Plan Review Details - Permit 06100047
Plan Review Stops For Permit 06100047
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-30 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 15:55 Rev Time 0.33
Received By btrobaug Date 2006-10-30 Time 15:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 07:50 Rev Time 0.50
Received By btrobaug Date 2006-10-12 Time 07:41 Sent To PC
Notes
2006-10-12 07:43:35 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 2 } PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} THE EQUIPMENT GROUNDINGCONDUCTOR MUST COMPLY WITH
 250.66. INDICATE SIZE ON PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-24 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 14:25 Sent To E
Notes
2006-10-24 14:25:33TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 07:43 Rev Time 0.00
Received By btrobaug Date 2006-10-05 Time 13:52 Sent To E
Notes
2006-10-05 00:00:00TO "E" BOX