE CHANGE OF
 CONTRACTOR FORM ALONG WITH RELATED FEES. SEE ATTACHED
 COPY OF CHANGE OF CONTRACTOR FORM AND COMPLETE ALL
 REQUIRED INFORMATION.
  
 2- FLAT ROOF PRODUCT APPROVAL:
 A)SPECIFY PROPOSED FASTENING OPTION FOR SELECTED
 APPROVED ASSEMBLY ON PAGE 17 OF NOA 02-0212.07 AS
 REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE
 ATTACHED COPY.
  
 B) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7. SEE LAST PAGE OF NOA 02-0212.07.
 CALCULATIONS MUST BE DONE ONLY BY ANY ONE OF THE
 PROFESSIONALS LISTED IN LIMITATION #7.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES.
  
 4- ENERGY CALCULATIONS SUBMITTED FORM 600B-04 CAN NOT
 BE USED FOR SINGLE ASSEMBLY ROOF/CEILING CONSTRUCTION.
 SEE GENERAL DIRECTIONS NOTE #1 ON FRONT PAGE OF ENERGY
 CALCULATIONS. PROPOSED ADDITION ISSINGLE ASSEMBLY
 CONSTRUCTION.PROVIDE PROPER ENERGY CALCULATIONS
 FORM.
  
 5- PROVIDE PRODUCT APPROVAL FOR SIMPSON CONNECTORS
 SPECIFIED ON PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND SPECIFIC SHEET WHERE CONNECTOR
 IS SHOWN WITH FASTENING AND UPLIFT SPECIFICATIONS. GO
 TO DCA WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL
 PRODUCT APPROVAL INFORMATION.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- TYPICAL WALL SECTION WAS NOT REVISED AS REQUESTED ON
 PREVIOUS CHECKLIST. SEE CURRENT SIMPSON CATALOGUE FOR
 CORRECT UPLIFT LOADS AND NUMBER OF FASTENERS.
 OTHERWISE, ENGINEER TO PROVIDE COMPLETE ENGINEERING
 ANALYSIS IF NUMBERS ARE DIFFERENT THAN THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By jgomez Date 2006-10-20 Time 18:54 Rev Time 1.00
Received By jgomez Date 2006-10-20 Time 18:39 Sent To  
Notes
2006-10-20 18:57:02BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 CHECK IF IMPACT FEES WILL NEED TO BE PAID.BRING BACK
 STAMPED DRAWINGS AND COPY OF PAID RECEIPT.
  
 3- PROVIDE ENERGY CALCULATIONSUSING 2004 FORM.
 OWNER'AGENT TO SIGN AND DATE FORM AS WELL.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) FLAT ROOF.SBCCI REPORT SUBMITTED IS ONLY GOOD
 FOR UP TO -45PSF UPLIFT PRESSURES. SEE LIMITATIONS OF
 PRODUCT ON LAST PAGE OF THE REPORT. NEED PRODUCT THAT
 CAN RESIST AT LEAST -89PSF FOR CORNER AREAS. SEE TABLE
 1609.6B FBC 2004.SUBMIT FLORIDA OR LOCAL PRODUCT
 APPROVAL AND CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED. READGENERAL LIMITATIONS OF THE PRODUCT AND
 PROVIDE REQUIRED INFORMATION.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND SPECIFIC PAGE SHOWING THE CONNECTORS.
  
 C) SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE WAS SUBMITTED. NEED TO PROVIDE THE
 DRAWINGS ALSO.
 NOTE: IF SINGLE HUNG WINDOWS HAVE NOT MISSILE IMPACT
 GLAZING,THEN NEED TO PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS AS REEQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- BUILDING PERMIT VALUATION WAS UPDATED TO $35970.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.. OWES $124.13.
  
 7- REVISE TYPICAL WALL SECTION DETAIL.NUMBER OF NAILS
 AND UPLIFT LOAD FOR CONNECTOR SIMPSON HETAL 20 NEED TO
 BE UPDATED. SEE CURRENT SIMPSON CATALOGUE AND REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 14:21 Rev Time 0.50
Received By btrobaug Date 2006-10-19 Time 14:10 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 11:11 Sent To B
Notes
2007-03-23 11:11:19TO "JGOMEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 11:06 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 11:05 Sent To M
Notes
2007-02-14 11:06:17TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 11:59 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 11:59 Sent To M
Notes
2007-01-03 11:59:30TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 08:22 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 08:22 Sent To M
Notes
2006-12-12 08:23:34TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 14:20 Sent To Z
Notes
2006-12-04 14:23:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 14:53 Sent To E
Notes
2006-10-12 14:53:49TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By jgomez Date 2006-10-20 Time 18:57 Rev Time 0.00
Received By jgomez Date 2006-10-10 Time 17:42 Sent To  
Notes
2006-10-10 17:42:57TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 09:07 Rev Time 0.15
Received By tgordon Date 2007-02-20 Time 09:07 Sent To B
Notes
2007-02-20 09:08:15NO MECHANICAL WORK TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-01-04 Cont ID  
Sent By tgordon Date 2007-01-04 Time 08:03 Rev Time 0.25
Received By tgordon Date 2007-01-04 Time 08:03 Sent To B
Notes
2007-01-04 08:04:54MACHANICAL PERMIT #06100203 HAS BEEN VOIDED, NO
 MECHANICAL WORK TO BE DONE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By tgordon Date 2006-12-13 Time 14:28 Rev Time 0.20
Received By tgordon Date 2006-12-13 Time 14:28 Sent To B
Notes
2006-12-13 14:37:29*** DENIED ***
 1) IF NO A/C WORK IS TO BE DONE THAN YOU NEED TO SUBMIT
 A NOTARIZED LETTER FROM GERARD HERLIHY REQUESTING
 MECHANICAL PERMIT #06100203 BE VOIDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-10-19 Time 15:43 Rev Time 0.25
Received By tgordon Date 2006-10-19 Time 15:43 Sent To B
Notes
2006-10-19 15:50:23*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS FORM 600C-2004
 (SHORT FORM), PER 2004 FBC 13-101.4.1.1 .
  
 2) PLEASE HAVE NEW ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2 .
  
 3) PLEASE SHOW ON PLANS THE A/C SUPPLY AIR DUCT SIZE,
 GRILL SIZE, AND THE CFM'S., PER 2004 FBC/ WPB AMEND.
 106.3.5.4(10) .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-09 Cont ID  
Sent By mmclean Date 2006-12-09 Time 12:41 Rev Time 0.00
Received By mmclean Date 2006-12-09 Time 12:41 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By adavila Date 2006-10-12 Time 11:28 Rev Time 0.00
Received By adavila Date 2006-10-12 Time 11:28 Sent To I
Notes
2006-10-12 11:30:3210/12/2006 ***FAILED***
  
 1) ACC (ARCHITECTURAL CONTROL COMMITTEE) APPROVAL
 LETTER SHALL BE PROVIDED.
 2) SETBACKS FROM THE PROPOSED WORK TO THE PROPERTY LINE
 SHALL BE PROVIDED ON THE SURVEY AND SITE PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA, PLANNER,
 822-1435.