Plan Review Details - Permit 06091103
Plan Review Stops For Permit 06091103
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-02 Cont ID  
Sent By lursu Date 2006-10-02 Time 16:24 Rev Time 0.00
Received By lursu Date 2006-09-29 Time 15:46 Sent To  
Notes
2006-10-02 00:00:00ATTACH PERMIT EXT #0001 UNDER PCN =
 74434321010020080
2006-09-29 00:00:00ADDRESS DOES NOT MATCH PCN #

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By shill Date 2006-10-25 Time 16:46 Rev Time 0.00
Received By shill Date 2006-10-25 Time 16:11 Sent To  
Notes
2006-10-25 16:54:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER ASSISTED SHALL BE AS SHOWN IN
 FIGURE 11-25, FBC11-4.13.6.SHOW MANEUVERING
 CLEARANCE, PULL SIDE, DOORS 103 AND 107.
  
 2.) FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2), ATTACHED LETTER FROM DCA.
  
 3.)IT APPEARS THAT WINDOWS 121 AND 118 ARE BEING
 REPLACED.DECLARE WIND DESIGN CRITERIA FBC1603.1.4,
 PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 4.)DECLARE INTERIOR FINISH CLASSIFICATION, FBC TABLE
 803.5.
  
 5.)THE LIFE SAFETY PLAN DOESN'T HAVE ANY DIMENSIONS
 ON IT, PLEASE PROVIDE.
  
 6.)PROVIDE DESIGN LOAD INFORMATION FOR THE MECHANICAL
 EQUIPMENT ON THE ROOF.
  
 7.)FBC TABLE 601, TYPE IIIA REQUIRES 1 HOUR ON THE
 ROOF AND THE FLOORS.MECHANICAL AND PLUMBING SHEETS
 SHOW PENETRATIONS.PENETRATIONS ARE TO COMPLY WITH
 SECTION 712.
  
 8.)THE SCHEDULE ON M-2.01 IS NOT CONSISTENT WITH FBC
 TABLE 1509.7.IT IS NOT CLEAR AS TO DISTANCE
 REQUIREMENTS FOR DIMENSIONS BETWEEN THE CATEGORIES.
  
 9.)THE SQUARE FOOT AREA ON THE ENERGY CALCS DO NOT
 MATCH THE ARCHITECTURALS.THEY SHOULD BE THE SAME.
  
 10.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS,
 FBC13-103.1.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2006-10-23 Time 20:21 Sent To  
Notes
2006-10-24 18:45:15****** UNSAT ***********
  
 ** PLEASE SEE PLANS ARE BEING SUBMITTED FOR 2ND FLR
 BUILD OUT.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS BOUND
 TOGETHER INTO TWO COMPLETE SETS. PLEASE SEE SETS AS
 SUBMITTED ARE LOOSE AND FALLING APART INTO INDIVIDUAL
 SHEETS.
 FBC 106.1 ADMIN SECT.
  
 2) NOTE: PLEASE INDICATE THE FOLLOWING MINIMUM RELEVANT
 CODE FOR DESIGN AND COMPLIANCE.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2004 FBC.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION FOR FBC CHAPTER
 13 FOR MIN CONTROLS OF LIGHTING FOR NEW SPACE/ BUILD
 OUT.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.
 PLEASE INDICATE THE MAX TIMES OF ON THE TYPE OF DEVICES
 INSTALLED FOR OVER RIDES(4HRS MAX ON TIMER TYPE, 30MINS
 MAX ON OCCUPANT SENSOR TYPE).
 PLEASE INDICATE THE SCHEDULING IF USED ON A SYSTEM.
  
 4) NOTE: PLEASE INDICATE THE NEW OR EXISTING LIGHTING
 REQUIRED FOR EGRESS ON STAIRS. PLEASE SEE 7.8.1.3 AND
 7.9.2.2 FOR NORMAL AND EMERGENCY.
  
 5) NOTE: PLEASE SEE SOME SYMBOLS SHOWN ON PLANS WHICH
 ARE NOT SHOWN ON LEGEND?
  
 6) NOTE: PLEASE SEE RISER AND PANELS ARE MIS-LABLED.
 LA/LB, "A" AND "B".
 106.1.2 FBC ADMIN SECT
  
 7) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM /
 EXT LTS WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS
 WERE DERIVED.
 220.3,220.10,220.11,220.13,
  
 9) NOTE: PLEASE SEE ROOF TOP GFI RECEPT IS BEING SHOWN
 CIRCUITEDTO THE CU, WHICH IS NOT PERMITTED.
 THIS IS REQUIRED TO CONTAIN A NEUTRAL ETC.
 2002 NEC.(TOO MANY SECTIONS TO LIST)
  
 10) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. ROOM USAGES FOR LOCATION OF THE ELECTRICAL
 PANELS NEEDS TO BE DECLARED.
 110.26, 240.24, 408.7 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-23 20:21:35IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By mwennerg Date 2006-10-31 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2006-10-31 Time 14:54 Sent To  
Notes
2006-10-31 15:02:47***DENIED***
  
 1) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 2) PLEASE SHOW TRAVEL DISTANCE DIMENSIONS ON LIFE
 SAFETY PLANS.
  
 3) ONLY (1) MEANS OF EGRESS IS ILLUSTRATED BUT (2)
 EXITS ARE PROVIDED.
  
 4) SEPARATE SHOP DRAWINGS ARE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 6) FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE.
  
 7) CONSTRUCTION, ALTERATION AND DEMOLITION TO BE IN
 COMPLIANCE WITH NFPA 241.
  
 8) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED
 NOT TO EXCEED 75' TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By lmartine Date 2006-10-31 Time 17:22 Rev Time 0.00
Received By lmartine Date 2006-10-03 Time 16:54 Sent To  
Notes
2006-10-17 13:43:26TO "COMM" BD#55
2006-10-03 00:00:00WAITING FOR "COMM"BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By rregueir Date 2006-10-23 Time 18:58 Rev Time 0.00
Received By rregueir Date 2006-10-23 Time 17:57 Sent To  
Notes
2006-10-23 19:02:37----------------DENIED---------------
  
 1. MECHANICAL PLANS WERE NOT SIGNED AND SEALED BY THE
 ENGINEER.
  
 2. ROOMS 102 & 109 ARE NOT IN COMPLIANCE WITH FBC,M
 601.4 WHICH REQUIRES BALANCED RETURN FROM ALL HABITABLE
 ROOMS. PLEASE SHOW COMPLIANCE WITH EXCEPTION #2 UNDER
 THIS SECTION OR DEMONSTRATE HOW BALANCED RETURN IS TO
 BE ACHIEVED IN THESE AREAS.
  
 3. ROOF PENETRATION DETAIL SHOWS REFRIGERANT PIPING
 PENETRATING A CONCRETE SLAB TO THE ROOF. PIPING
 PENETRATING CONCRETE FLOORS OR CEILINGS SHALL BE
 PROVIDED WITH A SLEEVE OR THIMBLE PER FBC,M 1107.2.1.
 PLEASE PROVIDE DETAIL SHOWING COMPLIANCE.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-30 Cont ID  
Sent By kstevens Date 2006-10-30 Time 15:46 Rev Time 0.00
Received By kstevens Date 2006-10-30 Time 14:21 Sent To  
Notes
2006-10-30 16:54:02DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T-1 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. PLEASE CORRELATE THE INDEX WITH
 SHEETS SUBMITTED. SECTION 106.1.1.
  
 2. SUBMIT INFORMATION ON REVELANT DESIGN CODE. SECTION
 106.1.2.
  
 3. INDICATE OCCUPANCY. SECTION 106.3.5.1.1(2).
  
 4. SUBMIT A DETAIL FOR THE BREAK ROOM, (104), SINK.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 5. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 6. SHT P-1.01 PLUMBING FIXTURE P-1 ELKAY LR17720 NOT
 APPROVED FOR AN ACCESSIBLE SINK. MAXIMUM SINK DEPTH IS
 6-1/2". MODEL SHOWN INDICATES THE SINK DEPTH AS 7-1/2".
 SECTION 11-4.24.4. (SEE ATTACHED SHEET).
  
 7. SHT P-1.O1 DOMESTIC WATER RISER ISOMETRIC. A WATER
 HAMER ARRESTOR IS REQUIRED FOR THE DISHWASHER ON EH
 WATER LINE. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By lmartine Date 2006-11-02 Time 17:22 Rev Time 0.00
Received By lmartine Date 2006-10-31 Time 16:09 Sent To  
Notes
2006-10-31 16:10:26ZONING REVIEW-
  
 - INTERIOR BUILDING ONLY; NO ZONING REVIEW REQ'D.
 - EXTERIOR ELEVATIONS REVIEWED UNDER SEPARATE PERMIT.
  
 -MATT FLIS 822-1445