| 2006-10-24 18:45:15 | ****** UNSAT *********** |
| | |
| | ** PLEASE SEE PLANS ARE BEING SUBMITTED FOR 2ND FLR |
| | BUILD OUT. |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS BOUND |
| | TOGETHER INTO TWO COMPLETE SETS. PLEASE SEE SETS AS |
| | SUBMITTED ARE LOOSE AND FALLING APART INTO INDIVIDUAL |
| | SHEETS. |
| | FBC 106.1 ADMIN SECT. |
| | |
| | 2) NOTE: PLEASE INDICATE THE FOLLOWING MINIMUM RELEVANT |
| | CODE FOR DESIGN AND COMPLIANCE. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION FOR FBC CHAPTER |
| | 13 FOR MIN CONTROLS OF LIGHTING FOR NEW SPACE/ BUILD |
| | OUT. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2, 13-415.2.ABC.1. |
| | PLEASE INDICATE THE MAX TIMES OF ON THE TYPE OF DEVICES |
| | INSTALLED FOR OVER RIDES(4HRS MAX ON TIMER TYPE, 30MINS |
| | MAX ON OCCUPANT SENSOR TYPE). |
| | PLEASE INDICATE THE SCHEDULING IF USED ON A SYSTEM. |
| | |
| | 4) NOTE: PLEASE INDICATE THE NEW OR EXISTING LIGHTING |
| | REQUIRED FOR EGRESS ON STAIRS. PLEASE SEE 7.8.1.3 AND |
| | 7.9.2.2 FOR NORMAL AND EMERGENCY. |
| | |
| | 5) NOTE: PLEASE SEE SOME SYMBOLS SHOWN ON PLANS WHICH |
| | ARE NOT SHOWN ON LEGEND? |
| | |
| | 6) NOTE: PLEASE SEE RISER AND PANELS ARE MIS-LABLED. |
| | LA/LB, "A" AND "B". |
| | 106.1.2 FBC ADMIN SECT |
| | |
| | 7) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM / |
| | EXT LTS WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS |
| | WERE DERIVED. |
| | 220.3,220.10,220.11,220.13, |
| | |
| | 9) NOTE: PLEASE SEE ROOF TOP GFI RECEPT IS BEING SHOWN |
| | CIRCUITEDTO THE CU, WHICH IS NOT PERMITTED. |
| | THIS IS REQUIRED TO CONTAIN A NEUTRAL ETC. |
| | 2002 NEC.(TOO MANY SECTIONS TO LIST) |
| | |
| | 10) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS. ROOM USAGES FOR LOCATION OF THE ELECTRICAL |
| | PANELS NEEDS TO BE DECLARED. |
| | 110.26, 240.24, 408.7 ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-10-23 20:21:35 | IN ELEC FOR REVIEW. |