Plan Review Details - Permit 06100098
Plan Review Stops For Permit 06100098
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-11 Cont ID  
Sent By lursu Date 2006-12-11 Time 10:08 Rev Time 0.00
Received By lursu Date 2006-10-04 Time 09:53 Sent To  
Notes
2006-12-11 10:08:51PERMIT WAS CORRECTLY ASSIGNED.
2006-10-04 00:00:00NEED AN EXTENSION FOR THIS ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By rmcdouga Date 2006-12-11 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2006-12-11 Time 07:33 Sent To  
Notes
2006-12-11 10:04:57SEE ELECTRICAL COMMENTS. ENGINEERS ADDRESS IS REQUIRED
 ON THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By rmcdouga Date 2006-10-10 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2006-10-10 Time 09:11 Sent To  
Notes
2006-10-10 10:48:59 
 DENIED BY BUILDING
  
 1)PLANS FOR PUBLIC BUILDINGS ARE REQUIRED TO BE
 PREPARED, SIGNED, SEALED AND DATED BY A FLORIDA
 CERITIFIED DESIGN PROFESSIONAL.SEE FS 471.003 AND
 481.229.
  
 2)SPECIFY THE LEVEL OF ALTERATION FOR THE WORK AS
 INDICATED IN CHAPTER 3 OF THE 2004 FBC EXISTING
 BUILDING CODE.
  
 3)SPECIFY THE CODES AND EDITIONS THAT APPLY TO THE
 WORK.
  
 4)SPECIFY THE BUILDING'S CONSTRUCTION TYPE,
 OCCUPANCY, HEIGHT, NUMBER OF STORIES, AND INDICATE IF
 BUILDING IS SPRINKLERED.
  
 5) INDICATE THE LOCATION OF EXISTING TENANT SEPARATION
 WALLS AND OTHER FIRE RATED WALLS SHOWN ON THE PLANS.
  
 6) IF SPRINKLER HEADS ARE REQUIRED TO BE RELOCATED,
 SUBMIT DRAWINGS UNDER A SEPARATE PERMIT.
  
 7) ADDITIONAL PERMITS MAY BE REQUIRED FOR ELECTRICAL,
 MECHANICAL, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 20:17 Sent To I
Notes
2006-12-07 20:23:50****** PASSED PENDING ,,,,, A TITLE BLOCK FOR THE
 ENGINEER OF RECORD MUST BE ON PLANS PER FAC
 61G15-23.002.
 PLEASE KNOW THIS INFORMATION MAY BE HAND WRITTEN ON
 PLANS. THIS MUST BE DONE BEFORE PLANS CAN EB ISSUED.
 STAMPED ELECTRICAL FOR RELOCATION OF ONE RECEPT ONLY.
2006-12-07 20:17:29REMOVED FROM INCOMING, IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 17:14 Sent To  
Notes
2006-10-12 17:32:12****UNSAT ****
  
 1) NOTE: PLEASE SEE FLORIDA STATUES, 481.229(1)(C) AS
 PLANS ARE REQUIRED TO BE DONE BY ANARCHITECT AT
 MINIMUM.
  
 2) NOTE: PLEASE SEE "REDTAG" MENTIONS ELECTRICAL IN
 WALL(S) ALSO, WHICH IS NOT SHOWN ON PLANS, HOWEVER WILL
 BE REQUIRED TO BE SHOWN AT THIS TIME.
 PLEASE INDICATE CIRCUITING AS REQUIRED/NEED.
 408.4,
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE NEC 517 FOR POSSIBLE PATIENT CARE
 AREAS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 13:40 Rev Time 0.00
Received By mawillia Date 2006-12-11 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mawillia Date 2006-10-26 Time 14:10 Rev Time 0.00
Received By mawillia Date 2006-10-26 Time 14:10 Sent To  
Notes
2006-10-26 14:22:18*****DENIED*****
  
  
  
 1. IF SO EQUIPPED,PLEASE SHOW THE LOCATION OF FIRE
 SPRINKLER HEADS AND/OR FIRE ALARM DEVICES.HOW WILL
 THEY BE AFFECTED BY THE ADDITION OF THE PARTITION
 WALL.
  
 2.IF THE ADDITION OF THE PARTITION WALL REQUIRES
 MODIFICATION OF FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM
 DEVICES, SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 REVIEW AND APPROVAL.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 11:33 Sent To  
Notes
2006-12-08 16:47:32TO "BOB"15
2006-11-17 11:33:34WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-26 Cont ID  
Sent By mawillia Date 2006-10-26 Time 14:24 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 11:29 Sent To  
Notes
2006-10-05 00:00:00TO "BOB"#2