| 2007-01-24 17:40:14 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON THE REVISED RISER AND REVISED PANEL |
| | SCHEDULE(S) SUBMITTED. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, SEE COMMENT BELOW. |
| | |
| | ** PREVIOUS REVIEW NOTE #4** |
| | PLEASE SEE POSSIBLE MISSING GFI FOR KITCHEN COUNTER |
| | SPACE. 210.52C1,210.8A6. |
| | |
| | 5) NOTE:NO, PLEASE STILL SEE MISSING RECEPTACLE IN |
| | KITCHEN FOR 2FT OR MORE OF WALL SPACE. |
| | |
| | ** PREVIOUS REVIEW NOTE #5 ** |
| | PLEASE SEE SOME MISSING RECEPTS PER 210.52 AS THESE |
| | ROOMS WHERE ELECTRICAL IS TAKING PLACE APPEAR TO BE |
| | REWIRED? |
| | PLEASE KNOW, DUE TO THE ALTERATION IN DWELLING, PLEASE |
| | INDICATE EXISTING RECEPTS (E) . |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 6) NOTE: NO, PLEASE SEE THREE SETS OF PLANS ARE BEING |
| | SUBMITTED. PLEASE SEE ALL THREE ARE NEW AND ARE SIGNED, |
| | DATED AND SEALED BY THE ARCHITECT; HOWEVER THE THIRD |
| | SET OF PLANS ARE NOT SIGNED, DATED OR SEALED BY THE |
| | ENGINEER. PLEASE KNOW THAT ONLY TOW SETS ARE REQUIRED, |
| | HOWEVER IF THREE SETS ARE BEING SUBMITTED FOR REVIEW |
| | AND FOR STAMPING THEN ALL THREE SETS ARE REQUIRED TO BE |
| | SIGNED , DATED AND SEALED. FS 471.025, FAC |
| | 61G15-23.002. |
| | |
| | ** PREVIOUS REVIEW NOTE #6** |
| | PLEASE SEETHERE ARE A COUPLE OF SEALS FROM ENGINEER |
| | WHICH ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION ON |
| | SAID SEAL. |
| | FS 471.025 |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE:NO, PLEASE SEE NEW RISER NOTES FOR REVISED |
| | RISER SUBMITTED. PLEASE SEE AS SHOWN, THIS SERVICE IS |
| | BEING DONE A 250 AMP SERVICE. PLEASE SEE 310.15B6 FOR |
| | MINIMUM SIZES FOR THE SEC?S. |
| | ** PLEASE CALL TO GO OVER THIS COMMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE #8** |
| | PLEASE SEE SERVICE ENTRANCE CONDUCTORS SHALL BE SIZED |
| | PER 310.15B6 AT A MINIMUM. SERVICE SHOWN IS 250A'S. |
| | 240.4 |
| | |
| | 9) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE #9** |
| | PLEASE ADJUST METER CAN SIZE FOR SERVICE (300A MIN). |
| | 110.3, 90.7, 240.4 |
| | |
| | 10) NOTE: NO, SAME NOTE DEPENDING ON THE OUTCOME OF THE |
| | SERVICE BEING PROVIDED. AS SHOWN THE GEC IS TOO SMALL. |
| | |
| | ** PREVIOUS PLEASE SEE 250.66 AS THE MIN SIZE OF THE |
| | GROUNDING ELECTRODE CONDUCTOR SHALL BE #2 BASED ON THE |
| | NEW SEC'S WHICH WILL BE REQUIRED FOR THE SERVICE SIZE |
| | AS SHOWN. |
| | |
| | 11) NOTE: NO, PLEASE SEE THERE ARE SOME CIRCUITS NOW |
| | BEING SHOWN FOR THE EXISTING PANEL WHICH SEEM TO BE |
| | DEDICATED/MOTOR/APPLIANCE CIRCUITS; HOWEVER IT IS |
| | UNCLEAR WHERE THESE ARE FIGURED INTO THE MAIN LOAD |
| | CALCULATIONS. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE #11** |
| | PLEASE PROVIDE PANEL SCHEDULE AND LOAD INFORMATION FOR |
| | EXISTING PANEL"A". SEEMS TO BE ONLY A 5A DIFFERENCE |
| | IN LOAD. |
| | 240.4, 220.31B |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE:NO, PLEASE SEE THIS ELECTRIC WATER HEATER IS |
| | STILL SHOWN IN THE CLOSET. |
| | |
| | ** PREVIOUS REVIEW NOTE #14** |
| | PLEASE SEE 422.17, AS THE ELEC HWH SEEMS TO BE SHOWN IN |
| | THE CLOTHES CLOSET. PLEASE PROVIDE MIN SEPARATION |
| | REQUIRED OR RELOCATE. |
| | |
| | 15) NOTE: OK. |
| | |
| | *** NEW NOTES *** |
| | |
| | |
| | 16) NOTE: PLEASE CORRELATE RISER DIAGRAM AND PANELS. |
| | PLEASE SEE THE RISER SHOWS A 100A MBC PANEL, PANEL |
| | SHOWS A 100A PANEL WITH A 150A MCB AND SHOWS A 60AMP |
| | MAIN BREAKER BEING BACK-FED.???? |
| | PLEASE SEE OF THIS 60A BREAKER IS NOT THE SERVICE |
| | ENTRANCE RATED MAIN, PLEASE SUBMIT DETAILS IF INDEED |
| | THIS IS THE CASE. |
| | 17) NOTE: PLEASE CORRELATE FEEDERS /SERVICE ENTRANCE |
| | CONDUCTORS TO THIS EXISTING PANEL AND NEW PANEL. PLEASE |
| | SEE PANEL SCHEDULE INDICATES THESE AS FEEDERS, WHEN |
| | THEY ARE SERVICE ENTRANCE CONDUCTORS. PLEASE ALSO SEE |
| | THE CONDUCTORS ON RISER DO NOT CORRELATE WITH THAT OF |
| | THE PANEL SCHEDULE WHICH SHOWS A DIFFERENT CONDUCTOR |
| | SIZE. |
| | |
| | 18) NOTE: PLEASE SEE RISER IS SHOWING *EQUIPMENT |
| | GROUNDING CONDUCTORS* FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6, |
| | AND 250.24B. PLEASE SEE THIS IS PARALLELING THE |
| | NEUTRAL. |
| | |
| | 19) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. THIS IS ONLY BEING GIVEN AS A NOTICE AT |
| | THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |