Plan Review Details - Permit 06100138
Plan Review Stops For Permit 06100138
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 10:19 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 10:18 Sent To PC
Notes
2006-10-16 10:20:01TWO EXTENSIONS #0007 FRO UNIT 120 AND #0008 FOR UNIT
 121 WERE CREATED.TWO PERMIT NECESSARY?
2006-10-13 14:43:28NEEDS, TWO SUITES.?

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 17:36 Rev Time 1.10
Received By jwitmer Date 2007-01-22 Time 17:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By jwitmer Date 2006-12-13 Time 15:05 Rev Time 2.22
Received By jwitmer Date 2006-12-13 Time 15:05 Sent To  
Notes
2006-12-13 15:19:45BUILDING PLAN REVIEW
 PERMIT: 06100138
 ADD: 1475 CENTREPARK BLVDSUITES 120 & 121
 CONT: PASS INTERNATIONAL
 TEL: (561)706-7201
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COVERSHEET PROJECT DATA BUILDING TYPE IV
 UNPROTECTED UNDER THE 2004 FBC
 IS FOR HEAVY TIMBER CONSTRUCTION PLEASE UPDATE
 THE BUILDING TRMINOLGY TO THE 2004 FBC.
 TABLE 601.
  
 4) COVERSHEET GENERAL NOT# 3 INDICATES DESIGNED TO
 THE AMERICANS WITH DISSIBILITY ACT,
 PLEASE CORRECT TO THE FLORIDA BUILDING CODE CHAPTER 11,
  
 THE FLORIDA ACCESSIBILITY REQUIREMEENTS ARE MORE
 STRINGENT
 THAN THE ADA ANDAPPROVED BY THE DEPARTMENT OF
 JUSTICEAS SO.
  
 5) SHEET A-2 BREAK ROOM SINKS, ARE HIGHLIGHTED WITH THE
 LANGUAGE
 INDICATING A FORWARD APPROACH COULD BE MADE EXCEPT
 THAT THE PLAN STILL INDICATES THERE TO BEADJUSTIBLE
 SHELVING IN THE ACCESSIBLE UNITS.
  
 6)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 G ) NUMBER OF FLOORS
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By alange Date 2006-10-12 Time 12:44 Rev Time 0.00
Received By alange Date 2006-10-12 Time 12:44 Sent To  
Notes
2006-10-12 12:49:59DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.SHOW HOW SINKS IN BOTH KITCHEN AREAS WILL COMPLY
 WITH THE CLEAR FLOOR SPACE FOR A WEEL CHAIRFBC
 11-4.24.5
 ONE SINK MAY NEED TO BE MOVED OVER AND ONE MAY NEED TO
 HAVE A CLEAR AREA UNDERNEATH.SHOW ON PLANS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-19 Cont ID  
Sent By dpalmer Date 2007-10-19 Time 08:04 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 17:53 Sent To PC
Notes
2007-10-19 08:04:52REV FOR SUITE/METER LABELING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 13:17 Rev Time 0.00
Received By dpalmer Date 2007-01-22 Time 13:17 Sent To  
Notes
2007-01-22 13:18:16STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 13:57 Rev Time 0.00
Received By dpalmer Date 2006-12-08 Time 09:17 Sent To I
Notes
2006-12-08 14:00:11**** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 WHICH IS STILL IN NEED OF ADDRESSING ALONG WITH SOME
 NEW NOTES WITH THE CHANGES MADE ON PLANS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A NOTATION OF "NO" OR "OK".
 PLEASE SEE SOME MAY BE NOTED AS "OK/NO" AS PART OF THE
 COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY.
  
 1) NOTE: OK..
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE THE NOTE WAS LOCATED ABOUT H
 NON-BONDING OF THE NEUTRAL, HOWEVER A NOTE OR
 INDICATION FOR THE REQUIRED "FLOATING NEUTRAL" COULD
 NOT LOCATE DON THE RISER. THIS IS BEING REQUESTED AS WE
 HAVE HAD NUMEROUS SITUATIONS OUT IN THE FIELD WHERE
 THIS IS NOT BEING DONE CORRECTLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE/ NOTE THE "FLOATING NEUTRAL" AT THE
 TENANT METERS. 250.6, 250.24B.
  
