Plan Review Details - Permit 06100017
Plan Review Stops For Permit 06100017
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-14 Cont ID  
Sent By rmcdouga Date 2008-05-14 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2008-05-14 Time 08:13 Sent To  
Notes
2008-05-14 09:28:12REVISED ROOFING PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-30 Cont ID  
Sent By rmcdouga Date 2007-08-30 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2007-08-29 Time 19:00 Sent To  
Notes
2007-08-30 10:12:39PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By rmcdouga Date 2007-07-18 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2007-07-18 Time 17:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By rmcdouga Date 2007-03-02 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2007-03-02 Time 07:32 Sent To  
Notes
2007-03-02 10:37:46DENIED BY BUILDING
 PLAN REVIEW
 6255 N. JOG RD.
 SWA TRUCK WASH
 TYPE II-B / FULLY SPRINKLERED
  
 1)ITEMS 1-4 OF FIRST REVIEW WILL APPLY WHEN
 SUBMITTING FOR PERMIT.
  
 2) SIGNED AND SEALED COPIES OF THE GEOTECHNICAL REPORT
 FROM TIERRA ARE REQUIRED.
  
 3) IN REGARDS TO THE RESPONSE TO ITEM # 8 OF THE FIRST
 REVIEW. THE FIRE SPRINKLER INCREASE ALLOWED BY FBC
 506.3 REQUIRES THE BUILDING TO BE EQUIPPED THROUGHOUT
 WITH AN APPROVED SPRINKLERED IN ACCORDANCE WITH FBC
 903.3.1.1. THIS MEANS THAT BOTH OF THE BUILDINGS ARE
 REQUIRED TO BE FULLY SPRINKLERED. THE ALLOWABLE AREA IN
 TABLE 503 IS PER FLOOR. THEREFORE, THE SQUARE FOOT AREA
 OF THE DOES NOT NEED TO BE INCLUDED IN THE CALCULATIONS
 FOR THE FIRST FLOOR. THIS INFORMATION SHOULD BE ON THE
 PLANS.
  
 4) IN REGARDS TO ITEM #9 REQUESTING ENERGY
 CALCULATIONS. SUBMIT A SIGNED AND SEALED LETTER
 SPECIFYING WHICH ONE OF THE EXEMPTIONS IN FBC
 13-101.5.7 APPLIES AND WHY.
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE #12 ON FIRST REVIEW. THE PRODUCT APPROVALS
 SUBMITTED ARE NOT ACCEPTABLE. THE INSTALLATION
 INSTRUCTIONS AND DESIGN PRESSURES ARE REQUIRED. THESE
 ARE TYPICALLY INCLUDED IN THE EVALUATION REPORT OR NOA
 THAT WAS SUBMITTED TO THE STATE.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY A
 FLORIDA REGISTERED ARCHITECT OR ENGINEER. FS 471 AND
 481.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By rmcdouga Date 2006-10-23 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2006-10-23 Time 16:16 Sent To  
Notes
2006-10-23 16:28:41DENIED BY BUILDING
 6255 N. JOG RD.
 SWA TRUCK WASH FACILITY
 TYPE II BCONSTRUCTION/ UNSPRINKLERED
  
 1) WHEN SUBMITTING FOR PERMIT SPECIFY THE VALUE OF THE
 PROJECT ON THE APPLICATION.
  
 2) RADON FEES WILL BE ASSESSED BASED ON THE SQUARE
 FOOTAGE UNDER ROOF.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
  
  
 5)FBC 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 6) PLEASE CORRECT THE TYPO ON SHEET A1. THE TEST
 PROTOCOLS SHOULD READ HVHZ NOT HVH2.
  
 7) THE ALLOWABLE HEIGHT AND AREA SPECIFIED ON SHEET A1
 ARE FOR A TYPE II GROUP S1 OCCUPANCY AND A GROUP B
 OCCUPANCY IS SPECIFIED. PLEASE CORRECT.
  
 8)FBC 704.3 BUILDINGS ON THE SAME LOT.
  
 FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND
 OPENING PROTECTION AND ROOF-COVERING REQUIREMENTS,
 BUILDINGS ON THE SAME LOT SHALL BE ASSUMED TO HAVE AN
 IMAGINARY LINE BETWEEN THEM.
  
 WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT
 AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED
 IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING
 SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING
 PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA
 AS SET FORTH IN SECTIONS 704.5 AND 704.8 . EXCEPTION:
 TWO OR MORE BUILDINGS ON THE SAME LOT SHALL EITHER BE
 REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED
 AS PORTIONS OF ONE BUILDING IF THE AGGREGATE AREA OF
 SUCH BUILDINGS IS WITHIN THE LIMITS SPECIFIED IN
 CHAPTER 5 FOR A SINGLE BUILDING. WHERE THE BUILDINGS
 CONTAIN DIFFERENT OCCUPANCY GROUPS OR ARE OF DIFFERENT
 TYPES OF CONSTRUCTION, THE AREA SHALL BE THAT ALLOWED
 FOR THE MOST RESTRICTIVE OCCUPANCY OR CONSTRUCTION.
 PROVIDE A SITE PLAN INDICATING THE ASSUMED PROPERTY
 LINE BETWEEN THE TWO STRUCTURES. NOTE BOTH THE NEW AND
 EXISTING STRUCTURES ARE REQUIRED TO COMPLY WITH WALL
 CONSTRUCTION RATING AND ALLOWABLE OPENINGS. ALSO SEE
 FBC 702 FOR DEFINITION OF FIRE SEPARATION DISTANCE.
 SHOW COMPLIANCE.
  
 9) SUBMIT ENERGY CALCULATION FORMS AS REQUIRED BY FBC
 13-4.
  
 10) SPECIFY THE ROOF PITCH ON THE PLANS. FBC 106.1.2*
 CITY AMENDMENTS
  
 11) THE DESIGN WIND PRESSURES FOR COMPONENTS AND
 CLADDING LISTED IN THE TABLE ON SHEET S5 APPEAR TO BE
 TOO LOW FOR 140 MPH EXPOSURE B BASED ON FBC TABLE
 1609.6B. SUBMIT SIGNED AND SEALED CALCULATIONS. FBC
 106.1.2 * CITY AMENDMENTS
  
 12) SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS,
 DOORS, OVERHEAD GARAGE DOORS, STORM PANELS, LOUVER
 VENTS, ROOFING MATERIALS, ETC. FOR PRODUCTS SPECIFIED
 BY FLORIDA ADMINISTRATIVE CODE RULE 9B-72.
  
 13) FBC 106.3.3* CITY AMENDMENTS REQUIRES THE PRODUCT
 APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT.
  
 14) FBC 1609.1.4 REQUIRES OPENINGS IN ENCLOSED
 STRUCTURES TO BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS. SHOW COMPLIANCE.
  
 15) FBC 1503.6 REQUIRES CONDENSATE LINES AND ROOF
 DOWNSPOUTS TO DISCHARGE AT LEAST ONE FOOT AWAY FROM THE
 STRUCTURE SIDEWALLS. SHOW COMPLIANCE.
  
 16) FBC 1816 REQUIRES TERMITE PROTECTION. SHOW
 COMPLIANCE.
  
 17) SUBMIT INFORMATION, PRODUCT APPROVAL, CALCULATIONS
 AND SPECIFICATIONS FOR THE OCTAFORM WALL SYSTEM. FBC
 106.1.2* CITY AMENDMENTS.
  
 18) SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR THE
 PRECAST HOLLOW CORE CONCRETE ROOF DECK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 14:53 Sent To  
Notes
2007-02-27 07:53:32*** UNSAT 2ND REVIEW***
  
  
  
 1) NOTE:PLEASE KNOW, PLANS HAVE STILL ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT AT THIS TIME.
 AS PERMIT APPLICATION WAS NOT MADE BEFORE DECEMBER 8TH,
 2006 ALL PLANS, DESIGNS,AND CODES REFLECTED ON PLANS
 WILL BE UNDER THE NEW CODES AS ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THAT THE PLANS ARE SHOWING INCORRECT CODES
 AT THIS TIME.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 PLEASE KNOW THAT THE "LATEST EDITION? MAY NOT BE STATED
 ON PLANS.
 THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES OR REVIEWS.
 IF PLANS CONTAINED ALL THE CORRECT CODES AND WERE CODE
 COMPLIANT, THE REVIEW COULD NOT BE ?PASSED? AS PERMIT
 APPLICATION HAS NOT YET BEEN MADE AND REVIEW OF SCOPE,
 PERMIT APPLICATION AND VALUATION OF PROJECT STILL NEEDS
 TO TAKE PLACE.
  
 2) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL
 SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER
 IF NOT A FPL UNIT.
 220, FBC 106.1.2
 THIS WAS REQUESTED ON THE PREVIOUS REVIEW HOWEVER LOAD
 SUMMARY OR CALCULATIONS FOR THE EXISTING MAIN DIST SWGR
 HAS NOT BEEN PROVIDED.
  
