| Plan Review Stops For Permit 06100017 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-05-14 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-05-14 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2008-05-14 09:28:12 | REVISED ROOFING PRODUCT APPROVALS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-08-30 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-08-29 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2007-08-30 10:12:39 | PROCESS PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-07-18 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-07-18 |
Time |
17:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-03-02 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-03-02 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2007-03-02 10:37:46 | DENIED BY BUILDING | | | PLAN REVIEW | | | 6255 N. JOG RD. | | | SWA TRUCK WASH | | | TYPE II-B / FULLY SPRINKLERED | | | | | | 1)ITEMS 1-4 OF FIRST REVIEW WILL APPLY WHEN | | | SUBMITTING FOR PERMIT. | | | | | | 2) SIGNED AND SEALED COPIES OF THE GEOTECHNICAL REPORT | | | FROM TIERRA ARE REQUIRED. | | | | | | 3) IN REGARDS TO THE RESPONSE TO ITEM # 8 OF THE FIRST | | | REVIEW. THE FIRE SPRINKLER INCREASE ALLOWED BY FBC | | | 506.3 REQUIRES THE BUILDING TO BE EQUIPPED THROUGHOUT | | | WITH AN APPROVED SPRINKLERED IN ACCORDANCE WITH FBC | | | 903.3.1.1. THIS MEANS THAT BOTH OF THE BUILDINGS ARE | | | REQUIRED TO BE FULLY SPRINKLERED. THE ALLOWABLE AREA IN | | | TABLE 503 IS PER FLOOR. THEREFORE, THE SQUARE FOOT AREA | | | OF THE DOES NOT NEED TO BE INCLUDED IN THE CALCULATIONS | | | FOR THE FIRST FLOOR. THIS INFORMATION SHOULD BE ON THE | | | PLANS. | | | | | | 4) IN REGARDS TO ITEM #9 REQUESTING ENERGY | | | CALCULATIONS. SUBMIT A SIGNED AND SEALED LETTER | | | SPECIFYING WHICH ONE OF THE EXEMPTIONS IN FBC | | | 13-101.5.7 APPLIES AND WHY. | | | | | | 5) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. SEE #12 ON FIRST REVIEW. THE PRODUCT APPROVALS | | | SUBMITTED ARE NOT ACCEPTABLE. THE INSTALLATION | | | INSTRUCTIONS AND DESIGN PRESSURES ARE REQUIRED. THESE | | | ARE TYPICALLY INCLUDED IN THE EVALUATION REPORT OR NOA | | | THAT WAS SUBMITTED TO THE STATE. | | | | | | 6)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 7) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY A | | | FLORIDA REGISTERED ARCHITECT OR ENGINEER. FS 471 AND | | | 481. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-10-23 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-10-23 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2006-10-23 16:28:41 | DENIED BY BUILDING | | | 6255 N. JOG RD. | | | SWA TRUCK WASH FACILITY | | | TYPE II BCONSTRUCTION/ UNSPRINKLERED | | | | | | 1) WHEN SUBMITTING FOR PERMIT SPECIFY THE VALUE OF THE | | | PROJECT ON THE APPLICATION. | | | | | | 2) RADON FEES WILL BE ASSESSED BASED ON THE SQUARE | | | FOOTAGE UNDER ROOF. | | | | | | 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 4) BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION. | | | | | | | | | 5)FBC 1804.2.2AREA OF QUESTIONABLE | | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. | | | | | | 6) PLEASE CORRECT THE TYPO ON SHEET A1. THE TEST | | | PROTOCOLS SHOULD READ HVHZ NOT HVH2. | | | | | | 7) THE ALLOWABLE HEIGHT AND AREA SPECIFIED ON SHEET A1 | | | ARE FOR A TYPE II GROUP S1 OCCUPANCY AND A GROUP B | | | OCCUPANCY IS SPECIFIED. PLEASE CORRECT. | | | | | | 8)FBC 704.3 BUILDINGS ON THE SAME LOT. | | | | | | FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND | | | OPENING PROTECTION AND ROOF-COVERING REQUIREMENTS, | | | BUILDINGS ON THE SAME LOT SHALL BE ASSUMED TO HAVE AN | | | IMAGINARY LINE BETWEEN THEM. | | | | | | WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT | | | AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED | | | IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING | | | SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING | | | PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA | | | AS SET FORTH IN SECTIONS 704.5 AND 704.8 . EXCEPTION: | | | TWO OR MORE BUILDINGS ON THE SAME LOT SHALL EITHER BE | | | REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED | | | AS PORTIONS OF ONE BUILDING IF THE AGGREGATE AREA OF | | | SUCH BUILDINGS IS WITHIN THE LIMITS SPECIFIED IN | | | CHAPTER 5 FOR A SINGLE BUILDING. WHERE THE BUILDINGS | | | CONTAIN DIFFERENT OCCUPANCY GROUPS OR ARE OF DIFFERENT | | | TYPES OF CONSTRUCTION, THE AREA SHALL BE THAT ALLOWED | | | FOR THE MOST RESTRICTIVE OCCUPANCY OR CONSTRUCTION. | | | PROVIDE A SITE PLAN INDICATING THE ASSUMED PROPERTY | | | LINE BETWEEN THE TWO STRUCTURES. NOTE BOTH THE NEW AND | | | EXISTING STRUCTURES ARE REQUIRED TO COMPLY WITH WALL | | | CONSTRUCTION RATING AND ALLOWABLE OPENINGS. ALSO SEE | | | FBC 702 FOR DEFINITION OF FIRE SEPARATION DISTANCE. | | | SHOW COMPLIANCE. | | | | | | 9) SUBMIT ENERGY CALCULATION FORMS AS REQUIRED BY FBC | | | 13-4. | | | | | | 10) SPECIFY THE ROOF PITCH ON THE PLANS. FBC 106.1.2* | | | CITY AMENDMENTS | | | | | | 11) THE DESIGN WIND PRESSURES FOR COMPONENTS AND | | | CLADDING LISTED IN THE TABLE ON SHEET S5 APPEAR TO BE | | | TOO LOW FOR 140 MPH EXPOSURE B BASED ON FBC TABLE | | | 1609.6B. SUBMIT SIGNED AND SEALED CALCULATIONS. FBC | | | 106.1.2 * CITY AMENDMENTS | | | | | | 12) SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS, | | | DOORS, OVERHEAD GARAGE DOORS, STORM PANELS, LOUVER | | | VENTS, ROOFING MATERIALS, ETC. FOR PRODUCTS SPECIFIED | | | BY FLORIDA ADMINISTRATIVE CODE RULE 9B-72. | | | | | | 13) FBC 106.3.3* CITY AMENDMENTS REQUIRES THE PRODUCT | | | APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD FOR THE PROJECT. | | | | | | 14) FBC 1609.1.4 REQUIRES OPENINGS IN ENCLOSED | | | STRUCTURES TO BE IMPACT RESISTANT OR PROTECTED WITH | | | IMPACT RESISTANT COVERINGS. SHOW COMPLIANCE. | | | | | | 15) FBC 1503.6 REQUIRES CONDENSATE LINES AND ROOF | | | DOWNSPOUTS TO DISCHARGE AT LEAST ONE FOOT AWAY FROM THE | | | STRUCTURE SIDEWALLS. SHOW COMPLIANCE. | | | | | | 16) FBC 1816 REQUIRES TERMITE PROTECTION. SHOW | | | COMPLIANCE. | | | | | | 17) SUBMIT INFORMATION, PRODUCT APPROVAL, CALCULATIONS | | | AND SPECIFICATIONS FOR THE OCTAFORM WALL SYSTEM. FBC | | | 106.1.2* CITY AMENDMENTS. | | | | | | 18) SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR THE | | | PRECAST HOLLOW CORE CONCRETE ROOF DECK. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-19 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-19 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-27 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-25 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2007-02-27 07:53:32 | *** UNSAT 2ND REVIEW*** | | | | | | | | | | | | 1) NOTE:PLEASE KNOW, PLANS HAVE STILL ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED | | | FOR PERMIT AT THIS TIME. | | | AS PERMIT APPLICATION WAS NOT MADE BEFORE DECEMBER 8TH, | | | 2006 ALL PLANS, DESIGNS,AND CODES REFLECTED ON PLANS | | | WILL BE UNDER THE