Plan Review Details - Permit 06100075
Plan Review Stops For Permit 06100075
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-04-11 Cont ID  
Sent By lursu Date 2007-04-11 Time 11:26 Rev Time 0.00
Received By lursu Date 2007-04-11 Time 10:37 Sent To  
Notes
2007-05-31 14:44:55BASED ON THE NEW ADDRESSING GUIDE POLICY FOR THE CITY
 OF WEST PALM BEACH - NO LETTERS ARE ALLOWED TO BE USED
 FOR ANY SITE ADDRESSES -AN ADDRESS CHANGE IS REQUIRED
 FOR THE UNIFIED UNIT .PLEASE CONTACT THIS OFFICE TO
 REQUEST AN ADDRESS CHANGE .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-04-11 11:27:35BASED ON THE UNITY OF TITLE RECEIVED FOR THESE THREE
 UNITS INVOLVED : C2, C3 & C4 , THE PERMIT IS ATTACHED
 TO THE LOWEST PCN WHICH CORRESPONDS TO UNIT C2.
 THE ADDRESS IS 1970 S DIXIE HWY # C2.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By lursu Date 2006-10-04 Time 15:30 Rev Time 0.00
Received By lursu Date 2006-10-03 Time 13:57 Sent To  
Notes
2006-10-04 00:00:00SINCE INTERIOR WORK WILL BE DONE TO
 COMBIEN ALL THREE UNITS INTO ON E, A
 UNITY OF TITLE IS REUQIRED.BASED ON THIS
 A NEW ADDRESS WILL BE ASSIGNED.
2006-10-03 00:00:00NO ADDRESS IN COMMUNITY PLUS/HAD TO KEY
 IN PER LILI/1970 S DIXIE HWY UNIT C2 C3
 & C4/UNITY OF TITLE REQUIRED BEFORE
 PERMITTING

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-06-03 Cont ID  
Sent By shill Date 2008-06-03 Time 10:31 Rev Time 0.00
Received By shill Date 2008-06-03 Time 10:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 13:36 Rev Time 0.00
Received By shill Date 2008-05-29 Time 13:36 Sent To P
Notes
2008-05-29 13:44:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FS481, FAC61G1-15, ARCHITECT'S SIGNATURE IS TO BE
 AN ORIGINAL (ENERGY CALCS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-03-24 Cont ID  
Sent By shill Date 2008-03-24 Time 09:01 Rev Time 0.00
Received By shill Date 2008-03-24 Time 09:01 Sent To  
Notes
2008-03-24 09:22:11****CORRECTIONS****
 ****REVISED 4/11/08****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.TWO COMPLETE ORIGINAL SETS REQUIRED FOR PERMIT
 ISSUANCE.ONLY ONE SET WAS SUBMITTED.
  
 2.SEE BUILDING REVIEW 3, COMMENT 2 (ATTACHED)
 PERFORMED BY KEN CONRAD WHEREIN HE REQUESTED EVIDENCE
 OF ORIGINAL DESIGNER NOTIFICATION.THIS NOTIFICATION,
 WHICH I HAVE SEEN PREVIOUSLY, HAS APPARENTLY BEEN
 REMOVED.THIS IS REQUIRED PRIOR TO ISSUANCE OF ANY
 REVISION DESIGNED BY A DESIGNER OTHER THAN THE ORIGINAL
 DESIGNER OF RECORD OR NEW PLANS SHOWING CODE COMPLIANCE
 MUST BE PROVIDED.
  
 3.SEE ATTACHED FS61G1-18.002, PROCEDURES FOR A
 SUCCESSOR ARCHITECT ADOPTING AS HIS OWN THE WORK OF
 ANOTHER ARCHITECT.A LETTER HAS BEEN DELIVERED TO THIS
 OFFICE STATING THAT G. RAYMOND BERRY IS NOT A SUCCESSOR
 ARCHITECT.I APOLOGIZE FOR MY CONFUSION, BUT
 ARCHITECT'S INTENTIONS REGARDING DESIGN DOCUMENTS IS
 NOT CLEAR TO ME.ARCHITECT WAS INFORMED THROUGH PLAN
 REVIEW COMMENTS SUCCESSOR DESIGNER REQUIREMENTS AND
 DOCUMENTS REQUIRED.THE NEW ARCHITECT AND PREVIOUS
 ARCHITECT HAVE AN UNDERSTANDING THAT THE PREVIOUS
 ARCHITECT'S WORK IS NOT TO BE USED, BUT THE NEW
 ARCHITECT DID NOT DISCLOSE THIS INFORMATION AND DID NOT
 SUBMIT NEW PLANS.WHAT WAS/IS THE NEW ARCHITECT'S
 INTENT AS TO WHAT IS TO BE USED TO DOCUMENT THIS
 PROJECT AS REQUIRED BY FLORIDA STATUTE?THE ONE
 ARCHITECTURAL SHEET SUBMITTED DOES NOT PROVIDE ENOUGH
 INFORMATION TO SHOW CODE COMPLIANCE FOR THE PROJECT.
 IF THE NEW ARCHITECT HAS TAKEN OVER THE PROJECT BUT IS
 NOT A SUCCESSOR ARCHITECT AS STATED, DOESN'T THAT
 INVALIDATE THE PLANS WHICH WE HAVE ON FILE, REQUIRING
 NEW PLANS?PLEASE NOTE THAT SOME OF THE DELAY WHICH IS
 OCCURRING NOW IS DUE TO INCOMPLETE OR INCORRECT
 INFORMATION PROVIDED.
  
 I UNDERSTAND THAT YOU ARE WORKING ON THIS ISSUE WITH
 KEN STEVENS AND ROBERT BROWN (CONSTRUCTION SERVICES
 DEPARTMENT).PLEASE RESOLVE THIS ISSUE; THIS WILL BE
 REQUIRED PRIOR TO ISSUANCE OF THE REVISION.
  
 4.SEE FIRESTOP C-AJ-1042 N SHEET A1.PLEASE CLARIFY
 WHERE THIS WILL BE UTILIZED AS THIS THROUGH UL
 PENETRATION FIRESTOP SYSTEM HAS A T RATING OF 0.SEE
 FBC712.4.1.2. THE T RATING WAS NOT INCLUDED IN THE
 DETAIL.PLEASE REVISE SO THAT USE AND LIMITATIONS OF
 THIS DETAIL ARE READILY APPARENT.
  
 5.OTHER SHEETS, SUCH AS A2, A3, AC1, ETC. ARE
 AFFECTED BY THE REMOVAL OF THE SINK.PLEASE REVISE ALL
 AFFECTED SHEETS.
  
 6.IF NEW PLANS ARE SUBMITTED, PLEASE NOTE THAT MS.
 DELASTATIOUS SIGNED AND SEALED THE ENERGY COMPLIANCE
 FORM AS WELL AS THE MEP ENGINEER(S).MR. BERRY HAS
 SUBMITTING NEW PLUMBING AND ELECTRIC SHEETS; THEREFORE,
 IT APPEARS THAT MR. BERRY'S OFFICE IS ALSO TO BECOME
 DESIGNER OF RECORD FOR MEPS AS WELL.IS MR. BERRY
 ACTING AS SUCCESSOR ENGINEER OR NOT?HAVE THESE DESIGN
 PROFESSIONALS BEEN ADVISED?
  
 7.AS I WAS UNAWARE THAT ALL WORK WAS BEING RECREATED
 RATHER THAN ARCHITECT TAKING OVER AS SUCCESSOR
 ARCHITECT, ONLY ITEMS CLOUDED AS A CHANGE WERE
 REVIEWED.UPON FURTHER REVIEW, IT APPEARS THAT THE
 PLANS ARE NOT CONSISTENT.THE SQUARE FOOT AREA
 DIFFERS; PLEASE CLARIFY.A LEVEL 2 ALTERATION WAS
 DECLARED BY THE NEW ARCHITECT, PERMIT WAS ISSUED AS A
 LEVEL 3.EITHER REVISE THE NEW PLAN OR PROVIDE
 JUSTIFICATION FOR LEVEL 2 ALTERATION.SHEET A1 WAS A
 LIFE SAFETY PLAN; IF OLD SHEETS ARE VOIDED AS
 APPARENTLY WOULD BE APPROPRIATE, ALL INFORMATION ON THE
 OLD SHEET A1 WOULD BE REQUIRED.
  
 8.MY INITIAL REVIEW WAS PERFORMED BASED ON MR.
 CONRAD'S COMMENTS AND CLOUDED ITEMS WHICH SHOULD HAVE
 INDICATED CHANGES TO AN APPROVED PLAN.AS APPARENTLY
 THE ENTIRE SHEET CHANGED, IT WOULD HAVE BEEN
 APPROPRIATE TO INDICATE SUCH (EITHER BY CLOUDING THE
 SHEET NUMBER, OR CLOUDING THE ENTIRE SHEET).SOME OF
 THE NEW COMMENTS ARE DUE TO THE FACT THAT A COMPLETE
 REVIEW OF ALL INFORMATION ON THE NEW A1 WAS NEVER DONE
 AS ONLY ITEMS WHICH HAVE CHANGED ARE REVIEWED FOR
 REVISIONS.IF THE NEW ARCHITECT CANNOT INDICATE WHAT
 HAS CHANGED, AS APPEARS TO BE THE CASE NOW AS THE NEW
 ARCHITECT STATES THAT THEY DID NOT HAVE ACCESS TO THE
 ORIGINAL PLANS, A COMPLETELY NEW REVIEW WOULD BE
 APPROPRIATE AS THERE MAY BE ADDITIONAL INFORMATION
 WHICH HAS CHANGED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-02-27 Cont ID  
Sent By shill Date 2008-02-27 Time 15:13 Rev Time 0.00
Received By shill Date 2008-02-27 Time 15:13 Sent To  
Notes
2008-02-27 15:18:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE PLUMBING COMMENTS.BASED ON THE INFORMATION
 PROVIDED BY THE ARCHITECT'S OFFICE, THE OWNER, AND THE
 CONTRACTOR, THIS AREA IS REQUIRED TO BE ACCESSIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-07 Cont ID  
Sent By shill Date 2007-12-07 Time 11:29 Rev Time 0.00
Received By shill Date 2007-12-07 Time 11:29 Sent To  
Notes
2007-12-07 11:30:04REVISION (12/4 AND 12/6)
 A1, A2

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-12-06 Cont ID  
Sent By shill Date 2007-12-06 Time 07:54 Rev Time 0.00
Received By shill Date 2007-12-06 Time 07:54 Sent To  
Notes
2007-12-06 08:34:10****CORRECTIONS****
 ****REVISION DATED 12/4/7****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE ARCHITECT'S RESPONSE TO THE PREVIOUS CORRECTION
 LIST REGARDING ENERGY CALC AREA OF 2653 NOT CORRELATING
 WITH THE SQUARE FOOT AREA ON THE PLAN OF 2910 IS NOTED.
 ARCHITECT STATES THAT THIS IS THE DIFFERENCE BETWEEN
 GROSS VS. NET.SEE FBC TABLE 1004.1.2, MERCANTILE
 OCCUPANT LOAD IS TO BE BASED ON GROSS, NOT NET.AT
 2910/30 (STORES FIRST FLOOR, SEE FBC TABLE 1004),
 OCCUPANT LOAD SHOULD BE 97, NOT 49 AS SHOWN ON THE
 PLAN.ENERGY CALCS AREA IS TO BE OUTSIDE WALL TO
 OUTSIDE WALL, SEE FBC13-202, DEFINITION OF GROSS FLOOR
 AREA.IF BUILDING AREA AND ENERGY CALCS BOTH REQUIRE
 GROSS AREA, THEY SHOULD BE THE SAME. ALSO PLEASE REVISE
 OCCPUANT LOAD ON THE PLAN.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-20 Cont ID  
Sent By shill Date 2007-11-20 Time 09:53 Rev Time 0.00
Received By shill Date 2007-11-20 Time 09:53 Sent To  
Notes
2007-11-20 10:07:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.NOT ADDRESSED, SEE ELECTRIC COMMENTS REGARDING
 CHANGE OF ARCHITECT.
  
 3.THE DETIAL IS INCOMPLETE.PLEASE SEE UL FIRE
 RESISTANCE DIRECTORY.FOR INSTANCE, FOR THE COLUMN, NO
 SPECIFICATION FOR CORNER BEAD OR SCREWS WAS SPECIFIED
 ON THE PLAN (ONLY "SECOND LAYER OF 5/8" GWB").THE
 PLAN STATES "GWB" BUT THE UL ASSEMBLY SPECIFIES
 WALLBOARD "CLASSIFIED FOR USE IN FIRE RESISTANT
 ASEMBLIES."PLEASE REVISE ALL FIRE RESISTANCE RATING
 DETAILS TO INCLUDE ALL REQUIRED INFORMATION.
  
 4.FROM PREVIOUS LIST; PLEASE INDICATE THE EXISTING
 TESTED ASSEMBLY NUMBER USED FOR THE TENANT SEPARATION
 AT THE EXISTING MERCANTILE SEPARATION.THE RESPONSE
 LETTER STATES THIS WAS ADDED, BUT I AM UNABLE TO LOCATE
 IT.ALSO SHOW ALL REQUIRED FIRE RESISTANCE RATINGS ON
 THE FLOOR PLAN.THERE IS A NOTE WITH A SPEC POINTING
 TO THIS WALL BUT NOTHING TO SPECIFY FIRE RESISTANCE
 RATING.
  
 5.RESPONSE IS NOTED.HOWEVER, PLEASE SEE FBC1210.2
 REGARDING WALL FINISH TO 4'.PLEASE NOTE THAT AS THIS
 IS A NEW COMMENT, IF THIS WAS THE ONLY COMMENT, THIS
 WOULD HAVE BEEN A PROVISO ITEM AFTER AGREEMENT WITH
 ARCHITECT.HOWEVER, AS THERE ARE OTHER COMMENTS,
 PLEASE REVISE PLAN TO BE COMPLIANT.
  
 NEW COMMENT:
  
 6.SEE ELECTRIC COMMENTS REGARDING ENERGY CALCS.
 PLEASE USE THE CORRECT VERSION.ALSO PLEASE CLARIFY
 WHY THE SQUARE FOOT AREA ON THE PLAN (2910) DOES NOT
 MATCH THE SQARE FOOT AREA ON THE ENERGY CALC (2653).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-11 Cont ID  
Sent By kconrad Date 2007-09-11 Time 19:33 Rev Time 0.00
Received By kconrad Date 2007-09-11 Time 18:00 Sent To I
Notes
2007-09-11 19:33:50PROJECT: 1970 SOUTH DIXIE HIGHWAY/UNIT C-2/REVISIONS
  
 REVIEW: 2004 FLORIDA EXISTING BUILDING CODE W/ 2006
 REVS
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE
 FOLLOWING:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2) PLEASE PROVIDE PROOF OF ORIGINAL DESIGNER
 NOTIFICATION AS PER THE FOLLOWING :
  
 61G15-27.001 PROCEDURES FOR A SUCCESSOR PROFESSIONAL
 ENGINEER ADOPTING AS HIS OWN THE WORK OF ANOTHER
 ENGINEER.
 (1) A SUCCESSOR PROFESSIONAL ENGINEER SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 PROFESSIONAL ENGINEER'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. IN OTHER WORDS, CALCULATIONS,
 SITE VISITS, RESEARCH AND THE LIKE MUST BE DOCUMENTED
 AND PRODUCEABLE UPON DEMAND. FURTHER, THE SUCCESSOR
 PROFESSIONAL ENGINEER MUST TAKE ALL PROFESSIONAL AND
 LEGAL RESPONSIBILITY FOR THE DOCUMENTS WHICH HE SEALED
 AND SIGNED AND CAN IN NO WAY EXEMPT HIMSELF FROM SUCH
 FULL RESPONSIBILITY. PLANS NEED NOT BE REDRAWN BY THE
 SUCCESSOR PROFESSIONAL ENGINEER; HOWEVER, JUSTIFICATION
 FOR SUCH ACTION MUST BE AVAILABLE THROUGH WELL KEPT AND
 COMPLETE DOCUMENTATION ON THE PART OF THE SUCCESSOR
 PROFESSIONAL ENGINEER AS TO HIS HAVING RETHOUGHT AND
 REWORKED THE ENTIRE DESIGN PROCESS. A SUCCESSOR
 PROFESSIONAL ENGINEER MUST USE HIS OWN TITLE BLOCK,
 SEAL AND SIGNATURE AND MUST REMOVE THE TITLE BLOCK,
 SEAL AND SIGNATURE OF THE ORIGINAL PROFESSIONAL
 ENGINEER BEFORE REUSING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING AND SIGNING WORK A SUCCESSOR
 PROFESSIONAL ENGINEER SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL PROFESSIONAL ENGINEER, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL PROFESSIONAL ENGINEER OF THE
 SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 PROFESSIONAL ENGINEER'S WORK. THE SUCCESSOR
 PROFESSIONAL ENGINEER WILL TAKE FULL RESPONSIBILITY FOR
 THE DRAWING AS THOUGH THEY WERE THE SUCCESSOR
 PROFESSIONAL ENGINEER'S ORIGINAL PRODUCT.
 SPECIFIC AUTHORITY 471.033(2) FS. LAW IMPLEMENTED
 471.033(1)(J), 471.005(6) FS. HISTORY?NEW 8-25-87,
 AMENDED 4-21-88, 8-3-88, FORMERLY 21H-27.001.
  
 3) PLEASE PROVIDE DETAILED UL/GA ASSEMBLY FOR TS COLUMN
 FIRE PROTECTION. REQUIRE
 EXACT DETAIL/FILE NUMBER AS LISTED.
  
 4) PLEASE INDICATE THE EXISTING TESTED ASSEMBLY NUMBER
 USED FOR THE TENANT SEPARATION AT THE EXISTING
 MERCHANTILE SEPARATION.
  
