Plan Review Details - Permit 06100197
Plan Review Stops For Permit 06100197
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-20 Cont ID  
Sent By lursu Date 2006-10-20 Time 10:27 Rev Time 0.00
Received By lursu Date 2006-10-20 Time 10:27 Sent To  
Notes
2006-10-20 10:28:18THE SITE ADDRESS HAS BEEN CHNAGED FROM 6425 S FALGLER
 DR TO 108 CORTEZ RD

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-10-20 Cont ID  
Sent By lmartine Date 2007-10-20 Time 11:48 Rev Time 0.00
Received By lmartine Date 2007-10-20 Time 11:48 Sent To  
Notes
2007-10-20 11:48:55SAME COMMENTS AS THE LAST TWO REVIEWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-27 Cont ID  
Sent By lmartine Date 2007-08-27 Time 08:34 Rev Time 0.00
Received By lmartine Date 2007-08-24 Time 11:33 Sent To  
Notes
2007-08-27 08:36:27SAME COMMENTS AS REVIEW DATED APRIL 9TH 2007

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-09 Cont ID  
Sent By lmartine Date 2007-04-09 Time 18:14 Rev Time 0.00
Received By lmartine Date 2007-04-09 Time 18:14 Sent To  
Notes
2007-04-09 18:27:19 
 BUILDING REVIEW COMMENTS
  
  
  
 PALM BEACH COUNTY IMPACT FEES ARE DUE, PROVIDE RECEIPT
 AND TWO COPIES OF APPROVED PLANS.
  
 A RECORDED NOTICE OF COMMENCEMENT IS ALSO REQUIRED
 BEFORE FIRST INSPECTION.
  
  
  
  
  
  
  
 L.MARTINEZ
 805-6710
2007-03-20 18:57:31NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-15 Cont ID  
Sent By rnuquist Date 2007-01-15 Time 16:36 Rev Time 0.00
Received By rnuquist Date 2007-01-15 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 09:00 Rev Time 0.00
Received By alange Date 2006-10-23 Time 09:00 Sent To  
Notes
2006-10-23 09:19:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $490,776.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 4."R" VALUES ON PLANS DO NOT MATCH ENERGY CALCS.
  
 5.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS WITH ENGINEERS
 SEALS SHOWN AS LICENSED NOT CERTIFICATE.FAC 61
 G1-16.001
  
 7.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 8.PROPERTY IS IN FLOOD ZONE "A" .BUILDING AND
 EQUIPMENT SLABS SHALL BE A MINIMUM OF 6" ABOVE THE BASE
 FLOOD ELEVATION OF 7 FT. NGVD.SHOW ON PLANS.
  
 9.SEPERATE PERMIT REQIRED FOR POOL, FENCE AND
 ROOFING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 19:16 Sent To M
Notes
2007-07-17 19:36:36REDLINED:
  
 VIF THE CLEARANCES FOR SERVICE. 110.26
 AHU #3 SHOWS 10KW AND 5KW, ALL EQUIPMENT AND OTHER
 INFORMATION POINTS TO THIS AS A 5KW UNIT. MAY BE
 MISPRINT.
  
 ** PLANS DO NOT NEED TO BE REVISED, STAMPED OK FOR
 PERMIT ISSUANCE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-20 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2007-03-20 Time 18:44 Sent To M
Notes
2007-03-20 19:40:52** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 STILL MISSING FROM BEING STATED AND SHOWN ON PLANS.
 PLEASE SEE THAT THE FOLLOWING ARE LISTED.
 2004 FBC
 2002 NFPA-70 (NEC).
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THAT THE PLANS DO NOT CONTAIN A
 SIGNATURE AND PRINTED NAME OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE MASTER BATHROOM WEST WALL SINK
 AREA WHICH REQUIRES A GFI WITHIN 3FT OF THE SINKS EDGE.
 THE GFI SHOWN BASED ON THE 3/16 SCALE ON PLANS DOES NOT
 MEET THE WITHIN 3FT.
 210.52D.
  
 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE TO THE LEFT
 OF THE RISER CONTAINS A #3 FOR THE GEC. THE OTHERS WERE
 CHANGED TO THE 1/0.
  
 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS
 FROM THE METER TO THE 200AMP MAIN2OF 2 ARE NOT LARGE
 ENOUGH. PLEASE SEE RISER SHOWS 1/0'S AND THE MINIMUM
 MUST BE 2/0'S PER 310.15B6
 THIS WAS SHOWN THE SAME ON THE PREVIOUS PLANS, HOWEVER
 WAS MISSED. PLEASE SEE THE 2/0'S SHOWN AFTER THE MAIN
 ARE OK.
  
 6) NOTE: PLEASE SEE THE CONDUIT SIZES BASED ON THE SCH
 80 AND BEING SHOWN AS 1 1/2 INCH IS NOT LARGE ENOUGH
 FOR THE 3-2/0'S AND THE #6.MUST BE 2INCH MINIMUM.
 THIS WAS SHOWN THIS WAY ON PREVIOUS RISER, HOWEVER WAS
 NOT COMMENTED ON BY THIS REVIEWER.
  
