Plan Review Details - Permit 06100031
Plan Review Stops For Permit 06100031
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 17:57 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 17:57 Sent To  
Notes
2006-10-05 00:00:00*****APPROVED*****
  
  
  
 AS PER WEST PALM BEACH FIRE PREVENTION:
  
  
 1.) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL ALARM.
  
 2.) THE SILENCING OF THE FIRE ALARM
 SYSTEM SHALL IN NO WAY DEACTIVATE ANY
 VISUAL DEVICES.
  
 3.) COORDINATE WITH THE GENERAL AND/OR
 SPRINKLER CONTRACTOR THAT THE DOUBLE
 DETECTOR CHECK VALVE BE CHAINED AND
 LOCKEDAT THE END OF FINAL FIRE ALARM
 INSPECTION.
  
 4.) WATERFLOW TO ACTIVATE A GENERAL
 ALARM WITHIN 45 TO 60 SECONDS.
  
 5.) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION. INSTALL
 AND/OR POST UL CERTIFICATE AT THE FIRE
 ALARM CONTROL PANEL AND PROVIDE A COPY
 TO WPBFR BY THE FINAL FIRE ALARM
 INSPECTION.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 17:57 Rev Time 0.00
Received By mawillia Date 2006-10-04 Time 14:00 Sent To  
Notes
2006-10-04 00:00:00TO "F" BOX