 5) ON THE EXISTING PLAN, SHEET A-1, THE ENTRY DOORS ARE
 NOT DESIGNATED FOR USE AT FLOOR AREAS 1 AND 3; THE
 REVISED SHEET A-1 DOES NOT REFLECT THIS. PLEASE
 CLARIFY.
  
 6) PLEASE PROVIDE FIRE-STOPPING DETAILS FOR ALL
 FLOOR/WALL/CEILING THROUGH PENETRATIONS:
  
 712.3.1.2 THROUGH-PENETRATION FIRESTOP
 SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 7) ALL FINISH BASE TRIM SHALL COMPLY WITH THE
 FOLLOWING:
  
 1210.1 FLOORS.
 IN OTHER THAN DWELLING UNITS, TOILET AND BATHING
 ROOM FLOORS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE THAT EXTENDS UPWARD ONTO THE WALLS AT LEAST 6
 INCHES (152 MM).
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-16 Cont ID  
Sent By alange Date 2006-11-16 Time 08:33 Rev Time 0.00
Received By alange Date 2006-11-16 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By alange Date 2006-10-06 Time 14:00 Rev Time 0.00
Received By alange Date 2006-10-06 Time 14:00 Sent To  
Notes
2006-10-06 00:00:00DENIED
  
 1.SHOW KITCHEN COUNTER AND SINK
 ELEVATION SO THAT THE HEIGHT CAN BE
 VERIFED FOR ACCESSABILITY REQUIREMENTS.
  
 2.SHOW SALES DESK COMPLIANCE WITH FBC
 11-7.2SHOW HEIGHT AND WIDTH OF
 COUNTER.
  
 3.SHOW OCCUPANCY OF 2ND FLOOR SO THAT
 COMPLIANCE CAN BE VARIFIED WITH FBC
 TABLE 302.3.2
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 11:55 Sent To  
Notes
2008-05-30 11:56:11RE-STAMP

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2008-04-14 Cont ID  
Sent By dpalmer Date 2008-04-14 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2008-04-14 Time 15:51 Sent To B
Notes
2008-04-14 15:52:13PLANS GIVEN TO LM>
2008-04-14 15:51:49** TEMPORARY DENIED REVIEW**
  
 1) NOTE: PLEASE KNOW AS THE LOCATION, FINAL
 DETERMINATION OF THE BREAK ROOM, BREAK AREA ETC NEEDS
 TO BE WORKED OUT WITH ALL OTHER TRADES.
  
 2) NOTE: PLEASE KNOW THAT THE LIGHTING FIXTURES WHICH
 INDICATE 40W BULBSAND OTHER FIXTURES MUST BE RATED AT
 THE 40WATTS OR FIXTURE DESIGNATED WATTAGE TO BE USED IN
 LIGHTING CALCULATIONS. PLEASE KNOW AS SHOW IS OK,
 HOWEVER FIXTURES ARE TO BE VERIFIED IN FIELD TO
 COORDINATE WITH PLANS AND CALCULATIONS AS SUBMITTED.
 FIXTURES ARE REQUIRED TO CORRELATE.
 13-415.2.ABC.1.1, .1.2
  
 ** PLEASE ALSO SEE ANY OTHER COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SUBMITTED PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 18:03 Sent To  
Notes
2008-03-08 18:03:35** DENIED REVISION **
  
 1) NOTE: PLEASE SEE ONLY ONE SET OF PLANS SUBMITTED FOR
 REVIEW AND STAMPING.
 WILL NOT ANY FURTHER ELECTRICAL REVISIONS UNTIL
 OCCUPANCY AND SPACE DESIGNATIONS ARE REVIEWED AND
 ACCEPTED BY THE OTHER TRADES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT OTHER TRADE
 REVIEWERS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:32 Sent To  
Notes
2008-02-11 08:32:47ELECTRICAL OK, STAMPED.
 REDLINED SPACE OCCUPANCY IS STATED AND STILL SHOWN AS
 RETAIL, NOT BUSINESS. REVISED AREA DESIGNATION ONLY PER
 BUILDING REVIEW NOTES TO *WORK AREA*
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-12-27 Cont ID  
Sent By dpalmer Date 2007-12-27 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2007-12-27 Time 16:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 07:51 Sent To PC
Notes
2007-12-24 08:19:15** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE WATTAGE IN CALCULATIONS SHALL
 BE BASED ON THE MAXIMUM WATTAGE PER MANUFACTURE LABEL
 ON FIXTURE.
 PLEASE SEE FOR ONE EXAMPLE, THE 100W PENDANTS INDICATE
 40W BULBS, HOWEVER THIS IS ONE EXAMPLE OF THE WHERE BY
 PLACING A LOWER WATTAGE BULB IN FIXTURE DOES NOT ALLOW
 LESS WATTAGE USE. THE SAME IS FOR ALL FIXTURES.
 13-415.2.ABC.1.2(1)
  
 2) NOTE: PLEASE SEE THE SEPARATE SHEETS SHOWING
 LIGHTING CALCULATIONS REQUIRE TITLE BLOCKS PER FAC
 61G1-16.004
  
 3) NOTE: PLEASE SEE THESE WERE BROUGHT BACK IN AS A
 SUBMITTAL WHEN IN FACT THESE ARE REVISIONS. PLEASE SEE
 THE FEE OF $70 IS DUE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-12-10 Cont ID  
Sent By dpalmer Date 2007-12-10 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2007-12-10 Time 08:24 Sent To  
Notes
2007-12-10 08:24:41**** DENIED REVISION ****
  
 1) NOTE: PLEASE SEE THE METHOD BEING SUBMITTED MAY NOT
 BE USED ON AN EXISTING BUILDING WHEN ALL COMPONENTS ARE
 NOT NEW OR NEW BEING INSTALLED. PLEASE KNOW THE
 MECHANICAL REVIEWER WILL LOOK AT OTHER SYSTEMS ALONG
 WITH THE BUILDING REVIEWER.
 IF THE *WHOLE* BUILDING BY DEFINITION IS NOT BEING
 DONE THEN METHOD *A* MAY NOT BE USED.
 PLEASE SEE FBC 13-415.2.B, 13-101.1.3. PLEASE SEE
 13-101.1.6 WHEN ALL ARE KNOWN OR NEW. THIS WAS
 CONFIRMED WITH THE FLORIDA BUILDING COMMISSION ON SEPT
 26, 2007.
 PLEASE ALSO KNOW THE VERSION AS SUBMITTED IS FROM THE
 ADOPTION OF THE 2006 REVISIONS TO THE FLORIDA BUILDING
 CODE WHICH DID NOT GO INTO EFFECT UNTIL DECEMBER 8TH,
 2006. PLEASE KNOW THIS PROJECT WAS APPLIED FOR PERMIT
 BEFORE THIS DATE WHICH PLACES THE VERSION UNDER THE
 2.11.
 PLEASE SEE IN EITHER CASE THE FIXTURE LEGEND ON PLANS
 IS NOT COMPLETE AT THIS TIME. PLEASE SEE THE INPUT DATA
 REPORT ALSO DOES NOT CORRELATE WITH THE PLANS AS
 SUBMITTED. THE FIXTURE LEGEND MUST BE COMPLETE WITH ALL
 FIXTURE INFORMATION ON PLANS IN ORDER TO REVIEW THE
 INPUT DATA REPORT FOR ACCURATE REVIEW.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 **
 PLEASE ALSO SEE 13-413.1.ABC.2.1 AND .2.2. THIS IS A
 NEW COMMENT AS THIS IS NOW KNOWN TO THIS OFFICE THAT
 NOTES ARE REQUIRED ON PLANS ACCORDINGLY.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-11-04 Cont ID  
Sent By dpalmer Date 2007-11-04 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2007-11-04 Time 09:09 Sent To I
Notes
2007-11-04 09:31:372007-11-4 09:31:37
  
 ** DENIED 2ND REVIEW OF REVISIONS**
  
 ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS
 REVIEW ALONG WITH SOME NEW COMMENTS DUE TO CHANGES ON
 PLANS/DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE ENERGY CALCULATIONS AS SUBMITTED
 ARE FROM THE 2001 CODE. THESE MAY NOT BE USED AS THE
 PERMIT APPLICATION WAS MADE AFTER OCT 1ST, 2005. PLEASE
 KNOW AS PERMIT APPLICATION DATE WAS ALSO BEFORE THE
 MOST RECENT CODE CHANGE, THE VERSION IS 2004, 2.11. THE
 METHOD IS BASED ON ACTUAL SCOPE OF WORK. AS STATED
 PREVIOUSLY PLEASE SEE 13-415.2 AS PERFORMANCE
 CALCULATIONS FOR TRACK LIGHTING USE REALLY NEEDS TO BE
 LOOKED AT. PLEASE SEE THE METHOD AND PRESCRIPTIVE
 REQUIREMENTS.
 13-415.1.B, 13-415.2.ABC.1.2 ETC.
 THE NEWER VERSION CONTAINS SEVERAL CHANGES.
  
 2) NOTE: PLEASE SEE 210.12 FOR TRACK LIGHTING
 CALCULATIONS REQUIRED FOR NEC MINIMUM CODE COMPLIANCE.
  
 3) NOTE: PLEASE SEE THE NEW GFI RECEPTACLES WERE ADDED
 PRE PREVIOUS NOTE, HOWEVER MISSING CIRCUITING.
 FBC 106.1.2 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS AS
 MENTIONED AS NO LOW VOLTAGE PERMITS TO DATE HAVE BEEN
 APPLIED FOR THE SCOPE OF WORK AS SHOWN ON PLANS.
  
 5) NOTE: PLEASE SEE THE LETTER AS SUBMITTED FOR CHANGE
 IN ARCHITECT IS NOT ACCEPTABLE. THIS IS THE SAME LETTER
 AS PREVIOUSLY SUBMITTED.
 PLEASE SEE THE GUIDELINES AS SET-FORTH IN THE FAC
 61G1.
 PLEASE KNOW THE LETTER NEEDS TO ORIGINAL SIGNED, DATED
 AND SEALED.
 THE LETTER IS ALSO NOT NOTARIZED CORRECTLY PER FS
 117.05.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-11-04 09:10:302007-11-04 09:10:30
  
 IN ELECTRIC FOR REVIEW, WILL BE ROUTED BACK TO INCOMING
 ONCE REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 17:33 Sent To  
Notes
2007-08-01 18:54:16** UNSAT **
  
  
 1) NOTE: PLEASE REVISE AND UPDATE ENERGY CALCULATIONS
 TO COORDINATE WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROL NEED TO CORRELATE WITH
 PLANS. THIS CAN NOT BE *MANUAL ON/OFF* WHEN AUTOMATED
 MEANS IS BEING SHOWN ON PLANS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOAD IN
 ENERGY CALCULATIONS.
 13-415.1.A, 13-415.2
 PLEASE SPECIFY THE MAXIMUM TIMES ON DEVICES FOR OVER
 RIDES.
  
 2) NOTE: PLEASE SEE THE PLANS ARE MISSING GFI
 RECEPTACLES FOR OUTSIDE CONDENSING UNITS. 210.63,
 210.8B
  
 3) NOTE: PLEASE SEE CIRCUITS IN PANEL NEED TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. PLEASE
 SEE 408.4. PLEASE ALSO SEE THE FOLLOWING WHICH IS
 EXTRACTED FROM THE CODE COMMENTARY.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE AHU IN PANEL ?C? WHICH CONTAINS #8
 ON A 60AMP BREAKER. THE CONDUCTORS ARE NOT LARGE
 ENOUGH. 240.4,310.16.
  
 5) NOTE: PLEASE SEE THE RISER AS THIS IN SHOWING A
 2200AMP DESIGNATION FOR METERS. THIS MUST BE A
 MISPRINT.
 FBC 106.1.2
  
 6) NOTE: PLEASE KNOW THAT NO LOW VOLTAGE PERMIT HAS
 BEEN APPLIED FOR TO DATE FOR THE LOW VOLTAGE SCOPE OF
 WORK AS SHOWN ON PLANS.
 PLEASE KNOW THIS IS REQUIRED TO BE SEPARATE PERMIT,
 SEPARATE FEE.
  
 7) NOTE: PLEASE BE SURE THE LETTER SUBMITTED FOR CHANGE
 IN DESIGN PROFESSIONAL OF RECORD IS NOTARIZED. PLEASE
 SEE THE FS 117.05 GIVES THE SPECIFICS ON CORRECT NOTARY
 INFORMATION REQUIRED ON PLANS.
 PLEASE CLARIFY IF THE DESIGNER OF RECORD WHO SIGNED,
 DATED AND SEALED ENERGY CALCULATIONS IS STILL THE
 DESIGNER OF RECORD.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-12 Cont ID  
Sent By dpalmer Date 2007-07-12 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2007-07-12 Time 16:59 Sent To P
Notes
2007-07-12 17:00:05**** UNSAT****
  
  
  
 1) NOTE: PLEASE SUBMIT REVISIONS ON REVISED PLANS.
 PLEASE SEE THE LETTER IN LIEU OF REVISED PLANS IS NOT
 PERMITTED TO THE EXTENT AS SHOWN.
 PLEASE ALSO THAT ALL REVISIONS SHALL BE DONE BY THE
 DESIGNER OF RECORD. FS 481/471.
 FBC 106.1.2, 106.3.5.4, 106.3
 NEC
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 12:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 19:12 Sent To  
Notes
2006-10-12 19:54:52*** UNSAT ***
  
 1) NOTE:PLEASE CORRELATE VOLTAGE FOR A/C SYSTEMS,.
 PLEASE SEE MECH PLANS INDICATE 208V AND ELECTRICAL
 PLANS INDICATE 240 V.
  
 2) NOTE: PLEASE SEECONDUCTOR SIZES FOR AHU #2, PLEASE
 SEE , 424.3B, 310.16, 240.4. ETC
 PLEASE KNOW, DEPENDING ON VOLTAGE OF SERVICE THE OCP
 DEVICES AS SHOWN MAY INDEED CHANGE.
  
 3) NOTE: PLEASE SHOW CALCULATIONS FOR TRACK LIGHTING
 PER 220.12B
  
 4) NOTE: PLEASE SEE SERVICE SHOWS 4-METERS , HOWEVER
 THIS IS BEING SHOWN AS ONE NEW TENANT BUILD OUT. PLEASE
 KNOW, IF THIS IS GOING TO BE FOUR SEPARATE TENANT
 SPACES, THEN PLEASE ADJUST.
 PLEASE SEE ONLY ONE TENANT SPACE IS BEING SHOWN W/OUT
 ANY FIRE/TENANT SEPARATION WALLS BEING SHOWN??
 PLEASE ALSO SEE A FORTH BEING SHOWN WITHOUT GOING TO
 ANYTHING?
 PLEASE KNOW THE SERVICE RISER AT THIS TIME IS UNCLEAR.
  
 230.2,
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE
 INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
 220.3,220.10,220.13,220.11 ETC.
  
 6) NOTE: PLEASE CLARIFY SIZE OF EXISTING MCB AND SEC'S
 FOR SERVICE.
 230.70, 240.4, 310.16
  
 7) NOTE; PLEASE SEE THE FOLLOWING CODES AT A MINIMUM
 SHALL BE STATED ON PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101
  
 8) NOTE: PLEASE SEE THE OVER RIDE DEVICES REQUIRED
 LOCATED AT THE POINT OF ENTRANCE INTO ANY ONE SPACE
 SHALL BE LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING
 CONTROLLED.
 PLEASE INDICATE THE MAX TIME ALLOWED ON OVER -RIDES,
 DEPENDING ON TYPE OF OR DEVICE BEING USED.
 IF IT THE INTENT TO COMPLY W/ FBC CHAPTER 13, PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 30MINS MAX OCCUPANT TYPE/ 4HRS MAX ON TIMER TYPE
  
  
 ** PLEASE KNOW, AS THE A/C UNITS ARE BEIGN SHOWN AS 208
 AND SERVICE AT 240V, EITHER THE "M" SHEETS WILL BE
 REVISEDFOR THIS OR ELECTRICAL PLANS WILL BE. IF
 SERVICE IS INDEED 240V, PLEASE VOID AND REPLACE "M"
 SHEETS WITH NEW REVISED SHEETS INDICATING THE CORRECTED
 VOLTAGES.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-05-30 Cont ID  
Sent By mwennerg Date 2008-05-30 Time 14:43 Rev Time 0.00
Received By mwennerg Date 2008-05-30 Time 14:43 Sent To  
Notes
2008-05-30 14:44:00RE-STAMP

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2008-06-02 Cont ID  
Sent By lmartine Date 2008-04-03 Time 10:58 Rev Time 0.00
Received By lmartine Date 2008-04-03 Time 16:03 Sent To  
Notes
2008-04-03 16:11:56*****INCOMPLETE******
  
  
 ONLY ONE PLAN SET SUBMITTED FOR REVIEW;THE APPROPIATE
 REVISED PLAN SHEET(S) NEEDED TO BE FIRE-STAMPED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 14:36 Sent To  
Notes
2008-02-27 14:37:52REVISIONS DON'T APPEAR TO IMPACT LIFE SAFETY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2007-11-21 Cont ID  
Sent By mwennerg Date 2007-11-21 Time 11:53 Rev Time 0.00
Received By mwennerg Date 2007-11-21 Time 11:53 Sent To  
Notes
2007-11-21 11:53:46PLANS WILL BE STAMPED UPON CORRECTIONS FOR OTHER REVIEW
 COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2007-09-26 Cont ID  
Sent By mwennerg Date 2007-09-26 Time 14:44 Rev Time 0.00
Received By mwennerg Date 2007-09-26 Time 14:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-18 Cont ID  
Sent By mwennerg Date 2006-10-18 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2006-10-18 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-06-02 Cont ID  
Sent By lmartine Date 2008-06-02 Time 10:59 Rev Time 0.00
Received By lmartine Date 2008-05-29 Time 11:46 Sent To  
Notes
2008-05-29 11:47:23GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 08:42 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 08:42 Sent To P
Notes
2008-04-08 08:43:03TO "KSTEVENS" DESK/REV--SEE FRONT SCREEN NOTES

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 08:52 Sent To  
Notes
2008-03-04 08:55:24TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 15:54 Sent To  
Notes
2008-02-07 15:56:29TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 14:49 Sent To P
Notes
2008-01-15 14:51:04TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:01 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:01 Sent To E
Notes
2007-12-26 15:01:37TO DEWEY PALMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-22 Cont ID  
Sent By rregueir Date 2007-12-22 Time 09:12 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 09:12 Sent To  
Notes
2007-12-22 09:13:39SENT TO LM DESK TO CHECK IF FIRE STOP IS NEEDED AND TO
 BE PROCESSED.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 11:09 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 11:09 Sent To E
Notes
2007-12-19 11:09:58TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 16:52 Sent To  
Notes
2007-12-04 16:54:33TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 14:14 Sent To  
Notes
2007-11-05 09:30:36TO "COMM' BD#1
2007-10-15 14:14:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 11:01 Sent To  
Notes
2007-08-01 13:36:37TO "COMM" BD#16
2007-07-20 11:03:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 11:58 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 11:58 Sent To E
Notes
2007-07-12 11:59:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-06 Cont ID  
Sent By adarroug Date 2006-11-06 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-11-06 Time 11:22 Sent To  
Notes
2006-11-12 14:13:54TO "BOB"#13
2006-11-06 11:23:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-24 Cont ID  
Sent By jleech Date 2006-10-24 Time 09:31 Rev Time 0.00
Received By jleech Date 2006-10-05 Time 11:41 Sent To  
Notes
2006-10-05 00:00:00TO "BOB"#17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-30 Cont ID  
Sent By tgordon Date 2008-05-30 Time 16:44 Rev Time 0.30
Received By tgordon Date 2008-05-30 Time 16:44 Sent To  
Notes
2008-05-30 16:45:49RE-STAMP,SENT TO LUIS M.DESK.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-22 Cont ID  
Sent By rregueir Date 2007-12-22 Time 08:38 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 08:36 Sent To  
Notes
2007-12-22 09:01:11MECHANICAL PLANS NOT BEING REVISED AT THIS TIME. NEW
 METHOD A ENERGY CALCULATIONS HAVE BEEN SUBMITTED. AS AN
 EXISTING BUILDING WHERE THE SCOPE OF WORK IS NOT THE
 ENTIRE BUILDING AND DOES NOT MEET THE DEFINITION OF A
 RENOVATION, METHOD A IS NOT ACCEPTABLE FOR
 DEMONSTRATING COMPLIANCE WITH FBC CHAPTER 13. SEE FBC
 13-400.0.C.4. FOR MECHANICAL THE ONLY REQUIREMENT IS
 MINIMUM PRESCRIPTIVE EFFICIENCIES IN ACCORDANCE WITH
 THIS SECTION AND FBC 13-101.6. THAT HAS ALREADY BEEN
 DEMONSTRATED ON PLANS AND PLANS ARE COMPLIANT.
 THEREFORE THE METHOD A CALCULATIONS PROVIDED WITH THIS
 REVISION HAVE NOT BEEN REVIEWED OR CONSIDERED AS PART
 OF THIS PERMIT FOR MECHANICAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-11 Cont ID  
Sent By tgordon Date 2006-10-11 Time 08:38 Rev Time 0.30
Received By tgordon Date 2006-10-11 Time 08:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-05-30 Cont ID  
Sent By kstevens Date 2008-05-30 Time 10:54 Rev Time 0.00
Received By kstevens Date 2008-05-30 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 08:05 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 08:05 Sent To B
Notes
2008-04-12 08:16:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS A-2, 2 0F 3 & A-3, 3 OF 3 STILL SHOW THE BREAK
 ROOM SINK AND SHT A-3 STILL SHOWS THE BREAK ROOM SINK
 DETAILS. PLEASE REVISE ALL SHEETS WITH THE BREAK ROOM
 SINK SHOWN. DELETE THE SINK REFERENCES TO REFLECT
 REVISION. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT DURING OUR CONVERSATION WITH
 THE REPRESTATIVE OF ARCHITECT G. RAYMOND BERRY, IT WAS
 INDICATED THAT IF THE WORK OF THE ENGINEER WAS TO BE
 TAKEN OVER BY THE NEW ARCHITECT, THEN ALL WORK BY THE
 ENGINEER SHALL BE RESUBMITTED. THIS WILL INCLUDE THE
 MECHANICAL SHEETS AND THE FIRE SPRINKLER SHEETS.
  
 3. SHT P1 PLUMBING RISER BREAK AREA DOES NOT MEET CODE
 REQUIREMENTS. AS SHOWN THERE IS NO TRAP FOR THE ICE
 MAKER, AND THE ICE MAKER SHALL BE INDIRECTLY CONNECTED
 TO THE SANITARYSYSTEM NOT DIRECT CONNECTION AS SHOWN.
 SECTIONS 802.1.1 & 1002.1. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO AIR GAP IS SHOWN ON THE
 RISER DIAGRAM. THE PIPING FROM THE ICE MAKER IS
 DIRECTLY CONNECTED TO THE STANDPIPE.
  
 4. SHT P1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR
 IS REQIRED AT THE ICE MACHINE PER SECTION 604.9. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS
 SHOWN ON THE SANITARY RISER DIAGRAM, NOT ON THE WATER
 LINE TO THE ICE MAKER AS REQUIRED.
  
 5. ALL SHEETS. THE ADDRESS FOR THE ARCHITECT DOES NOT
 RELFECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THEY CORRELATE. FAC
 61G1-16.004(1) & FS 481.2055.
 ****RESPONSE NOTED, BUT THE ADDRESS ON THE TITLE BLOCKS
 STILL DO NOT REFLECT THE STATE OF FLORIDA DBPR WEBSITE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-04-01 Cont ID  
Sent By kstevens Date 2008-04-01 Time 15:58 Rev Time 0.00
Received By kstevens Date 2008-04-01 Time 15:58 Sent To  
Notes
2008-04-01 16:48:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. A MINIMUM 2 COPIES OF ALL SHEETS TO BE REVISED SHALL
 BE SUBMITTED FOR REVIEW PER SECTION 106.1. ONLY ONE SET
 SUBMITTED.
  
 2. SHTS A-2, 2 0F 3 & A-3, 3 OF 3 STILL SHOW THE BREAK
 ROOM SINK AND SHT A-3 STILL SHOWS THE BREAK ROOM SINK
 DETAILS. PLEASE REVISE ALL SHEETS WITH THE BREAK ROOM
 SINK SHOWN. DELETE THE SINK REFERENCES TO REFLECT
 REVISION. SECTION 106.1.3.
  
 3. SHT P1 PLUMBING RISER BREAK AREA DOES NOT MEET CODE
 REQUIREMENTS. AS SHOWN THERE IS NO TRAP FOR THE ICE
 MAKER, AND THE ICE MAKER SHALL BE INDIRECTLY CONNECTED
 TO THE SANITARYSYSTEM NOT DIRECT CONNECTION AS SHOWN.
 SECTIONS 802.1.1 & 1002.1. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
  
 4. SHT P1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR
 IS REQIRED AT THE ICE MACHINE PER SECTION 604.9. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201.
  
 5. ALL SHEETS. THE ADDRESS FOR THE ARCHITECT DOES NOT
 RELFECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THEY CORRELATE. FAC
 61G1-16.004(1) & FS 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-02-13 Cont ID  
Sent By jleech Date 2008-02-13 Time 15:02 Rev Time 0.00
Received By jleech Date 2008-02-13 Time 14:15 Sent To  
Notes
2008-02-13 15:21:17DENIED;
 AREA MARKED ON PLANS AS (WORK AREA) IS NOT A WORK AREA.
 SEE RESONS BELOW;
 1. THERE IS A ICE MACHINE AND A REFRIGATOR SHOWN ON
 PLANS IN THIS AREA.
 2. SHEET A-1 "DESIGN DATA" TABLE LISTS SPACE AS RETAIL.
 NO WORK IS DONE NORMALY IN A RETAIL SPACE.
 3. A COPY OF A LETTER FROM; DUNWORTH CONSTRUCTION INC.
 TO SAMANTHA HILL, BUILDING PLAN REVIEW, CITY OF WPB WAS
 SUBMITED WITH YOUR REVISION. THIS LETTER STATES THAT
 THE" WORK AREA WILL BE USED ON A LIMITED BASIS FOR
 PRIVATE SOCIAL FUNCTIONS" . THE REST OF THE TIME THE
 AREA WILL BE USED AS A BREAK ROOM FOR EMPLOYEES.
 I HAVE RETAINED ONE COPY OF THE PLAN SUBMITED AND THE
 LETTER SENT TO SAMANTHA.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-02-06 Cont ID  
Sent By jleech Date 2008-02-06 Time 07:46 Rev Time 0.00
Received By jleech Date 2008-02-06 Time 07:44 Sent To  
Notes
2008-02-06 07:58:56DENIED;
 1.IF THE BREAK SINK IS TO BE A WORK SINK ALL PAGES
 SHOWING A LOUNGE MUST BE REVISED. A-2, A-3 (LOUNGE SINK
 DETAIL), AC-1,E-1, E-2, P-1, ANDFS-1.
 2. REVISED SHEET A-1 STILL SHOWS A HANDICAP SINK
 DETAIL. SINK WOULD STILL BE REQUIRED TO BE INSTALL PER
 APPROVED PLANS.
 3. PLEASE EXPLAIN ON PLANS WANT SINK IS TO BE USED FOR.
 THERE IS NOTHING SHOWING THE NEED FOR A WORK SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-27 Cont ID  
Sent By jleech Date 2007-11-27 Time 14:29 Rev Time 0.00
Received By jleech Date 2007-11-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-14 Cont ID  
Sent By jleech Date 2007-08-14 Time 08:01 Rev Time 0.00
Received By jleech Date 2007-08-14 Time 07:42 Sent To  
Notes
2007-08-14 08:12:08DENIED;
 1. INFORMATION MISSING FROM REVISED PLAN;
 A) WATER RISER DIAGRAM REQUIRED BY CHAPTER 1
 BUILDING SECTION 106.3.5.1.3.
 B) " PLUMBING FIXTURE DESCRIPTION"
 C) WATER HEATER DETAIL.
 2. ICE MACHINE MUST BE AN INDIRECT WASTE. IF FLOOR
 DRAIN IS NOT INSTALLED AN AIR GAP FITTING MUST BE USED.
 PLEASE ADD NOTE TO PLAN
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-14 Cont ID  
Sent By jleech Date 2006-11-14 Time 14:07 Rev Time 0.00
Received By jleech Date 2006-11-14 Time 14:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By jleech Date 2006-10-24 Time 09:12 Rev Time 0.00
Received By jleech Date 2006-10-24 Time 09:12 Sent To  
Notes
2006-10-24 09:30:58DENIED;
 1. PLEASE SHOW A DETAIL OF LOUNGE SINK WITH ALL
 DIMENSIONS REQUIRED TO MEET FBC-2004 CHAPTER 11
 ACCESSIBITY CODE SECTIONS;
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 DEPTH OF SINK
 11-4.24.5 CLEAR FLOOR SPACE UNDER SINK
 11-4.24.6 EXPOSED PIPES
 11-4.24.7 FAUCETS
 2. SHOW DETAIL OF DRINKING FOUNTAIN, DIMENSIONS
 REQUIRED FOR ADA
 11-4.15.2 SPOUT HEIGHT
 11-4.15.3 SPOUT LOCATION
 11-4.15.4 CONTROLS
 11-4.15.5 CLEARANCES
 3.COULD NOT FIND ICE MAKER CUT SHEET PLEASE PROVIDE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695