 7) NOTE: PLEASE SEE SHEET A-17 WAS NOT SEALED BY THE
 ENGINEER WHICH IS SIGNED AND DATED ON PLANS AND SHEET
 ALSO CONTAINS A TITLE BLOCK FOR SAID SHEETS. PLEASE SEE
 FS 471.025, FAC 61G15-23.002
 THIS SHEET WAS VOIDED EVEN THOUGH THIS WAS STAMPED.
  
 ** PLANS ROUTED BACK TO MECHANICAL AS M SHEETS DO NOT
 CONTAIN PRINTED NAME AND SIGNATURE FROM ANY RESPONSIBLE
 DESIGNER.
  
 ** PLEASE ONLY VERIFY THE SPACE ON THE WALL BY THE
 GARAGE WHICH INDICATES A 400AMP METER AND TWO 200AMP
 DISCONNECTS IN A SPACE NOTE ON PLANS AS 4FT, 2INCHES?
 THIS DOES NOT SEEM TO BE ENOUGH SPACE BASED ON THE
 PLANS AND DIMENSIONS SHOWN WITH THE A/C EQUIPMENT AS
 SHOWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-20 18:45:17ZONING COMPLETED 3/16, RECEIVED FROM INCOMING ON 3/20

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 10:27 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 09:37 Sent To M
Notes
2006-12-10 10:27:27***** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING. PLEASE SEE NOTES ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH A "OK" OR "NO" AT
 THE SAME NUMERICAL NOTE. PLEASE SEE SOME MAY BE NOTED
 AS "NO/OK", WHICH MEANS PART OF THE NOTE MAY HAVE BEEN
 ADDRESSED.
  
 1) NOTE: OK. LV SECURITY UNDER SEPARATE PERMIT ALONG
 WITH POOL.PLEASE KNOW POOL WILL BE UNDER THE 2005
 NEC. (PLEASE SEE GROUNDING CHANGES).
  
 2) NOTE: NO, COULD NOT LOCATE THESE NOTED ON PLANS.
 PLEASE KNOW AS THE CODE HAS CHANGED IT IS IMPORTANT THE
 RELEVANT CODES ARE SHOWN AS NOT TO FALL UNDER NEW CODE
 OF 2005 NEC AND THE REVISIONS TO THE 2004 FBC. (REV
 #6).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, PLEASE SEE ? BATH WHICH DOES NOT INDICATE
 ANY GFI AS REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE REQUIRED
 GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN BATHRMS.
 250.52D, 210.8A1
  
 9) NOTE: NO, PLEASE SEE STUDY AND LAUNDRY ROOMS WITH
 RECEPTS WITHIN 6' OF SINKS AND NOTE #8 ABOVE. REDLINED
 ONCE AGAIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MANY LOCATIONS ARE MISSING THE GFI
 DESIGNATIONS AS REQUIRED PER 210.8A1,A2, A3, A7< PLEASE
 SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT IS IN
 NO WAY ALL WHICH ARE MISSING THIS DESIGNATION.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: OK.
  
 15) NOTE:NO, PLEASE SEE NO RATINGS SHOWN. THE LETTER
 FROM FPL DOES NOT GIVE THE RATINGS TO BE INSTALLED ONLY
 WHAT IS AVAILABLE AT THE POLE/TRANSFORMER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE EQUIPMENT
 AND SERIES RATINGS SHALL BE COORDINATED BY THE
 DESIGNERS. PLEASE SUBMIT. 110.9, 240.12
  
 16) NOTE: OK.
  
 17) NOTE: OK/NO, PLEASE SEE THREE CIRCUITS ARE SHOWN
 HOWEVER THEY ARE ALL SHOWN FOR BEDROOM #2.
 PLEASE ADJUST FOR OTHER CIRCUITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE(S) TO BE PROVIDED.
 PLEASE SEE 210.12, 408.4,
 * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS
 REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS
 TIME.
 FBC 106.1.2 ADM IN SECT
  
 18) NOTE: OK.
  
 19) NOTE: OK, AS ONLY NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 *** IMPORTANT ** PLEASE SEE POSSIBLE MECHANICAL NOTES
 FOR THE LOCATION OF THE ATTIC ACCESS TO THE MECHANICAL
 EQUIPMENT. PLEASE KNOW, IT SEEMS THE EQUIPMENT IS
 FARTHER THAN SIX FT FROM ACCESS. PLEASE SEE MECH REVIEW
 COMMENTS, AS THIS WILL CLEARLY AFFECT THE ELECTRICAL
 PLANS.
  
 20) NOTE:OK.
  
 21) NOTE: NO, PLEASE SEE 424.3B FOR MINIMUM OCP FOR
 10KW UNITS.
 REDLINED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE AHU'S
 SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY
 CONDUCTOR SIZES IF NEEDED.
  
 22) NOTE: OK.
  
 23) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED LTS BASED
 ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT BE FIGURED
 IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR
 FIXTURES BEING USED.
  
 24) NOTE: NO. THE FIXTURE TYPE AS SHOWN DOES NOT MEET
 FBC 13-606.1.ABC.1.2.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED LIGHTING
 PER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT CANS ETC.
  
 25) NOTE: OK.
  
 26) NOTE: OK.
  
 27) NOTE: OK, HOWEVER SAME NOTE ONLY BEING NOTED, AS
 THE SERVICE IS STILL BEING SHOWN AS OVER HEAD. PLEASE
 KNOW, BASED ON THE FPL TRANSFORMER LOCATION AND THE
 FUTURE PROPOSED POOL AS SHOWN ON PLANS, THIS MAY BECOME
 AN ISSUE AT A FUTURE TIME
  
 ** PREVIOUS REVIEW NOTE**
 ** FOR FUTURE REFERENCE, WHEN APPLYING FOR POOL PERMIT,
 PLEASE SEE 680.8 FOR ANY OVER HEAD CONDUCTOR CLEARANCES
 AS THE SERVICE ON RISER SHOWS THE SEC'S AS OH.
  
 28) NOTE: OK.
  
 29) NOTE: OK.
  
 30) NOTE:NO/OK, PLEASE SEE PLANS DO NOT CONTAIN THE
 REQUIRED SIGNATURE OF PERSON RESPONSIBLE FOR PLANS
 DESIGN.
 FBC ADMIN SECTION 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO IS AND IS
 NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES AND
 PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE SURE
 THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID
 DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE
 ANY QUESTIONS, ON THIS PLEASE CONTACT THE STATE'S LEGAL
 COUNSEL TO THE BOARD OF ARCHITECT'S.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE AT THIS TIME.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. PLEASE KNOW THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By dpalmer Date 2006-10-14 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 20:03 Sent To Z
Notes
2006-10-14 13:16:00***** UNSAT ****
  
 1) NOTE: PLEASESEE NOTES FROM ZONING AND BUILDING
 REVIEW AS THE POOL AND WALL WILL NOT PART OF THIS
 PERMIT AND WILL REQUIRE SEPARATE PERMIT APPLICATION FOR
 EACH ALONG WITH PLANS ETC. ANY WALL DETAILS ETC WOULD
 BE IN THESE PLANS.
 PLEASE KNOW, BESIDES THE SEPARATE ELECTRICAL PERMIT,
 SEPARATE PERMITS FOR LV PHONE/CATV /SPKRS ETC ARE
 SEPARATE. THESE MAY REFERENCE THESE PLANS AS TURN
 AROUND PERMIT HOWEVER WILL REQUIRE FEE BASED ON LV
 SCOPE OF WORK VALUE.
 ** PLEASE KNOW THE LV SECURITY PERMIT IS SEPARATE FROM
 ALL OF THE ABOVE AS THEY ARE REPORTED TO THE POLICE
 DEPT SEPARATELY.
  
 2) NOTE: PLEASE SEE THAT THE FOLLOWING MINIMUM CODES
 ARE REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72.
  
 3) NOTE: PLEASE SEE SEC'S TO THE 200A MAIN 1OF 2 IS
 REQUIRED TO BE SIZED PER 310.16. (31.15B6DOES NOT
 APPLY)
  
 4) NOTE: PLEASE SEE MAIN PANEL 2OF 2 SHOWS A 200A PANEL
 SCHEDULE YET RISER SHOWS 100A'S WITH A LOAD EXCEEDING
 THE RATING OF THE 100A MAIN DISCONNECT.
 PLEASE ADJUST.
 230.70, 240, 240.4, 310.16 ETC.
  
 5) NOTE: PLEASE SEE PLANS DO NOT SHOW LOCATION OF THE
 MAINS. ONLY SHOWS THE LOCATIONS OF METER AND EACH
 PANEL. PLEASE SHOW AND PLEASE SEE 230.70, 230.72 FOR
 GROUPING OF MAINS REQUIRED.
  
 6) NOTE: PLEASE SEE GEC IS NOT LARGE ENOUGH. PLEASE SEE
 TABLE IN 250.66 AS #3 IS NOT ON TABLE AND #3 IS NOT
 LARGE ENOUGH. PLEASE KNOW, AS BASED ON THE MIN SEC'S
 WHICH WILL BE REQUIRED AS THE MAINS AS SHOWN WILL BE
 CHANGING, PLEASE SEE 250.66 1/0 AWG MIN.
  
 7) NOTE: PLEASE SEE BASED ON PREVIOUS NOTES AND LOADS
 SHOWN, IF INDEED SERVICE IS GOING CONTAIN A 400A METER
 AND 2-200A DISCONNECTS, PLEASE SEE 310.15B6 MAY BE USED
 TO PROVIDE MIN SEC'S ON RISER ONL.
  