NEW CODES AS ADOPTED BY THE STATE OF | | | FLORIDA. | | | PLEASE SEE THAT THE PLANS ARE SHOWING INCORRECT CODES | | | AT THIS TIME. | | | 2004 FBC W/2006 REVISIONS. | | | 2005 NFPA-70 | | | PLEASE KNOW THAT THE "LATEST EDITION? MAY NOT BE STATED | | | ON PLANS. | | | THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER OR | | | NOT COMMENT IS MADE BY OTHER TRADES OR REVIEWS. | | | IF PLANS CONTAINED ALL THE CORRECT CODES AND WERE CODE | | | COMPLIANT, THE REVIEW COULD NOT BE ?PASSED? AS PERMIT | | | APPLICATION HAS NOT YET BEEN MADE AND REVIEW OF SCOPE, | | | PERMIT APPLICATION AND VALUATION OF PROJECT STILL NEEDS | | | TO TAKE PLACE. | | | | | | 2) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL | | | SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER | | | IF NOT A FPL UNIT. | | | 220, FBC 106.1.2 | | | THIS WAS REQUESTED ON THE PREVIOUS REVIEW HOWEVER LOAD | | | SUMMARY OR CALCULATIONS FOR THE EXISTING MAIN DIST SWGR | | | HAS NOT BEEN PROVIDED. | | | | | | 3) NOTE: PLEASE INDICATE ALL BRANCH CIRCUIT CONDUCTORS | | | ON PANEL SCHEDULE. PLEASE SEE 310.16 FOR SIZING. | | | 240.4, 310.16, | | | FBC 106.5.3.1.2 | | | *SOME CONDUCTOR SIZES ARE SHOWN ON PLANS AND NOTE WAS | | | VIEWED FOR OTHER CONDUIT RUNS, HOWEVER NOT ALL AND | | | PLEASE PLACE ON PANEL SCHEDULE. | | | | | | . | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-02-26 07:03:19 | 2007-02-25 07:03:19 | | | IN PROGRESS | | 2007-02-25 14:55:45 | 2007-02-25 14:55:45 | | | REVIEW WILL CONTINUE, PLANS WILL FOLLOW INTO "F" STATUS | | | ONCE REVIEW IS COMPLETED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-26 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-26 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2006-10-26 17:54:05 | *** UNSAT **** | | | | | | ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR | | | "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT AT | | | THIS TIME. PLANS EVEN IF CODE COMPLIANT CAN NOT BE | | | STAMPED OR SIGNED OFF UNTIL APPLICATION FOR PERMIT HAS | | | BEEN MADE. | | | | | | 1) NOTE: PLEASEPLACE ALL RELEVANT CODES ON PLANS | | | WHICH ARE CURRENT AND UNDER ADOPTION OF THE FBC. | | | NFPA-70 2002,ETC. | | | PLEASE KNOW THAT THE "LATEST EDITION" HAS NOT YET BEEN | | | ADOPTED PER THE STATE OF FLORIDA. | | | | | | 2) NOTE: PLEASE SEE FBC ADMIN SECT 106.1.3 WHICH | | | REQUIRES PLANS AT A MIN OF 1/8" SCALE. | | | | | | 3) NOTE: PLEASE SEE 700.12EWHICH REQUIRES THE BRANCH | | | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME | | | BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN | | | THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. | | | | | | 4) NOTE: PLEASE PROVIDE INFORMATION ON THE 500 KVA 4160 | | | TRANSFORMER AS SHOWN. IS THISFPL OR ON SITE DOWN | | | STREAM FROM A 4160 SERVICE. | | | PLEASE SEE OTHER COMMENTS WHICH MAY REFLECTTHIS | | | INFORMATION WHICH IS NOT YET PROVIDED. | | | FBC 106.1.2 | | | | | | 5) NOTE; PLEASE SEE MISSING NEUTRAL CONDUCTOR FROM THIS | | | TRANSFORMER TO THE NEW MDP. PLEASE SEE THIS IS REQUIRED | | | WHETHER OR NOT THIS IS A FPL TRANSFORMER. | | | PLEASE SHOW AND INDICATE ALL GROUNDING ELECTRODE | | | SYSTEMS PER 250.20,250.30,250.66 ETC | | | PLEASE SEE 250.6, 250.24B. | | | IT IS UNCLEAR AT THIS TIME IF THESE ARE FEEDERS OR | | | SEC'S.? | | | | | | 6) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL | | | SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER | | | IF NOT A FPL UNIT. | | | 220, FBC 106.1.2 | | | | | | 7) NOTE: PLEASE SUBMIT ALL INFORMATION ON THE EQUIPMENT | | | LISTING ETC FOR INSTALLING A NEW 600A MCB INSIDE THIS | | | EXISTING TRANSFORMER. | | | PLEASE KNOW ALL DISCONNECTING MEANS SHALL BE READILY | | | ACCESSIBLE ETC. AT THIS TIME THIS SCENARIO AS SHOWN | | | DOES NOT MEET CODE AND MORE INFORMATION IS NEEDED. | | | 110.3, 110.27, 90.7, 110.26,, 250.24B, 230.70,ETC | | | ETC. | | | PLEASE SUBMIT THE MANUFACTURES SPEC /CUT SHEETS ON THIS | | | EQUIPMENT. MUST INDICATE A LISTING FROM A NRTL BEFORE | | | THIS CAN BE REVIEWED. | | | | | | 8) NOTE: PLEASE INDICATE GROUNDING FOR TR1 250.66, | | | 250.30, 250.20 ETC. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-06-27 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-06-27 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-03-02 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-03-02 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2007-03-02 15:37:00 | PLEASE PROVIDE THE FOLLOWING INFO: | | | 1. AS YOU MENTIONED IN YOUR "SUMMARY OF RESPONSES TO | | | PLAN REVIEW NOTES" (NO DATE), ITEM # 4 , WE NEED TO | | | REVIEW PPSC FROM DEP WITH SFWMD, PLEASE PROVIDE A COPY | | | OF PPSC. | | | 2. YOUR RESPONSE ITEM 5, PLEASE PROVIDE THE STORM WATER | | | DESIGN FOR THE SITE......,,WE NEED A COPY OF THE STORM | | | WATER CALCULATIONS. | | | 3. YOUR RESPONSE ITEM # 6,PLEASE PROVIDE TOTAL | | | PERVIOUS AREA, TOTAL IMPERVIOUS AREA ALONG WITH TOTAL | | | SITE AREA | | | 4. YOUR RESPONSE ITEM # 9, WE HAVE NOT HEARD FROM | | | MANNY, 45TH ST. UTILITY PLAN APPROVED OR NOT?? | | | | | | PLEASE RESPONSE EACH ITEM TO EXPEDITE YOUR PERMIT. ALSO | | | PLEASE SEND A COPY OF YOUR RESPONSE OF THESE ITEMS. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-11-16 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-11-16 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2006-11-16 17:12:06 | PLEASE PROVIDE FOLLOWING INFO: | | | 1. CITY OF WPB STANDARD NOTES ON DRAWING FOR PARKING, | | | HANDICAP PARKING, PAINTPER CITY CODES ETC.,, MUST | | | MEET PER ADA,,SIDEWALK WIDTH, ITS SLOPE, DRIVEWAY | | | ETC., | | | 2. DUMPSTER DETAILS PER CITY OF WPB, &LOCATION ON | | | DWG, MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | | ON THE DRAWINGS. | | | 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, AND | | | GEOTECHNICAL REPORT | | | 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA | | | YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE | | | OR2.5"CRITERIA, ?PERVIOUS,IMPERVIOUS AREA CAL., | | | | | | 6. WHAT IS THE SITE AREA, ? | | | 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CAN DETERMINE THE BEST PIPE TO | | | CONNECT WITH THE STORM WATER FROM ALL OTHER STORM WATER | | | PIPES. PLEASE SHOW DETAIL OF THE CONTROL STRUCTURES | | | WITH ELEVATIONS.DID YOU USE EXFILTRATION TRENCH? | | | 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT | | | ETC., PLANS LIKE SHOWING SILT FENCE AROUND THE SITE | | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | 10. ALSO PLEASE SHOW ALL CATCH BASINS AROUND YOUR SITE | | | FOR STORM WATER DRAIN. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-21 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-21 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2008-05-21 14:00:01 | 1) ALL PIPING TO BE HYDROSTATIC TESTED FOR (2) HOURS. | | | | | | 2) FIRE HYDRANT REINSTALLATION TO BE INSPECTED, TESTED | | | AND APPROVED BY THIS OFFICE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-17 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-17 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-07-17 14:50:45 | *****APPROVED***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS PLAN REVIEWS HAVE BEEN | | | ADDRESSED;PLAN SHEETS A-2, E-3,FP-1AND FP-2 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-20 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-20 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2007-03-20 10:04:16 | *****UNSAT***** | | | | | | | | | PLEASE RE-ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE | | | PREVIOUS FIRE PLAN REVIEW: | | | | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | NFPA 241 TO CODE SUMMARY ON SHEET NO. A-1 | | | | | | 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION | | | SYSTEM , THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE | | | SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED TO SERVICE. | | | PLEASE ADD THIS STATEMENT TO SHEET NO. FP-1. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-13 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-13 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2006-12-13 16:03:35 | *****DENIED***** | | | | | | | | | | | | | | | 1.THE ADDRESS OF THE TRUCK WASH FACILITY SHALL BE IN | | | THE TITLE BLOCK OF EACH SUBMITTED PLAN. | | | | | | 2.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE | | | APPROPIATE ELEVATION (SHEET A-2).AS PER WEST PALM | | | BEACH CODE, THE NUMERICAL ADDRESS SHALL BE NO LESS THAN | | | 6" IN HEIGHT AND 1"IN WIDTH. | | | | | | 3.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). | | | | | | 6.ACCESS ROADS SHALL BE CAPABLE OF SUPPORTING AND | | | MAINTAINING 32 TONS OF FIRE EQUIPMENT. | | | | | | 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER SYSTEM.NFPA 13 (2002 EDITION) SHALL BE | | | REFERENCED. | | | | | | 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION | | | SYSTEM (IF NEEDED TO RELOCATE THE FIRE DEPT. CONN. AS | | | STATED ON SHEET FP-1.0) , THE FIRE DEPARTMENT SHALL BE | | | NOTIFIED WHEN THE SYSTEM IS SHUT DOWN AND WHEN IT IS | | | RETURNED TO SERVICE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-13 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-13 |
Time |
10:07 |
Sent To |
FIRE |
|
| Notes |
| 2008-05-13 10:07:23 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-13 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-13 |
Time |
09:40 |
Sent To |
B |
|
| Notes |
| 2008-05-13 09:41:01 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-21 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-21 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2007-06-12 11:36:07 | TO "COMM" BD#45--PLANS ROUTED TO ROBBIE FOR | | | PROCESSING--8/29/07 | | 2007-05-21 13:43:11 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-03-02 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-02-23 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2007-02-23 14:48:22 | TO "COMM" BD#62/PLANS FOUND TODAY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-13 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-04 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2006-10-17 15:13:31 | TO "COMM" BD#25 | | 2006-10-04 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-19 |
Time |