 6) NOTE:NO, PLEASE SEE 13-415.1.ABC.1.1, AND .1.2.
 PLEASE SEE CONTROLS REQUIRED COULD NOT BE LOCATED.
 PLEASE SEE PREVIOUS REVIEW NOTE.
 PLEASE SEE ENERGY CALCULATIONS WHICH MENTIONS "MANUAL
 ON/OFF" YET, ACTUALLY THIS SHOULD INDICATE "AUTO"
 ON/OFF"ON THE PROGRAM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR MIN
 LIGHTING CONTROLS FOR EACH SPACE.
 PLEASE SEE 13-415.2.ABC.1 FOR MAX LPD'S. (LIGHTING
 POWER DENSITIES).
  
 7) NOTE: OK/NO, PLEASE SEE POWER PLANS WHICH THE ROOM
 #'S ARE NOT ON PLANS. THIS IS OK ON THE LIGHTING
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM/OFFICE DESIGNATIONS SPECIFIC TO
 ROOM OR AREA. IE; OFFICE RECEPTS 101, OFFICE RECEPTS
 104, ETC.
 408.6, 240.4, 310.16.
 FBC 106.1.2
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: NO/OK. PLEASE SEE THE LOCATIONS ARE NOW BEING
 SHOWN; HOWEVER PLEASE SEE NOTE ON RISER MENTIONS 25FT
 MAX FOR THE CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER YET PLEASE SEE 240.21C AS THE CONDUCTORS ON
 THE SECONDARY SIDE ARE ONLY PERMITTED AT 25FT IN A
 DIFFERENT SCENARIO. PLEASE ADJUST NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SHOW LOCATIONS OF TRANSFORMERS.
 PLEASE ALSO PROVIDE MORE OF A DETAIL FOR THE "TAPS"
 BEING DONE ON THE PRIMARY SIDES OF THE TRANSFORMERS FOR
 THE VAV'S.
 PLEASE SEE 240.21, 450.9 ETC
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-08 09:18:04REMOVED FROM INCOMING, IN ELECTRICA FOR REVIEW AND WILL
 BE ROUTED BACK TO INCOMING ONCE COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 14:41 Sent To  
Notes
2006-10-13 15:29:10 
  
 ***** UNSAT ******
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES SHALL
 BE REFELECTED ON PLANS.2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101 FBC 2004. SOME OF THESE ARE SHOWN ON
 ARCHITECTURAL PLANS, HOWEVER SHOULD ALSO BE ON
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE BE SURE PLANS ARE SIGNED WITH SIGNATURE
 AS ON FILE AND RECOGNIZED BY THE CITY OF WEST PALM
 BEACH.
 FS 471.025
  
 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 4) NOTE: PLEASE INDICATE MIN AIC RATINGS ON THE OCP
 DEVICES AT MAINS.
 110.9, FBC 106.1.2
  
 5) NOTE: PLEASE INDICATE/ NOTE THE "FLOATING NEUTRAL"
 AT THE TENANT METERS. 250.6, 250.24B.
  
 6) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MIN LIGTHING CONTROLS FOR EACH SPACE.
 PLEASE SEE 13-415.2.ABC.1 FOR MAX LPD'S. (LIGHTING
 POWER DENSITIES).
  
 7) NOTE: PLEASE PROVIDE ROOM/OFFICE DESIGNATIONS
 SPECIFIC TO ROOM OR AREA. IE; OFFICE RECEPTS 101,
 OFFICE RECETPS 104, ETC.
 408.6, 240.4, 310.16.
 FBC 106.1.2
  
 8) NOTE: PLEASE LIST THE MIN LIGHTING/AUDIO LEVELS
 REQUIRED PER2004 FBC ADA 11-4.28. IT IS NOTED ON
 PLANS, HOWEVER SPECIFIC LEVELS IS REQUIRED TO BE SHOWN
 FOR EACH.
  
 9) NOTE: PLEASE VERIFY RISER AS THIS SHOWS "NEUTRAL"
 CONDUCTORS ON THE LINE SIDE OF THE TRANSFORMERS? PLEASE
 SEE 250.20,250.30, ETC.
  
