Plan Review Details - Permit 06100038
Plan Review Stops For Permit 06100038
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-09 Cont ID  
Sent By btrobaug Date 2006-11-09 Time 07:16 Rev Time 0.33
Received By btrobaug Date 2006-11-09 Time 06:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-31 Cont ID  
Sent By btrobaug Date 2006-10-31 Time 08:21 Rev Time 0.50
Received By btrobaug Date 2006-10-31 Time 06:20 Sent To PC
Notes
2006-10-31 08:21:01 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLANS SUBMITTED FOR REVIEW MUST BE OF SUFFICIENT
 CLARITY FOR RECORD RETENTION AND REVIEW, PENCIL
 CLOUDING AND CROSSING OUT ITEMS DOES NOT MEET THE
 STANDARDS FOR CLARITY PER 106.3.1 FBC AS AMENDED. DO
 NOT COPY REVIEWED PLANS FOR REVIEW.
  
 2} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 3} SOME CIRCUIT NUMBERS AREDESIGNATED AT THE DEVICES
 AND SOME ARE NOT, PLEASE CORRELATE. IF THE PANEL
 SCHEDULES ON THE DRAWING ARE NOT TO BE USED, REMOVE
 THEM FROM THE DRAWING.
  
 4} LABEL THE ROOMS ON THE PLAN AS TO USE.
  
 5} THE DELETED RECEPTACLE IN WHAT APPEARS TO BE BEDROOM
 #2, BETWEEN THE CLOSET AND ENTRY , MUST BE INSTALLED
 PER 210.52(A)(2), NEC.
  
 6} THE BATH CIRCUIT REQUIRED TO HAVE A 20 AMP
 RECEPTACLE PER 210.11(C) (3), .INDICATE THE CIRCUIT ON
 THE PANEL SCHEDULE
  
 7} CHECK THE LOAD CALCULATION FOR ACCURACY .ADD THE
 HEATING AND A/C AS REQUIRED BY 220.30 OR 220.31. VERIFY
 THE POOL PUMP, SPRINKLER PUMP AND WATER PUMP.
  
 8} THERE IS A RANGE SHOWN ON THE PANEL SCHEDULE, AND ON
 THE CALCULATION A COOKTOP AND OVEN, PLEASE CORRELATE.
  
 9} SHOW THE SMALL APPLIANCE CIRCUITS LOCATION ON THE
 PANEL SCHEDULE. CURRENTLY THEY ARE LISTED ON THE
 DW/COMPACTER CIRCUITS.
  
 10} THE REFRIGERATOR IS LISTED ON THE GENERAL LIGHTING
 CIRCUIT IN VIOLATION OF 210.52(B)(1)
  
 11} THE PLAN INDICATES THE PANEL WAS RELOCATED. PLEASE
 SHOW PREVIOUS LOCATIION AND ROUTING OF CONDUIT(S) TO
 NEW LOCATION.
  
 12} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2,
 THIS INCLUDES THE ATTACHED PAGES.
  
 IF THERE ARE ANY QUESTIONS CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By btrobaug Date 2006-10-20 Time 12:02 Rev Time 0.33
Received By btrobaug Date 2006-10-20 Time 11:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 08:29 Rev Time 0.33
Received By btrobaug Date 2006-10-12 Time 08:20 Sent To PC
Notes
2006-10-12 08:28:48NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER AND RESUBMIT.
  
 2} PLEASE SUBMIT FLOOR PLANS INDICATING THE SCOPE OF
 WORK, ONLY LOAD CALCULATIONS AND PANEL SCHEDULES WERE
 SUBMITTED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.FBC AS
 AMENDED.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 15:49 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 15:49 Sent To E
Notes
2006-10-30 15:50:07TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 14:16 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 14:16 Sent To E
Notes
2006-10-13 14:17:11TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 08:20 Rev Time 0.00
Received By btrobaug Date 2006-10-04 Time 14:34 Sent To E
Notes
2006-10-04 00:00:00TO "E" BOX