 3) NOTE: PLEASE INDICATE ALL BRANCH CIRCUIT CONDUCTORS
 ON PANEL SCHEDULE. PLEASE SEE 310.16 FOR SIZING.
 240.4, 310.16,
 FBC 106.5.3.1.2
 *SOME CONDUCTOR SIZES ARE SHOWN ON PLANS AND NOTE WAS
 VIEWED FOR OTHER CONDUIT RUNS, HOWEVER NOT ALL AND
 PLEASE PLACE ON PANEL SCHEDULE.
  
 .
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-26 07:03:192007-02-25 07:03:19
 IN PROGRESS
2007-02-25 14:55:452007-02-25 14:55:45
 REVIEW WILL CONTINUE, PLANS WILL FOLLOW INTO "F" STATUS
 ONCE REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By dpalmer Date 2006-10-26 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2006-10-26 Time 09:53 Sent To  
Notes
2006-10-26 17:54:05*** UNSAT ****
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT AT
 THIS TIME. PLANS EVEN IF CODE COMPLIANT CAN NOT BE
 STAMPED OR SIGNED OFF UNTIL APPLICATION FOR PERMIT HAS
 BEEN MADE.
  
 1) NOTE: PLEASEPLACE ALL RELEVANT CODES ON PLANS
 WHICH ARE CURRENT AND UNDER ADOPTION OF THE FBC.
 NFPA-70 2002,ETC.
 PLEASE KNOW THAT THE "LATEST EDITION" HAS NOT YET BEEN
 ADOPTED PER THE STATE OF FLORIDA.
  
 2) NOTE: PLEASE SEE FBC ADMIN SECT 106.1.3 WHICH
 REQUIRES PLANS AT A MIN OF 1/8" SCALE.
  
 3) NOTE: PLEASE SEE 700.12EWHICH REQUIRES THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN
 THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON THE 500 KVA 4160
 TRANSFORMER AS SHOWN. IS THISFPL OR ON SITE DOWN
 STREAM FROM A 4160 SERVICE.
 PLEASE SEE OTHER COMMENTS WHICH MAY REFLECTTHIS
 INFORMATION WHICH IS NOT YET PROVIDED.
 FBC 106.1.2
  
 5) NOTE; PLEASE SEE MISSING NEUTRAL CONDUCTOR FROM THIS
 TRANSFORMER TO THE NEW MDP. PLEASE SEE THIS IS REQUIRED
 WHETHER OR NOT THIS IS A FPL TRANSFORMER.
 PLEASE SHOW AND INDICATE ALL GROUNDING ELECTRODE
 SYSTEMS PER 250.20,250.30,250.66 ETC
 PLEASE SEE 250.6, 250.24B.
 IT IS UNCLEAR AT THIS TIME IF THESE ARE FEEDERS OR
 SEC'S.?
  
 6) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL
 SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER
 IF NOT A FPL UNIT.
 220, FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT ALL INFORMATION ON THE EQUIPMENT
 LISTING ETC FOR INSTALLING A NEW 600A MCB INSIDE THIS
 EXISTING TRANSFORMER.
 PLEASE KNOW ALL DISCONNECTING MEANS SHALL BE READILY
 ACCESSIBLE ETC. AT THIS TIME THIS SCENARIO AS SHOWN
 DOES NOT MEET CODE AND MORE INFORMATION IS NEEDED.
 110.3, 110.27, 90.7, 110.26,, 250.24B, 230.70,ETC
 ETC.
 PLEASE SUBMIT THE MANUFACTURES SPEC /CUT SHEETS ON THIS
 EQUIPMENT. MUST INDICATE A LISTING FROM A NRTL BEFORE
 THIS CAN BE REVIEWED.
  
 8) NOTE: PLEASE INDICATE GROUNDING FOR TR1 250.66,
 250.30, 250.20 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-06-27 Cont ID  
Sent By rchokshi Date 2007-06-27 Time 15:53 Rev Time 0.00
Received By rchokshi Date 2007-06-27 Time 15:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By rchokshi Date 2007-03-02 Time 15:37 Rev Time 0.00
Received By rchokshi Date 2007-03-02 Time 13:40 Sent To  
Notes
2007-03-02 15:37:00PLEASE PROVIDE THE FOLLOWING INFO:
 1. AS YOU MENTIONED IN YOUR "SUMMARY OF RESPONSES TO
 PLAN REVIEW NOTES" (NO DATE), ITEM # 4 , WE NEED TO
 REVIEW PPSC FROM DEP WITH SFWMD, PLEASE PROVIDE A COPY
 OF PPSC.
 2. YOUR RESPONSE ITEM 5, PLEASE PROVIDE THE STORM WATER
 DESIGN FOR THE SITE......,,WE NEED A COPY OF THE STORM
 WATER CALCULATIONS.
 3. YOUR RESPONSE ITEM # 6,PLEASE PROVIDE TOTAL
 PERVIOUS AREA, TOTAL IMPERVIOUS AREA ALONG WITH TOTAL
 SITE AREA
 4. YOUR RESPONSE ITEM # 9, WE HAVE NOT HEARD FROM
 MANNY, 45TH ST. UTILITY PLAN APPROVED OR NOT??
  
 PLEASE RESPONSE EACH ITEM TO EXPEDITE YOUR PERMIT. ALSO
 PLEASE SEND A COPY OF YOUR RESPONSE OF THESE ITEMS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-16 Cont ID  
Sent By rchokshi Date 2006-11-16 Time 17:12 Rev Time 0.00
Received By rchokshi Date 2006-11-16 Time 16:53 Sent To  
Notes
2006-11-16 17:12:06PLEASE PROVIDE FOLLOWING INFO:
 1. CITY OF WPB STANDARD NOTES ON DRAWING FOR PARKING,
 HANDICAP PARKING, PAINTPER CITY CODES ETC.,, MUST
 MEET PER ADA,,SIDEWALK WIDTH, ITS SLOPE, DRIVEWAY
 ETC.,
 2. DUMPSTER DETAILS PER CITY OF WPB, &LOCATION ON
 DWG, MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, AND
 GEOTECHNICAL REPORT
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS,IMPERVIOUS AREA CAL.,
  
 6. WHAT IS THE SITE AREA, ?
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CAN DETERMINE THE BEST PIPE TO
 CONNECT WITH THE STORM WATER FROM ALL OTHER STORM WATER
 PIPES. PLEASE SHOW DETAIL OF THE CONTROL STRUCTURES
 WITH ELEVATIONS.DID YOU USE EXFILTRATION TRENCH?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS LIKE SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS AROUND YOUR SITE
 FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-21 Cont ID  
Sent By mwennerg Date 2008-05-21 Time 13:51 Rev Time 0.00
Received By mwennerg Date 2008-05-21 Time 13:51 Sent To  
Notes
2008-05-21 14:00:011) ALL PIPING TO BE HYDROSTATIC TESTED FOR (2) HOURS.
  
 2) FIRE HYDRANT REINSTALLATION TO BE INSPECTED, TESTED
 AND APPROVED BY THIS OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-17 Cont ID  
Sent By mawillia Date 2007-07-17 Time 15:34 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 14:45 Sent To  
Notes
2007-07-17 14:50:45*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEWS HAVE BEEN
 ADDRESSED;PLAN SHEETS A-2, E-3,FP-1AND FP-2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 10:04 Rev Time 0.00
Received By mawillia Date 2007-03-20 Time 09:35 Sent To  
Notes
2007-03-20 10:04:16*****UNSAT*****
  
  
 PLEASE RE-ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW:
  
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO CODE SUMMARY ON SHEET NO. A-1
  
 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION
 SYSTEM , THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED TO SERVICE.
 PLEASE ADD THIS STATEMENT TO SHEET NO. FP-1.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By mawillia Date 2006-12-13 Time 15:05 Rev Time 0.00
Received By mawillia Date 2006-12-13 Time 15:05 Sent To  
Notes
2006-12-13 16:03:35*****DENIED*****
  
  
  
  
 1.THE ADDRESS OF THE TRUCK WASH FACILITY SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN.
  
 2.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE ELEVATION (SHEET A-2).AS PER WEST PALM
 BEACH CODE, THE NUMERICAL ADDRESS SHALL BE NO LESS THAN
 6" IN HEIGHT AND 1"IN WIDTH.
  
 3.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 6.ACCESS ROADS SHALL BE CAPABLE OF SUPPORTING AND
 MAINTAINING 32 TONS OF FIRE EQUIPMENT.
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER SYSTEM.NFPA 13 (2002 EDITION) SHALL BE
 REFERENCED.
  