19:27 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-19 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2007-06-19 19:27:01 | ************PROVISO************** | | | | | | REGARDING COMMENT #4 AND RESPONSE: IT IS THE | | | DETERMINATION OF THE BUILDING OFFICIAL THAT AN AHU WITH | | | A NOMINAL CAPACITY OF 2000 CFM HAS A DESIGN CAPACITY IN | | | EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS | | | REQUIRED UNDER FBC, M 606.2.1. A FAN SHUT-DOWN TEST | | | WITH AN AUDIO/VISUAL SIGNAL WILL BE REQUIRED AT FINAL | | | INSPECTION. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-08 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-08 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2007-03-08 13:12:02 | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY. | | | | | | COMMENT #1: FIRE DAMPER MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS WILL BE REQUIRED ON SITE FOR INSPECION. | | | FBC,M 307.2 | | | | | | COMMENT #2: OK | | | | | | COMMENT #3: OK | | | | | | COMMENT #4: THIS ITEM DOES NOT APPEAR TO HAVE BEEN | | | ADDDRESSED ON PLAN. | | | | | | COMMENT #5: PLEASE INDICATE ON NOTE #6 HOW MANY STRAPS | | | ARE REQUIRED PER SIDE. | | | | | | | | | RONALD J REGUEIRO | | | 561-805-6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-10-30 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-10-30 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2006-10-30 18:23:25 | ------------DENIED-------------- | | | 1. PLEASE PROVIDE DETAIL FOR THE WALL SLEEVE/ LOUVER/ | | | FIRE DAMPER ATTACHMENTS SHOWING COMPLIANCE WITH FIRE | | | DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS PER | | | FBC,M 607.2 | | | | | | 2. AUXILIARY DRAIN PROTECTION IS REQUIRED ON AHU PER | | | FBC,M 307.2.3 | | | | | | 3. CONDENSATE DISPOSAL TO BE IN COMPLIANCE WITH FBC,M | | | 307.2.1 AND FBC 1503.6 | | | | | | 4. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED ON AHU | | | PER FBC,M SECTION 606 | | | | | | 5. PLEASE PROVIDE DETAIL FOR C.U. ATTACHEMNT TO SLAB | | | SHOWING COMPLIANCE WITH FBC,M 301.13 | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-06-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-20 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-20 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-03-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-07 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-07 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2007-03-07 16:11:05 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | CITY WEST PALM BEACH MUNICIPAL CODE | | | | | | 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE | | | 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT | | | LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH | | | THEY ARE INSTALLED. | | | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON | | | THE WATER SUPPLY TO THE BUILDING. SHEET C-3 NOW | | | INDICATES THE WATER SUPPLY CONNECTING TO TWO SOURCES. A | | | 2" LINE AND A 1-1/2" LINE. PLEASE CLARIFY. SECTION | | | 608.13.2. ALSO SEE SHT P-3 AT THE INCOMING MINIMUM 2" | | | WATER SUPPLY INDICATES A BACKFLOW REQUIRED. | | | | | | 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE | | | REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL | | | COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561) | | | 822-2279, OR E-MAIL [email protected]. UTILITY ORD. | | | 3434. | | | ****RESPONSE NOTED, BUT THE REQUIREMENT FOR A SAND/OIL | | | INTERCEPTOR SHALL BE DETERMINED BY ENVIRONMENTAL | | | COMPLIANCE. ARTICLE III SECTION 90-124(7) OF THE | | | MUNICIPAL CODE. LOOKING THROUGH APPENDIX "I", THERE ARE | | | 14 PAGES OF INFORMATION. IF THERE IS INFORMATION ON A | | | SAND/OIL INTERCEPTOR IN THESE PAGES, PLEASE INDICATE | | | WHICH PART AND SUBPART PRETAINS TO THIS INFORMATION. | | | WILL THIS INFORMATION INDCATE IF THE OVERFLOWS WILL | | | HAVE THE OIL INTERCEPTED? | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-06 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-06 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2006-12-06 14:22:35 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | CITY WEST PALM BEACH MUNICIPAL CODE | | | | | | 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE | | | 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT | | | LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH | | | THEY ARE INSTALLED. | | | | | | 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE | | | REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL | | | COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561) | | | 822-2279, OR E-MAIL [email protected]. UTILITY ORD. | | | 3434. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-08-28 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-07-19 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2007-08-28 16:32:21 | PASSED BASED ON DEP FINAL ORDER MODIFYING CONDITIONS OF | | | CERTIFICATION DATED AUGUST 24, 2007. | | 2007-08-15 09:12:31 | SPOKE WITH ENGINEER - HE IS WAITING ON DEP TO ISSUE A | | | MODIFIED POWER PLANT CERTIFICATION.EXPECTS IT BY | | | AUGUST 24. | | 2007-07-19 09:08:44 | WAITING ON A DETERMINATION BY THE OFFICE OF THE CITY | | | ATTORNEY TO COMPLETE THE ZONING REVIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-03-01 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-03-01 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2007-03-01 10:06:17 | FAILED | | | | | | 1) IN THE FEBRUARY 1, 2007 PLAN REVIEW RESPONSE, IT IS | | | STATED THAT THE SITE FALLS UNDER THE DEP POWER PLANT | | | SITING CERTIFICATION.NO EVIDENCE HAS BEEN PROVIDED TO | | | THE PLANNING AND ZONING DEPARTMENT THAT THE ENTIRE 920 | | | ACRE SOLID WASTE AUTHORITY SITE FALLS UNDER THE | | | PROVISIONS OF CHAPTER 403, PART II ELECTRIC POWER PLANT | | | AND TRANSMISSION LINE SITING.NOR HAS EVIDENCE BEEN | | | PROVIDED THAT SPECIFICALLY SHOWS THE TRUCK WASH | | | FACILITY INCLUDED IN A SITE PLAN APPROVED AS PART OF A | | | POWER PLANT SITING CERTIFICATION OR CONDITIONS OF | | | CERTIFICATION. | | | | | | 2) THE FOLLOWING COMMENTS FROM THE DECEMBER 5, 2006 | | | REVIEW STILL APPLY: | | | | | | A) THE CONSTRUCTION OF THE NEW BUILDING REQUIRES THE | | | APPROVAL OF A REVISION TO THE SITE PLANS APPROVED BY | | | THE CLASS A SPECIAL USE PERMIT.THE CITY COMMISSION | | | MAY GRANT THE APPROVAL AFTER A PUBLIC HEARING. | | | | | | 2) THE PLANS ARE INSUFFICIENT TO REVIEW FOR COMPLIANCE | | | WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS.NO | | | DIMENSIONED SITE PLAN OR LANDSCAPE PLANS WERE | | | SUBMITTED. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-12-05 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-12-05 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2006-12-05 15:51:00 | FAILED | | | | | | 1) THE CONSTRUCTION OF THE NEW BUILDING REQUIRES THE | | | APPROVAL OF A REVISION TO THE SITE PLANS APPROVED BY | | | THE CLASS A SPECIAL USE PERMIT.THE CITY COMMISSION | | | MAY GRANT THE APPROVAL AFTER A PUBLIC HEARING. | | | | | | 2) THE PLANS ARE INSUFFICIENT TO REVIEW FOR COMPLIANCE | | | WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS.NO | | | SITE PLAN OR LANDSCAPE PLANS WERE SUBMITTED. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|