 10) NOTE: PLEASE VERIFY AND SHOW LOCATIONS OF
 TRANSFORMERS. PLEASE ALSO PROVIDEMORE OF A DETAIL FOR
 THE "TAPS" BEING DONE ON THE PRIMARY SIDES OF THE
 TRANSFORMERS FOR THE VAV'S.
 PLEASE SEE 240.21, 450.9 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 12:35 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 12:35 Sent To  
Notes
2007-01-24 12:37:10*****APPROVED*****
  
  
 SHEET E- 2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 12:58 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 12:58 Sent To  
Notes
2006-12-12 13:02:31*****APPROVED*****
  
  
  
  
 PLANS TO BE STAMPED WHEN OTHER PLAN REVIEWS COMMENTS
 HAVE BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mawillia Date 2006-10-26 Time 14:47 Rev Time 0.00
Received By mawillia Date 2006-10-26 Time 14:34 Sent To  
Notes
2006-10-26 14:59:41*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 2.ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST DEBRIS
 SHALL BE REMOVED FROM THE STRUCTURE AND ITS IMMEDIATE
 VICINITY AT THE END OF THE SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATIONS.
  
 3.EXITS AND EXIT ACCESS CORRIDORS ARE TO BE
 MAINTAINED AND REMAIN CLEAR AND OBSTRUCTED.
  
 4.)IF THE SCOPE OF TE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND PLAN ARE TO BE SUBMITTED
 FOR REVIEW.
  
 5.INTERIOR FINISH FOR WALL AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 10:26 Sent To E
Notes
2007-10-18 10:26:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 13:56 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 13:56 Sent To M
Notes
2007-08-21 13:56:31TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 11:32 Sent To  
Notes
2007-01-24 15:03:35 
  
  
 1/24/07PASSED.SENT TO DEWEY PALMER'S DESK FOR
 PROCESSING.RB
2007-01-22 11:35:05TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 14:26 Sent To  
Notes
2006-12-12 11:39:30TO "BOB"#3
2006-11-21 14:26:23WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-27 Cont ID  
Sent By jleech Date 2006-10-27 Time 14:50 Rev Time 0.00
Received By jleech Date 2006-10-06 Time 15:50 Sent To  
Notes
2006-10-12 09:50:34TO "BOB"#18
2006-10-06 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-22 Cont ID  
Sent By tgordon Date 2007-08-22 Time 08:11 Rev Time 0.20
Received By tgordon Date 2007-08-22 Time 08:11 Sent To  
Notes
2007-08-22 08:13:26REVISION, SUBMITTED DETAIL TO WALL WERE FIRE DAMPER IS
 INSTALLED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 14:39 Rev Time 0.30
Received By tgordon Date 2006-12-12 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 14:22 Rev Time 0.25
Received By tgordon Date 2006-10-16 Time 14:22 Sent To  
Notes
2006-10-16 14:26:17*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE
 # 2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-21 Cont ID  
Sent By jleech Date 2006-12-21 Time 14:08 Rev Time 0.00
Received By jleech Date 2006-12-21 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-27 Cont ID  
Sent By jleech Date 2006-10-27 Time 14:18 Rev Time 0.00
Received By jleech Date 2006-10-27 Time 14:18 Sent To  
Notes
2006-10-27 14:39:38DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTE 2.
 2. ADD TO KEY NOTE #7 NO DEAD ENDS INSANITARY
 DRAINAGE SYSTEM LONGER THAN 2 FT PLUMBING INSPECTION
 REQUIRED.
 3.BREAK ROOM SINKS SHALL COMPLY WITH FBC-2004 CHAPTER
 11 SECTIONS 11-4.24.2 THRU 11-4.24.7.
 11-4.24.2HEIGHT OF SINK
 11-4.24.3KNEE CKEARANCE
 11-4.24.4DEPTH OF SINK
 11-4.25.5CLEAR FLOOR SPACE
 11-4.25.6EXPOSED PIPES
 11-4.24.7FAUCETS
 SHOW ALL MEASUREMENTS PERTAINING TO ABOVE CODES ON
 PAGE A-2 ELEVATION 1
 SHOW CLEAR FLOOR SPACE ON FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy