Plan Review Details - Permit 06100011
Plan Review Stops For Permit 06100011
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-10-18 Cont ID  
Sent By mperson Date 2006-10-18 Time 09:50 Rev Time 0.33
Received By mperson Date 2006-10-18 Time 09:50 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By mperson Date 2006-10-05 Time 13:34 Rev Time 0.33
Received By mperson Date 2006-10-05 Time 13:33 Sent To PC
Notes
2006-10-05 00:00:00******UNSAT******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 ABOVE AND BELOW GROUND AND CORRESPONDING
 LENGTHS PER FBC-2004 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED ABOVE AND BELOW GROUND, ALL
 PIPE SIZES, (AND THE EDH NUMBER OF
 CORRUGATED STAINLESS STEEL TUBING FOR
 EACH PIPE SIZE BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS
 SYSTEM BTU LOAD AS WELL AS THE PROPOSED
 GAS SYSTEM BTU LOAD. PLEASE REFERENCE
 THE ATTACHED PERMIT INFORMATION SHEET
 INDICATING GAS AT SAID ADDRESS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING SYSTEM
 DUE TO THE FACT THAT GAS SYSTEMS ARE
 SIZED BY THE LONGEST LENGTH METHOD.
  
 5. NOTE: THE 2001 GAS PIPE SIZING TABLES
 ARE UNSAT. FBC-2004 FUEL GAS TABLES IN
 EFFECT.
  
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE KEEP AND REFERENCE THE
 ATTACHED CITY OF WEST PALM BEACH GAS
 PERMIT APPLICATION REQUIREMENTS FOR
 FUTURE GAS PERMIT APPLICATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 14:44 Sent To G
Notes
2006-10-14 14:44:20TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By mperson Date 2006-10-05 Time 14:49 Rev Time 0.00
Received By mperson Date 2006-10-04 Time 10:45 Sent To  
Notes
2006-10-04 00:00:00TO "G" BOX