 8) NOTE: PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE
 REQUIRED GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN
 BATHRMS. 250.52D, 210.8A1
  
 9) NOTE: PLEASE SEE MANY LOCATION ARE MISSING THE GFI
 DESIGNATIONS AS REQUIRED PER 210.8A1, A2, A3.A7 <
 PLEASE SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT
 IS IN NO WAY ALL WHICH ARE MISSING THIS DESIGNATION.
  
 10) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED.
  
 11) NOTE: PLEASE SEE MISSING SMOKE ALARM AT FOYER/AREA
 LEADING TO FLR ABOVE. PLEASE KNOW THE LOCATION ATTHE
 TOP OF THE STAIRS IS ALSO REQUIRED. PLEASE KNOW EVEN IF
 THIS UNIT HAS TO BE WALL MOUNTED, IT MUST BE IN CLOSE
 PROXIMITY OF THE STAIRS LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.5.1.1,
  
 12) NOTE: PLEASE SEE NFPA-72 AS ALL SA'S ARE REQUIRED
 TO BE LOCATED WITHIN 12' OF THE HIGHEST POINT OF ANY
 GIVEN ROOM'S FLAT CEILING. PLEASE SEE ANY AREAS WITH
 TRAY CEILINGS WHICH ARE 12" OR MORE WILL REQUIRE THE SA
 TO BE MOVED. PLEASE ALSO KNOW 3' W/IN THE PEAKS OF
 SLOPED CEILING, NONE NOTED AT THIS TIME. PLEASE SEE
 11.8.3
  
 13) NOTE: PLEASE VERIFY AND INDICATE OF THESE ARE
 INDEED GOING TO BE SMOKE DETECTORS ORSMOKE ALARMS?
 PLEASESEE NFPA-72 FOR DEFINITIONS. IF INDEED SA'S,
 PLEASE ADJUST DESIGNATIONS.
  
 14) NOTE: PLEASE PROVIDE INFORMATION FOR ELEVATOR AND
 POWER REQUIREMENTS ETC. PLEASE SEE NO INFORMATION
 /LOADS ETC ARE SHOWN ON PANEL SCHEDULE/LOAD CALCS. FBC
 106.1.2, NEC 2002.
 UNABLE TO VERIFY CODE COMPLIANCE FOR THIS AT THIS TIME
 AS ONLY A RECEPT IS BEING SHOWN.
  
 15) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AND SERIES RATINGS SHALL BE CO-ORDINATED BY
 THE DESIGNERS. PLEASE SUBMIT . 110.9, 240.12
  
 16) NOTE: PLEASE SEE 210.52E AS A WP LOCATION IS BEING
 SHOWN AT REAR OF DWELLING HOWEVERNORECEPT OR GFI?
 210.8A3
  
 17) NOTE; PLEASE LIST ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE(S) TO BE
 PROVIDED.
 PLEASE SEE 210.12, 408.4,
 * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS
 REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS
 TIME.
 FBC 106.1.2 ADM IN SECT
  
 18) NOTE: PLEASE SEE MISSING RECEPT /LT PER 210.63,
 210.70 FOR ATTIC EQUIPMENT.
  
 19) NOTE:*** IMPORTANT ** PLEASE SEE POSSIBLE
 MECHANICAL NOTES FOR THE LOCATION OF THE ATTIC ACCESS
 TO THE MECHANICAL EQUIPMENT. PLEASE KNOW, IT SEEMS THE
 EQUIPMENT IS FARTHER THAN SIX FT FROM ACCESS. PLEASE
 SEE MECH REVIEW COMMENTS, AS THIS WILL CLEARLY AFFECT
 THE ELECTRICAL PLANS.
  
 20) NOTE:PLEASE CORRELATE ALL MECHANICAL EQUIPMENT
 WITH THE ELECTRICAL PLANS AS THE LOADS SHOWN ARE NOT
 THE SAME.
 FBC 106.1.2. PLEASE ALSO SEE NEXT COMMENT.
  
 21) NOTE: PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE
 AHU'S SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY
 CONDUCTOR SIZES IF NEEDED.
  
 22) NOTE; PLEASE SEE BRANCH CIRCUIT CONDUCTOR FOR OVEN
 SHOWS 20A BRLR WITH #8?? PLEASE KNOW THIS CONDUCTOR
 WILL NOT FIT UNDER THE 20A BRKR SCREW/LUG/PLATE. IF THE
 WIRING IS GOING TO BE #8'S PLACE FOR POSSIBLE FUTURE
 ELECTRICAL RANGE/OVEN PLEASE NOTE.
 110.3,
  
 23 )NOTE: PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED
 LTS BASED ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR
 FIXTURES BEING USED.
  
 24) NOTE: PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED
 LIGHTINGPER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT
 CANS ETC.
  
 25) NOTE:PLEASE SEE MISSING WATER HEATER DISCONNECT
 PER 422.31, AS A RECEPT IS NOW BEING SHOWN WHICH IS NOT
 PERMITTED.
 PLEASE SHOW DISCONNECT.
  
 26) NOTE: PLEASE BE SURE A GFI RECEPT LOCATION IN TH
 REAR OF THE DWELLING IS WITHIN 20' OF POOL AND AT LEAST
 10FT. PLEASE SEE 210.8, 680.22
  
 27) NOTE:: ** FOR FUTURE REFERENCE, WHEN APPLYING FOR
 POOL PERMIT , PLEASE SEE 680.8 FOR ANY OVER HEAD
 CONDUCTOR CLEARENCES AS THE SERVICE ON RISER SHOWS THE
 SEC'S AS OH.
  
 28) NOTE: PLEASE SEE "ENHANCED" GROUNDING ELECTRODE
 SYSTEM GROUNDING DETAIL SHOULD REFLECT THE INCREASED
 GEC AS REQUIRED PER NOTES ABOVE 250.66.
 250.50.
  
 29) NOTE: PLEASE SEE SOME BATH RM RECEPTS ARE BEING
 SHOW WITH A SYMBOL WHICH INDICATE THE DEVICE AT
 220V'S??
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO ALL BATH RMS.
 210.8A1, 210.52D.
  
 30) NOTE: PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO
 IS AND IS NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES
 AND PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE
 SURE THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID
 DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE
 ANY QUESTIONS, ON THE THIS PLEASE CONTACT THE STATE'S
 LEGAL COUNSEL TO THE BOARD OF ARCHITECT'S.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
2006-10-13 20:32:38PLANS WILL BE PLACED INTO A "F" STATUS AND REVIEW NOTES
 ADDED ONCE COMPLETED.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 12:40 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 12:40 Sent To M
Notes
2008-09-08 12:40:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:38 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:38 Sent To Z
Notes
2007-09-05 10:39:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 09:18 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 09:18 Sent To E
Notes
2007-07-17 09:18:36TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 09:27 Sent To Z
Notes
2007-07-13 09:27:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 08:51 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 08:51 Sent To E
Notes
2007-03-20 08:51:58TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 10:05 Sent To Z
Notes
2007-03-09 10:06:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 09:36 Sent To E
Notes
2006-12-10 09:37:19PLANS ROUTED TO DVP'S DESK, REMOVED FORM INCOMING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:00 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:00 Sent To Z
Notes
2006-11-29 18:01:24RESUB/MMCLEAN DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 09:00 Rev Time 0.00
Received By alange Date 2006-10-11 Time 14:29 Sent To  
Notes
2006-10-12 14:29:36TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-07-20 Cont ID  
Sent By rkussner Date 2009-07-20 Time 14:07 Rev Time 0.00
Received By rkussner Date 2009-07-20 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-09-09 Cont ID  
Sent By tgordon Date 2008-09-09 Time 13:53 Rev Time 0.45
Received By tgordon Date 2008-09-09 Time 13:53 Sent To  
Notes
2008-09-09 13:54:18REVISION TO MECHANICAL PLAN A13, ENERGY CAL'S. AND
 COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 14:17 Rev Time 0.30
Received By tgordon Date 2007-09-12 Time 14:17 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-07-18 Cont ID  
Sent By tgordon Date 2007-07-18 Time 09:32 Rev Time 1.30
Received By tgordon Date 2007-07-18 Time 09:32 Sent To P
Notes
2007-07-18 10:01:36*** DENIED ***
 1) SEE MECHANICAL PLANS PAGE A13, SEE YELLOW HIGH
 LIGHTED DUCTS THAT NEED TO BE SIZED, OR SHOW TWO
 DIFFERENT SIZES FOR THE SAME DUCT, OR DUCT (FLEX)
 MISSING, OR SIZED WRONG. PLEASE CORRECT.
  
 2) SEE MECHANICAL PLANS LAUNDRY ROOM SHOWS A 4" METAL
 DUCT AND A 12X12 BOX PLEASE STATE ON PLAN WHAT THEY ARE
 FOR.
  
 3) MECHANICAL PLAN ALSO NEEDS THE PRINTED NAME OF THE
 PERSON WHO SIGNED THEM.
  
 4) MECHANICAL PLANS NEED THE JOB ADDRESS IN THE TITLE
 BLOCK.
  
 5) PLEASE SHOW THE SEER IN THE EQUIPMENT SCHEDULE.
  
 6) IS CLOTHES DRYER GAS OR ELECTRIC (NOT LISTED ON
 ELECTRICAL PANEL BUT SHOWN AS 220 VOLT) IF GAS PROVIDE
 COMBUSTION AIR.
  
 7) ENERGY CALCULATIONS SHOW THE WATER HEATER AS GAS,
 THE ELECTRICAL PLANS SHOW IT AS 220 VOLT, PLEASE
 CORRECT.
  
 8) SEE ENERGY CALCULATIONS ARE SHOWING THE WRONG BTU'S
 FOR THE ELECTRIC HEAT STRIPS, WHEN CONVERTED TO KW THEY
 DO NOT MATCH THE MECHANICAL PLANS, PLEASE CORRECT.
  
 9) ENERGY CALCULATIONS LINE 11 SHOWS DUCT INSULATION IS
 R-30, THE MECHANICAL PLANS SHOW THE DUCTS AS R-6,
 PLEASE CORRECT ENERGY CALCULATIONS OR SUBMIT
 MANUFACTURER'S SPECIFICATION SHEET FOR THE DUCTS
 (FLEX).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 10:39 Rev Time 0.20
Received By tgordon Date 2007-03-26 Time 10:39 Sent To P
Notes
2007-03-26 10:43:39*** DENIED ***
 1) SEE MECHANICAL PLANS PAGE A-13. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By tgordon Date 2006-12-11 Time 09:47 Rev Time 0.30
Received By tgordon Date 2006-12-11 Time 09:47 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-10-18 Time 08:53 Rev Time 1.00
Received By tgordon Date 2006-10-18 Time 08:53 Sent To Z
Notes
2006-10-18 09:10:08*** DENIED ***
 1) SEE PAGE A13 A/C SCHEDULE UNIT #1 EQUIPMENT SENSIBLE
 BTU'S ARE MORE THAN THE TOTAL BTU'S, PLEASE CORRECT.
  
 2) SEE A/C SCHEDULE UNIT #3 CONDENSER MODEL NUMBER IS
 FOR A 8 TON UNIT, PLEASE CORRECT.
  
 3) SEE SECOND FLOOR STUDY ROOM 10" RETURN AIR DUCT IS
 TO SMALL FOR 786 CFM'S OF SUPPLY AIR,PER FBC/R M1602.4,
 PLEASE CORRECT.
  
 4) PROVIDE RETURN SIR FOR AHU #1 TO FOYER SECOND FLOOR,
 PER 2004 FBC/R M 1602.4.
  
 5)ATTIC ACCESS MUST BE WITHIN SIX FEET OF THE AHU'S
 SERVICE PANEL, PER 2004 FBC/R M 1305.1.3, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-09-24 Cont ID  
Sent By mperson Date 2007-09-24 Time 14:00 Rev Time 0.00
Received By mperson Date 2007-09-24 Time 14:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-07-26 Cont ID  
Sent By mperson Date 2007-07-26 Time 10:08 Rev Time 1.25
Received By mperson Date 2007-07-26 Time 10:08 Sent To B
Notes
2007-07-26 11:42:13DENIED 4TH TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE WITH THE
 ADDITION OF BATH 4 AND CABANA BATH.:
  
 1. SHEET A15 THE RESUBMITTED ISOMETRIC SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 FOLLOWING AREAS. PER FBC-2004 CHAPTER 1, SECTION
 106.1.1 CONSTRUCTION DOCUMENTS (ISOMETRIC) SHALL BE OF
 SUFFICIENT CLARITY TO THE LOCATION OF THE PROPOSED
 WORK.
  
 A. ALL OF THE GROUND FLOOR PLUMBING (1/2 BATH,
 KITCHEN, AND CABANA BATH). PLEASE REFERENCE THE
 CORRECTED ISOMETRIC GROUND FLOOR PLUMBING THAT REFLECTS
 THE FLOOR PLAN ON THIS SHEET FOR THE RESUBMITTAL.
  
 B. 2ND FLOOR MASTER BATH DOES NOT INDICATE THE 1/8
 BEND OFFSETS OR WYE FITTINGS AND THE LAV BY SHOWER
 BEING INDICATED IN THE WRONG PLACE. THE TRAP IS BEING
 INDICATED AS GOING OUT THE BACK WALL. PLEASE INDICATE
 THE WASTE ARM AND CORRECT LOCATION OF TRAP.
  
 C. 2ND FLOOR LAUNDRY: SINK IN LAUNDRY IS MISLABELED,
 IT SHOULD BE INDICATED AS A LAUNDRY TRAY (L.T.). THE
 LAUNDRY TRAY WASTE ARM IS BEING INDICATED IN THE WRONG
 PLACE.
  
 D. 2ND FLOOR STUDY: THE SINK IS BEING INDICATED ON THE
 WRONG SIDE OF THE 4" HORIZONTAL SANITARY PIPE.
  
 E. 2ND FLOOR BATH 2: THE LAV WASTE IS BEING INDICATED
 IN THE WRONG PLACE.
  
 F. 2ND FLOOR BATH 3 AND 4: FLOOR PLAN ON SHEET A6 ARE
 INDICATING A TUBS, BUT THE SANITARY ISOMETRIC ARE
 INDICATING SHOWERS. PLEASE CLARIFY OR CORRECT THIS ON
 THE RESUBMITTAL.
  
 2. SHEET A15 PLUMBING NOTES: PLEASE DELETE THE
 FOLLOWING "PROVIDE MINIMUM PITCH 1/4" AT ALL HORIZONTAL
 BRANCHES AND SEWER LINES PER 701.01. PLEASE ADD IN ITS
 PLACE THE FOLLOWING "SLOPE OF HORIZONTAL DRAIN PIPE PER
 TABLE 704.1" ON THE RESUBMITTAL.
  
 3. SHEET A15 SANITARY ISOMETRIC RISER PLEASE INDICATE
 THE FOLLOWING.
  
 A. PER FBC-2004 PLUMBING SECTION, 708.3.4: CLEANOUT AT
 THE BASE OF THE 4" SOIL STACK TO THE 2ND FLOOR.
  
 B. PER FBC-2004 PLUMBING SECTION, 708.3.5: PLEASE
 INDICATE A TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER.
  
 4.SHEET A15 2ND FLOOR PLUMBING PLAN: PLEASE CORRECT
 THE BRANCH DRAIN TO THE LAUNDRY TO THREE INCH (3") PER
 FBC-2004 PLUMBING SECTION 406.3.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-03-26 Cont ID  
Sent By mperson Date 2007-03-26 Time 11:38 Rev Time 0.33
Received By mperson Date 2007-03-26 Time 11:38 Sent To B
Notes
2007-03-26 11:46:55DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 CHAPTER 1,SECTION 106.1.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-11 Cont ID  
Sent By mperson Date 2006-12-11 Time 11:45 Rev Time 0.33
Received By mperson Date 2006-12-11 Time 11:45 Sent To B
Notes
2006-12-11 13:12:52DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. ON SHEET A15 THE PLUMBING FLOOR PLAN LAYOUTS ARE
 INDICATED WRONG. THE KITCHEN AND 1/2 BATH SHOULD BE
 INDICATED AS THE GROUND FLOOR AND THE LAUNDRY, MASTER
 BATH, BATH 2 AND BATH 3 SHOULD BE INDICATED AS THE 2ND
 FLOOR PLUMBING. PLEASE CORRECT FOR THE RESUBMITTAL.
  
 2. ON SHEET A15 SANITARY RISER DIAGRAM: THE VENT
 INDICATED ON THE 2ND FLOOR PLUMBING PLAN IS MISSING ON
 THE SANITARY RISER DIAGRAM. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 3. ON SHEET A15 SANITARY RISER DIAGRAM:PLEASE REMOVE
 THE PARTIALLY DRAWN VENT TO THE FIRST FLOOR 1/2 BATH IT
 IS ALREADY INDICATED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By jleech Date 2006-10-19 Time 14:40 Rev Time 0.00
Received By jleech Date 2006-10-19 Time 14:40 Sent To B
Notes
2006-10-19 14:53:51DENIED;
 1.SANITARY RISER DIAGRAM; MASTER BATH ONLY HAS 2
 LAVATORIES. W/C IN HALF BATH IS NOT VENTED AS DRAWN.
 2.PLUMBING NOTES; HORIZONTAL PIPE TO BE PITCHED PER
 710.1. PIPE UNDER THREE INCH. TO SLOP A MINUMUM OF
 1/4".
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2007-09-12 Cont ID  
Sent By adavila Date 2007-09-12 Time 11:50 Rev Time 0.00
Received By adavila Date 2007-09-05 Time 14:15 Sent To M
Notes
2007-09-12 11:52:12PROVISO ALL TREES SHALL BE PLANTED PURSUANT TO THE CITY
 OF WEST PALM BEACH SUSTAINABLE PLANTING PLANS (ATTACHED
 TO LANDSCAPE PLANS).

Review Stop Z ZONING
Rev No 4 Status F Date 2007-07-17 Cont ID  
Sent By adavila Date 2007-07-17 Time 08:10 Rev Time 0.00
Received By adavila Date 2007-07-13 Time 12:24 Sent To I
Notes
2007-07-17 08:16:02PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. BALCONY 1 OF BEDROOM 2 SHALL BE SHOWN ON THE SURVEY
 AND SITE PLAN (REPEAT COMMENT).
 A. FLOOR PLANS SHOW THAT THE BALCONY PROJECTS 2 FEET 9
 INCHES INTO THE FRONT YARD; HOWEVER THE BALCONY IS
 STILL NOT SHOWN ON THE SITE PLAN OR SURVEY.
  
 2. PLEASE PROVIDE BUILDING HEIGHT FROM THE GRADE TO THE
 MID-POINT OF THE ROOF (REPEAT COMMENT).
 A. PLEASE NOTE THAT BUILDING HEIGHT MAY NOT EXCEED 30
 FEET FROM GRADE TO THE MID-POINT BETWEEN THE ROOF RIDGE
 AND THE ROOF EVE.
  
 3. PLEASE PROVIDE A TABULAR DATA TABLE WITH THE
 REQUIRED AND PROVIDED TREES AND SHRUBS (REPEAT
 COMMENT).
 A. PER SECTION 94-442(B)(2)(A), AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.IN
 ADDITION, AT LEAST ONE SHRUB SHALL BE PLANTED FOR EACH
 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF
 (REPEAT COMMENT).
 B. PLEASE NOTE THAT PER SECTION 94-442(C), PALM TREES
 MAY BE SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE
 SHADE OR FLOWERING TREES REQUIRED; HOWEVER, WHEN PALM
 TREES ARE SUBSTITUTED FOR SHADE TREES, TWO PALM TREES
 SHALL BE PROVIDED FOR EACH REQUIRED SHADE TREE.
  
 4. SURVEY AND SITE PLAN DIMENSIONS SHALL SHOW SAME
 CONDITION.
 A. SOUTH PROPERTY LINE DEPTH DIMENSION AND WEST
 PROPERTY LINE WIDTH DIMENSION SHALL BE REVISED TO SHOW
 DIMENSIONS ON SURVEY.
  
 5. PLEASE NOTE THAT SETBACK DIMENSIONS ARE MEASURED TO
 THE FURTHEST PROJECTION POINT, TO INCLUDE A VENEER OR
 CLADDING.THIS SHALL APPLY TO ALL BALCONIES.
  
 6. PROPOSED POOL, POOL DECK, AND WALL/FENCE (WITH AN
 APPROVED EASEMENT CONSENT FORM), SHALL BE APPROVED
 UNDER SEPARATE PERMITS.THIS SHALL BE NOTED ON THE
 SITE PLAN AND LANDSCAPE PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-03-16 Cont ID  
Sent By adavila Date 2007-03-16 Time 16:02 Rev Time 0.00
Received By adavila Date 2007-03-16 Time 16:02 Sent To I
Notes
2007-03-16 16:16:30PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SECOND FLOOR TUB POP-OUT IS PART OF THE PRIMARY
 STRUCTURE AND SHALL MEET THE MINIMUM REQUIRED SIDE
 SETBACK OF 12.5 FEET FROM THE SIDE PROPERTY LINE.
  
 2. SETBACK DIMENSIONS FROM PROPERTY LINE TO A/C UNITS
 AND ALL OTHER MECHANICAL EQUIPMENT SHALL BE PROVIDED.
  
 3. BALCONY 1 OF BEDROOM 2 SHALL BE SHOWN ON THE SURVEY
 AND SITE PLAN.
  
 4. PLEASE PROVIDE BUILDING HEIGHT FROM THE GRADE TO THE
 MID-POINT OF THE ROOF.
  
 5. PLEASE PROVIDE A TABULAR DATA TABLE WITH THE
 REQUIRED AND PROVIDED TREES AND SHRUBS.
 A. PER SECTION 94-442(B)(2)(A), AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.IN
 ADDITION, AT LEAST ONE SHRUB SHALL BE PLANTED FOR EACH
 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-08 Cont ID  
Sent By mmclean Date 2006-12-08 Time 07:58 Rev Time 0.00
Received By mmclean Date 2006-12-08 Time 07:58 Sent To I
Notes
2006-12-08 08:38:34DENIED. 2ND REQUEST.
 1. THE BALCONY ON SECOND FLOOR STILL PROJECTS 4FT INTO
 SETBACK. SEC 94-305(2).
 2. THE ROOF PROJECTION FROM BALCONY CAN ONLY BE LINED
 WITH THE BALCONY PROJECTING 3FT. SEC 94-305(2). PLANS
 A-2 SHOWS THE BALCONY PROJECTING 4FT, 1FT ROOF
 OVERHANG, WHICH CAN ONLY PROJECT 3FT INCLUDING
 PILISTAR.
 3. THE 2ND FLOOR PROJECTION BAY WINDOWS CAN ONLY
 PROJECT18 INCHES ON SIDE SETBACK OF CORTEZ.SURVEYS
 SHOWS 2 1/2 FT ON SIDE. SEC 94-305(8)
  
 NOTE: THE PROPOSED A/C UNIT SHALL NOT BE CLOSER THAN
 1.41FT FROM SIDE AND 8FT REAR PROPERTY LINE.
 NOTE: SEPARATE PERMIT MUST BE PULLED FOR THE PROPOSED
 POOL/SPA
 NOTE: SEPARATE PERMIT MUST BE PULLED FOR THE PROPOSED
 FENCE/GATE/WALL WITH CITY OF WEST PALM BEACH UTILITY
 EASEMENT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By mmclean Date 2006-10-18 Time 14:18 Rev Time 0.00
Received By mmclean Date 2006-10-18 Time 14:18 Sent To P
Notes
2006-10-18 14:29:47DENIED,
 1. MUST PULL A SEPARATE PERMIT FOR THE PROPOSED
 POOL/SPA.
 2. MUST PULL A SEPARATE PERMIT FOR THE PROPOSED WALL
 WITH EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT.
 3. THE PROPOSED BALCONY CAN ONLY PROJECT 3FT INTO
 REQUIRED SETBACK. SEC 94-305 (2)
 4. THE PROPOSED BAY WINDOWS CAN ONLY PROJECT 18 INCHES
 INTO ANY SIDE SETBACK. SEC 94-305(8).
  
  
 NOTE: THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 1FT FROM SIDE PROPERTY LINE.