Plan Review Details - Permit 06100105
Plan Review Stops For Permit 06100105
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-11-29 Cont ID  
Sent By mperson Date 2006-11-29 Time 11:43 Rev Time 0.33
Received By mperson Date 2006-11-29 Time 11:43 Sent To PC
Notes
2006-11-29 11:50:30REVISION: CHANGE DRYER TO A "FUTURE" DRYER
  
 ************PROVISO************
 IF FUTURE DRYER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,000 CUBIC FEET REQUIRED.
  
 FUTURE DRYER TO HAVE SHUT OFF VALVE INSTALLED AND TO BE
 CAPPED GAS TIGHT PER FBC-2004 FUEL GAS, SECTION 404.12.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-10-10 Cont ID  
Sent By mperson Date 2006-10-10 Time 15:38 Rev Time 0.33
Received By mperson Date 2006-10-10 Time 15:38 Sent To PC
Notes
2006-10-10 15:42:37 
  
 ******PROVISO******
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,000 CUBIC FEET REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 13:14 Sent To G
Notes
2006-11-15 13:15:36TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By mperson Date 2006-10-10 Time 15:43 Rev Time 0.00
Received By mperson Date 2006-10-06 Time 09:17 Sent To  
Notes
2006-10-06 00:00:00TO "G" BOX