| Plan Review Stops For Permit 06100097 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-12 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2006-10-06 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-13 |
Time |
11:39 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-10-13 |
Time |
11:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-12 |
Time |
13:43 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-12 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2006-10-12 13:52:42 | *** DENIED *** | | | 1) NEED TO SHOW MODEL NUMBER FOR | | | AIR HANDLER AND CONDENSER UNIT ON | | | PLANS. | | | | | | 2) SUPPLY AND RETURN DUCTS APPEAR | | | TO JOIN TOGETHER AT THE AIR HANDLER | | | PLEASE SHOW JUMP OVER OR OTHER | | | METHOD OF SEPARATION. | | | | | | 3) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
|