 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION
 SYSTEM (IF NEEDED TO RELOCATE THE FIRE DEPT. CONN. AS
 STATED ON SHEET FP-1.0) , THE FIRE DEPARTMENT SHALL BE
 NOTIFIED WHEN THE SYSTEM IS SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 10:07 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 10:07 Sent To FIRE
Notes
2008-05-13 10:07:23TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 09:40 Sent To B
Notes
2008-05-13 09:41:01TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-05-21 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 13:42 Sent To  
Notes
2007-06-12 11:36:07TO "COMM" BD#45--PLANS ROUTED TO ROBBIE FOR
 PROCESSING--8/29/07
2007-05-21 13:43:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-02 Cont ID  
Sent By rmcdouga Date 2007-03-02 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2007-02-23 Time 14:44 Sent To  
Notes
2007-02-23 14:48:22TO "COMM" BD#62/PLANS FOUND TODAY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-13 Cont ID  
Sent By mawillia Date 2006-12-13 Time 15:05 Rev Time 0.00
Received By mawillia Date 2006-10-04 Time 14:37 Sent To  
Notes
2006-10-17 15:13:31TO "COMM" BD#25
2006-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-19 Cont ID  
Sent By rregueir Date 2007-06-19 Time 19:27 Rev Time 0.00
Received By rregueir Date 2007-06-19 Time 19:24 Sent To  
Notes
2007-06-19 19:27:01************PROVISO**************
  
 REGARDING COMMENT #4 AND RESPONSE: IT IS THE
 DETERMINATION OF THE BUILDING OFFICIAL THAT AN AHU WITH
 A NOMINAL CAPACITY OF 2000 CFM HAS A DESIGN CAPACITY IN
 EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS
 REQUIRED UNDER FBC, M 606.2.1. A FAN SHUT-DOWN TEST
 WITH AN AUDIO/VISUAL SIGNAL WILL BE REQUIRED AT FINAL
 INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-08 Cont ID  
Sent By rregueir Date 2007-03-08 Time 13:07 Rev Time 0.00
Received By rregueir Date 2007-03-08 Time 12:53 Sent To  
Notes
2007-03-08 13:12:02THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 COMMENT #1: FIRE DAMPER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS WILL BE REQUIRED ON SITE FOR INSPECION.
 FBC,M 307.2
  
 COMMENT #2: OK
  
 COMMENT #3: OK
  
 COMMENT #4: THIS ITEM DOES NOT APPEAR TO HAVE BEEN
 ADDDRESSED ON PLAN.
  
 COMMENT #5: PLEASE INDICATE ON NOTE #6 HOW MANY STRAPS
 ARE REQUIRED PER SIDE.
  
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By rregueir Date 2006-10-30 Time 18:16 Rev Time 0.00
Received By rregueir Date 2006-10-30 Time 17:08 Sent To  
Notes
2006-10-30 18:23:25------------DENIED--------------
 1. PLEASE PROVIDE DETAIL FOR THE WALL SLEEVE/ LOUVER/
 FIRE DAMPER ATTACHMENTS SHOWING COMPLIANCE WITH FIRE
 DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 FBC,M 607.2
  
 2. AUXILIARY DRAIN PROTECTION IS REQUIRED ON AHU PER
 FBC,M 307.2.3
  
 3. CONDENSATE DISPOSAL TO BE IN COMPLIANCE WITH FBC,M
 307.2.1 AND FBC 1503.6
  
 4. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED ON AHU
 PER FBC,M SECTION 606
  
 5. PLEASE PROVIDE DETAIL FOR C.U. ATTACHEMNT TO SLAB
 SHOWING COMPLIANCE WITH FBC,M 301.13
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-20 Cont ID  
Sent By kstevens Date 2007-06-20 Time 11:08 Rev Time 0.00
Received By kstevens Date 2007-06-20 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By kstevens Date 2007-03-07 Time 15:48 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 15:48 Sent To  
Notes
2007-03-07 16:11:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WEST PALM BEACH MUNICIPAL CODE
  
 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE
 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT
 LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH
 THEY ARE INSTALLED.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON
 THE WATER SUPPLY TO THE BUILDING. SHEET C-3 NOW
 INDICATES THE WATER SUPPLY CONNECTING TO TWO SOURCES. A
 2" LINE AND A 1-1/2" LINE. PLEASE CLARIFY. SECTION
 608.13.2. ALSO SEE SHT P-3 AT THE INCOMING MINIMUM 2"
 WATER SUPPLY INDICATES A BACKFLOW REQUIRED.
  
 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE
 REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL
 COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected]. UTILITY ORD.
 3434.
 ****RESPONSE NOTED, BUT THE REQUIREMENT FOR A SAND/OIL
 INTERCEPTOR SHALL BE DETERMINED BY ENVIRONMENTAL
 COMPLIANCE. ARTICLE III SECTION 90-124(7) OF THE
 MUNICIPAL CODE. LOOKING THROUGH APPENDIX "I", THERE ARE
 14 PAGES OF INFORMATION. IF THERE IS INFORMATION ON A
 SAND/OIL INTERCEPTOR IN THESE PAGES, PLEASE INDICATE
 WHICH PART AND SUBPART PRETAINS TO THIS INFORMATION.
 WILL THIS INFORMATION INDCATE IF THE OVERFLOWS WILL
 HAVE THE OIL INTERCEPTED?
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By kstevens Date 2006-12-06 Time 14:16 Rev Time 0.00
Received By kstevens Date 2006-12-06 Time 14:15 Sent To  
Notes
2006-12-06 14:22:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WEST PALM BEACH MUNICIPAL CODE
  
 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE
 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT
 LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH
 THEY ARE INSTALLED.
  
 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE
 REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL
 COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected]. UTILITY ORD.
 3434.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-28 Cont ID  
Sent By eschneid Date 2007-08-28 Time 16:30 Rev Time 0.00
Received By eschneid Date 2007-07-19 Time 09:06 Sent To  
Notes
2007-08-28 16:32:21PASSED BASED ON DEP FINAL ORDER MODIFYING CONDITIONS OF
 CERTIFICATION DATED AUGUST 24, 2007.
2007-08-15 09:12:31SPOKE WITH ENGINEER - HE IS WAITING ON DEP TO ISSUE A
 MODIFIED POWER PLANT CERTIFICATION.EXPECTS IT BY
 AUGUST 24.
2007-07-19 09:08:44WAITING ON A DETERMINATION BY THE OFFICE OF THE CITY
 ATTORNEY TO COMPLETE THE ZONING REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-01 Cont ID  
Sent By eschneid Date 2007-03-01 Time 08:47 Rev Time 0.00
Received By eschneid Date 2007-03-01 Time 08:47 Sent To  
Notes
2007-03-01 10:06:17FAILED
  
 1) IN THE FEBRUARY 1, 2007 PLAN REVIEW RESPONSE, IT IS
 STATED THAT THE SITE FALLS UNDER THE DEP POWER PLANT
 SITING CERTIFICATION.NO EVIDENCE HAS BEEN PROVIDED TO
 THE PLANNING AND ZONING DEPARTMENT THAT THE ENTIRE 920
 ACRE SOLID WASTE AUTHORITY SITE FALLS UNDER THE
 PROVISIONS OF CHAPTER 403, PART II ELECTRIC POWER PLANT
 AND TRANSMISSION LINE SITING.NOR HAS EVIDENCE BEEN
 PROVIDED THAT SPECIFICALLY SHOWS THE TRUCK WASH
 FACILITY INCLUDED IN A SITE PLAN APPROVED AS PART OF A
 POWER PLANT SITING CERTIFICATION OR CONDITIONS OF
 CERTIFICATION.
  
 2) THE FOLLOWING COMMENTS FROM THE DECEMBER 5, 2006
 REVIEW STILL APPLY:
  
 A) THE CONSTRUCTION OF THE NEW BUILDING REQUIRES THE
 APPROVAL OF A REVISION TO THE SITE PLANS APPROVED BY
 THE CLASS A SPECIAL USE PERMIT.THE CITY COMMISSION
 MAY GRANT THE APPROVAL AFTER A PUBLIC HEARING.
  
 2) THE PLANS ARE INSUFFICIENT TO REVIEW FOR COMPLIANCE
 WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS.NO
 DIMENSIONED SITE PLAN OR LANDSCAPE PLANS WERE
 SUBMITTED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By eschneid Date 2006-12-05 Time 15:54 Rev Time 0.00
Received By eschneid Date 2006-12-05 Time 13:47 Sent To  
Notes
2006-12-05 15:51:00FAILED
  
 1) THE CONSTRUCTION OF THE NEW BUILDING REQUIRES THE
 APPROVAL OF A REVISION TO THE SITE PLANS APPROVED BY
 THE CLASS A SPECIAL USE PERMIT.THE CITY COMMISSION
 MAY GRANT THE APPROVAL AFTER A PUBLIC HEARING.
  
 2) THE PLANS ARE INSUFFICIENT TO REVIEW FOR COMPLIANCE
 WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS.NO
 SITE PLAN OR LANDSCAPE PLANS WERE SUBMITTED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved